Eliminating Voltage Notching on the Distribution System
When Silicon Controlled
Rectifiers (SCRs) are used in electrical controls, it is possible to experience
line voltage distortion in the form of "notches" in the waveform.
The types of equipment that utilize SCRs in converters or rectifiers,
to change the ac line voltage to a dc voltage, and thus experience notching
include DC motor speed controls and induction heating equipment.
Line notches are just
that - an irregularity in the voltage waveform that appears as a notch
as illustrated in Figure 1. They are typically present in the waveform
during SCR commutation. Commutation occurs when an SCR in one phase is
turned on to turn off an SCR in another phase. For this very small duration
of time, a short circuit is created between the two phases. With a short
circuit, the current increases and the voltage decreases. The decrease
in voltage is defined as a line notch.

Figure 1
The notch can appear at
any point during the half cycle since the point of commutation changes
as the firing point of the SCR changes. Since the speed of a dc motor
is a function of the voltage applied to the motor, at low speed the notch
may appear near the end of the half cycle. At higher speeds, the notch
may appear near the beginning of the half cycle. In the most severe cases,
the voltage is reduced to zero, creating an extra zero crossover or point
where voltage normally changes polarity. This extra zero voltage crossover
causes the biggest problems.
Zero Voltage Crossing
During a normal cycle
of sinusoidal voltage, the voltage crosses the "x" axis, or
zero, at 0 degrees and again at 180 degrees. During normal conditions,
there are two zero crossovers in each cycle. Some electronic equipment
is designed to be triggered on the zero crossover or when the voltage
is zero. This allows equipment to be activated without the surge currents
or inrush currents that would be present if switched while voltage was
present. Some equipment uses the zero crossovers for an internal timing
signal. DC drives use the zero crossovers to determine when to fire the
SCR. When two dc drives are operating on the same distribution system,
they can disturb the electrical system so that one dc drive operating
at low speed will affect the other dc drive that is operating at a higher
or different speed. To prevent the "power cross talk" between
dc drives, it is normal practice to install an isolation transformer ahead
of each dc drive.
When notches are present,
particularly in three phase equipment, we can experience extra zero crossovers.
Instead of two zero crossovers in each cycle of voltage, we can actually
experience four notches. These extra notches may tell other equipment
to "turn on." That means the equipment may turn on at the wrong
time resulting in damage.
Eliminated voltage
notching
Eliminating voltage notching
requires that the source of the notching (commutation) be isolated or
buffered from other sensitive equipment using the same distribution system.
Considering the DC drive or other SCR controller as a source of "notch
voltage" and the characteristics of the distribution system, it is
only required that other sensitive equipment not share the same voltage
source or a single voltage source. The simplest method to use to eliminate
the voltage notch is to isolate each piece of equipment with an input
transformer. If the impedance of the distribution system is low, generally
dc drives will not create a severe voltage notch that affects other equipment.
However, if the impedance of the distribution system is high (soft line)
than voltage notching will occur and likely impact other equipment. An
alternate method can use line reactors to reduce the voltage notch and
reduce the possibility of affecting other equipment. It is important to
note that notches created by dc drives will normally not affect the dc
drive that is causing the notching. It is other equipment that can be
affected.
It is important that we
understand and consider where other sensitive equipment connects to that
same voltage source. In order to protect the sensitive equipment, we must
reduce the notches before they get to that equipment. We will do this
through the creation of a simple voltage divider network.
Figure 2
If we add impedance, in
the form of inductive reactance, in series with the SCR controller, and
between the controller and the point of other equipment connection, (point
B) then the notch voltage will distribute itself across the new impedance
(reactance) and the pre-existing line to source impedance. If the added
impedance (L3=L1=L2)is one-half as much
as was already present, then 1/3 of the notch voltage is dropped across
the new impedance and two thirds still remains at the point of common
connection with the other equipment.
Figure 3
If the new impedance is
equal to the existing input impedance(L3
= L1 + L2), then
the notch distributes equally across the two impedances. One-half the
original notch voltage is now present at the point of common connection
(B).
Notice that if the new
impedance is added anywhere else but between the SCR controller and the
sensitive equipment, it will have minimal impact on the notch voltage.
Placing the reactance on the opposite side of point B offers no improvement
to the notching problem.
Use a 3%
impedance reactor to
solve three phase voltage notching problems. Experience shows that 3%
impedance is normally sufficient to reduce the notch voltage, at the point
of common connection with other sensitive equipment, to about 50% or less
of it's initial value (depth). This eliminates the multiple zero crossings
and typically solves the interference problems with neighboring equipment.
It is typically not recommended to use a 5% impedance reactor with SCR
circuits because the reactor not only reduces the depth of the notch,
but it also increases the notch width. Excess impedance could increase
the notch width (time) too much causing problems in the controller itself.
Increasing the notch width may be seen as a loss of line voltage by some
sensitive equipment. If the impedance of the distribution system is low
(1%), then a 3% impedance reactor will result in a very small notch depth.
Low impedance or stiff distribution systems often have no notching problems.
High impedance or soft distribution systems may require a larger value
of impedance to reduce voltage notching problems. It is important to note
that too much impedance can result in severe loss of input voltage starving
the equipment which can cause under voltage tripping problems.
>Voltage notching can introduce
harmonics on the distribution system. It is important that distribution
system be designed with the lowest possible impedance. Prior to the use
of power electronic equipment, designing an electrical system with impedance
served to reduce the short circuit current or fault current in a system.
With the use of power electronic equipment and its self contained current
limiting feature, the need for system impedances to control fault current
has been reduced.
|