Manufacturers must produce
an exploding array of products faster than ever while reducing costs
and increasing operational efficiencies to previously unreachable
levels. To meet these demands, companies are increasing the amount
of automation within their plants. While this additional electronic
equipment is helping boost production, it is also contributing to
an increase in harmonic distortion problems. Variable frequency
drives often comprise a large portion of this new equipment, so
drive users are taking a close look at harmonics issues and evaluating
potential mitigation strategies.
Harmonics defined Harmonics are
deviations from the base AC line voltage and current waveforms.
Most electrical circuits in North America operate at 60-Hz frequency.
A harmonic frequency is a multiple of this base frequency. In a
60-Hz system, for example, the second harmonic would be 120 Hz,
the third would be 180 Hz, and so on. Any frequency other than the
base creates distortion. The more harmonics present, the more distortion
in the electrical waveform.
That's the technical definition.
In its most basic description, however, harmonic distortion is simply
electrical noise. Non-linear loads, which are drawing power throughout
a facility, create this noise. If the plant's non-linear load is
significantly larger than the linear load, there is a potential
for harmonic distortion problems.
Other sources
While
drives certainly contribute to harmonic problems, they aren't the
only causes. In fact, any equipment that converts alternating current
(AC) to direct current (DC) can create harmonic distortion. This
includes many of the systems used on the plant floor, such as welders,
arc furnaces, process controllers, lighting systems, DC power supplies
and uninterruptible power supplies.
Harmonics problems usually aren't
catastrophic, but they can cause equipment overheating, erratic
system operation, nuisance tripping and noise transfer to other
loads. This can lead to equipment damage and production downtime.
In extreme cases, utilities can impose penalties on power users
or even disconnect a facility from the power grid until harmonic
problems have been resolved.
Clearing
the confusion
Although awareness and concern
about harmonics has grown considerably in recent years, it's often
misunderstood, inaccurately diagnosed and ineffectively mitigated.
Therefore, before rushing out and purchasing additional hardware
to solve a perceived harmonic problem, it's important to first address
a few basic questions.
- Is there actually a harmonic
problem within the system?
- If so, exactly what is causing
the problem?
- Based on the application and
the identified cause, which of the many solutions is the best
one?
As the number of drives used in automation
systems grows, so too does the misconception that they are always
the single largest cause of harmonic problems. While drives comprise
a sizable portion of non-linear loads, they are only one element
in the harmonic equation. That's why, before making any final conclusions,
it's important to analyze every electrical load that has the potential
to cause problems. The bottom line is that not all installations
have a problem, and not all problems are drive-related. In fact,
there are hundreds of thousands of drives operating in the field
without necessitating harmonic mitigation.
Measuring harmonics Because utility
power feeds supply multiple customers, a harmonic problem in one
location can severely distort the power supply and cause problems
for others. IEEE519-1992 is the North American harmonics standard
for power utilities, and is often imposed on large consumers and
medium voltage systems. Total harmonic distortion limits are recommended
based upon the type of installation. This specification also has
become common in low-voltage systems.
The ability to measure harmonics
is important for isolating the cause and recommending potential
remedies. In many cases, utilities use special meters that are connected
to the power lines feeding a plant to measure the total harmonic
distortion. Other instruments, such as high-speed spectrum analyzers,
determine the waveforms and help isolate the root of a harmonic
problem. Once users have identified the problem, they can implement
a number of approaches to reduce or eliminate the effects of these
unwanted frequencies (harmonics).
Eliminating bad vibes As
the occurrence of harmonics becomes more prevalent, drive manufacturers
are offering more advanced solutions to address the problem. Some
are small and inexpensive, while others require additional hardware
and are more technically complex. While many of these solutions
exceed IEEE 519-1992 requirements and may provide added benefits,
such as improved power factor,
it's important to evaluate
the requirements of the application and select the solution that
offers the best fit.
Drives using pulse width modulation
technology with the least distortion today are 12- and 18-pulse
AC variable frequency drives. They produce little transient noise
and can offer a total harmonic distortion of less than three percent.
And with a 0.95 power factor, or better, these drives eliminate
the need for power factor correction capacitors and tuned inductors.
Power factor is the percentage of
usable real power (in Watts) to the utility-supplied apparent power
(in volt-amps). The closer a product can come to achieving a 1.0
power factor, the better. In most cases, a power factor of 0.85
or higher is considered sufficient by the utility.
What's important to understand is
that there is more than one way to approach the harmonics problem.
And the most expensive method may not always be the best choice.
It's not uncommon for power users to oversize the solution to eliminate
a perceived harmonics problem. But this oversizing correlates directly
to cost increases that could be avoided by better assessing harmonic
mitigation options. Table 1 provides a cost-performance-size comparison
of various drive harmonic mitigation solutions.
Making an informed decision When addressing
harmonics issues, users should keep the following in mind. First,
not all installations have a problem. Second, if there is a problem,
the solution doesn't always have to involve adding more hardware
to the system. Third, while plants need to take precautions, keep
in mind that each application is different.
The bottom line is to make an informed
decision. Measure the load, determine how many potential harmonic
sources exist, assess future conditions and carefully consider the
various options available. Then, based on cost and benefits provided,
select the solution that fits the application.
Drive harmonic mitigation
technique |
Comments |
6-pulse AC drive without a DC link choke |
The simplest design of the AC drives. Doesn't
provide any harmonic mitigation capability. |
6-pulse AC drive with a DC link choke |
The choke provides reduction of low frequency
harmonics produced by the drive. |
Input line reactor |
Reduces surges or spikes on the line. Provides
enough harmonic mitigation on distribution systems that
have a very small percentage of non-linear loading. |
Tuned and non-tuned harmonic filters |
Cost and performance effective but can cause
power system resonance in some installations, especially
if there are any future system impedance changes. |
12-pulse converter with auto transformer |
Reasonable performance and cost effective,
but does not guarantee meeting IEE519-1992 without analysis.
Less component count and design complexity compared
to an 18 pulse. An auto transformer will have a lower
cost and smaller physical size (easier to mount in the
enclosure line-up) than an isolation transformer. |
12-pulse converter with isolation transformer |
Reasonable performance and cost effective,
but does not guarantee meeting IEE519-1992 without analysis.
Less component count and design complexity compared
to an 18 pulse. An isolation transformer supplies slightly
less THD than an auto transformer and non-proprietary
designs are more readily available. |
18-pulse converter with auto transformer |
Can guarantee meeting IEEE519-1992 limits
at the drive input terminals without analysis provided
the input power phases are balanced within 1 percent.
An auto transformer will have a lower cost and smaller
physical size (easier to mount in the enclosure lineup)
than an isolation transformer. |
18-pulse converter with isolation transformer |
Can guarantee meeting IEEE519-1992 limits
at the drive input terminals without analysis provided
the input power phases are balanced within 2 percent.
An isolation transformer supplies less THD than an auto
transformer and non-proprietary designs are more readily
available. |
Regenerative active front end |
Has the added feature of regenerative braking
back to the line. Generally only cost effective on large
common bus systems with many drives and/or high horsepower
ratings. |
Active power filter |
Most technologically advanced solution but
generally only cost effective on large common bus systems. |
Photos courtesy Rockwell Automation
Bruce Hachey is engineering manager
for the Allen-Bradley Custom & Configured Drives Business, Rockwell
Automation, a product group that specializes in adding additional
value to standard drive products. George Zenke is a product manager
with Rockwell Automation. For more information, visit http://www.rockwellautomation.com.
|