|
|
 |
System
Compatibility of Adjustable Frequency Drives
GENERAL
The characteristics of Adjustable Frequency Drives,
as an electrical system component, are not well understood. They have
been blamed for almost every electrical problem that can not be explained.
It is true that AFDs have characteristics not typical of more conventional
components like motors, starters, and transformers. Fortunately, the most
common AFDs of the 1990’s are very easy to understand. By far, the largest
installed base of AFDs is the Pulse Width Modulated, voltage source type.
The unique features of the PWM, AFD can be defined and with those definitions,
successfully applied for process improvements and for energy savings.
For simplicity, four categories will be explained.
- As a source for the ac motor (Energy Transfer component).
- As a load for the distribution system ( Energy Consumption component).
- As a load for the ac motor (Energy Absorption component).
- As a source for the distribution system (Energy Storage component).
Energy Transfer component
As a source for the ac motor, the task of the AFD is
to connect to the terminal of the motor a voltage potential that can provide
a positive or negative polarity. The positive polarity will allow current
to flow into the motor from the AFD. The negative polarity will allow current
to flow from the motor to the AFD. When polarity changes, in a symmetrical
fashion, the rate at which the change occurs becomes the applied frequency
for the connected voltage potential.
Since the function of
the AFD is to control 3 phase ac motors, a successful operation depends
on the ac motor experiencing a voltage source that provides the following
characteristics.
- symmetrical waveform
(mirrored imaged)
- balanced waveform
(+/- 2%)
- low impedance source
(less than 1%)
- 3 phase source (120
degree displacement)
- controlled volts/hertz
relationship through the speed range. The area under the voltage curve
must be fixed to the frequency. A 480V, 60Hz source and a 240V, 30Hz
source have the same volts per hertz relationship. The relationship
is 8 volts per hertz.
When connecting an ac motor directly to the ac supply
line, the utility supplies a voltage that meets the listed characteristics.
The resulting current waveform will, for the most part, produce a symmetrical
waveform. The torque (or work) that the motor is able to produce is proportional
to that current waveform. For a fixed terminal voltage (supplied by the
utility), the rms value of the current will indicate how much work the motor
is performing.
When connecting an ac
motor to an AFD, the resulting current waveform is also symmetrical. As
the polarity of the terminal voltage changes, the frequency of the current
waveform will change. The current produces the magnetic fields whose interaction
produces the motor torque and results in the rotation of the motor (rotor).
Changes in motor rotation stop when one of two factors occurs. The first,
and most important, occurs when there is insufficient voltage to produce
additional current that produces the torque necessary to change rotational
speed. The second occurs when the rotational speed of the rotor matches
the speed of the rotating magnetic field (applied frequency).
There is no significant
difference between the current in the motor operated directly across the
ac line or connected to the output terminals of an AFD. The real current
circulating in the motor always comes from the utility or power source
connected to the input terminals of the AFD. The AFD merely connects the
input source to the terminals of the motor. The AFD does not produce power
or store power. The AFD is simply a connecting device that allows a limited
amount of power to flow from a source to a load. The motor circuit carries
real and reactive current. Unlike the motor operating directly across
the line, the AFD operated motor does not allow the reactive current to
flow in the incoming distribution system. The reactive portion of the
motor current will flow in the output (inverter) section of the AFD. Only
real current flows from the incoming distribution system through the AFD
and into the motor. This single characteristic of PWM, voltage source
AFDs means that there will always be fewer system losses when operating
an ac motor with an AFD compared to an ac motor operated directly across
the line.
Energy Consumption component
As a load for the distribution system, the PWM, voltage
source AFD will permit only a limited amount of energy transfer. Unlike
other types of loads, like motors and transformer, the short circuit conditions
that can exist with AFDs are much, much less than typically found in distribution
systems. Protection from short circuit demands is normally controlled
by fuses or other circuit protection devices. An important feature of
the AFD is its current limiting capability.
As a connecting device,
the AFD can interrupt the flow of current in microseconds. This means
that no high rms values of fault current will ever exist. The connecting
semiconductor switch operates as a extremely fast recloser for values
of current within the AFD rating. The semiconductor switch operates as
a manually resettable circuit breaker when the instantaneous value of
current exceeds the trip limit of the AFD. It is rare that fuses or other
protective devices would function faster than the electronic current limiting
that exists in AFDs.
As a result of the current
limiting feature, the short circuit current let-through is well below
the typical values defined by branch circuit protection found with fuses
and circuit breakers. In practice, and for simplicity, branch circuit
protection for AFDs is selected as if the circuit were a standard motor
circuit. This is very conservative, but less confusing than attempting
to redefine local electrical codes. When input fuses are specified by
the AFD supplier, those fuses have, most often, been recommended to conform
to some testing criteria such as UL.
When the AFD, as a load,
is compared to the ac motor, electrical parameters such as power factor
and surge currents are more favorable than expected. A typical ac motor
may have a power factor of 0.8. The AFD controlling that same motor would
have a power factor much closer to unity. That difference in power factor
means that less current will flow in the distribution system. Less current
means lower system losses or greater system efficiency. The losses in
the AFD are similar to the losses experienced by the voltage drop across
the contacts of a motor starter. As the current increases, the voltage
drop will increase. As the current decreases, the voltage drop will decrease.
In some applications where power reduces as speed reduces (fans), the
efficiency of the system can improve significantly.
Energy Absorption component
As a load for the ac motor, the AFD is expected to
absorb some energy when the mechanical energy is converted by the motor
to electrical energy. This occurs when the motor rotates faster than the
applied frequency. The motor, now acting as a generator, will force energy
(current) back to the AFD. Since the standard AFD will transfer power
in one direction only, the energy supplied by the motor must be absorbed
or that energy will cause the AFD to shut down on an over voltage event.
Three factors must be
considered when the motor is operating as a generator. The first is that
the motor will operate as a voltage source, supplying current to the AFD
as long as the rotational speed of the motor is greater than the synchronous
speed of the motor. The second factor is that no generator action can
occur unless there is a magnetic field in the motor. Unlike a dc motor
which has a separately excited field, the ac motor depends on the operation
of the AFD to maintain the field. If the AFD sends no supply voltage to
the motor, then the motor can not send energy back to the AFD. The third
factor is that the AFD will rectify the ac voltage being supplied by the
motor and store that voltage in the filter capacitor (dc bus) of the AFD.
Since the AFD can not send that motor voltage back to the distribution
system, rectification will continue until the voltage being stored in
the AFD filter capacitor exceeds the over voltage limit. The amount of
energy that can be stored is very small, so the limit is reached very
rapidly. When the limit is reached, the AFD will shut down.
This shut down will result
in the AFD being disconnected from the ac motor. Since the ac motor is
disconnected, the magnetic field of the ac motor will disappear and the
motor can no longer operating as a generator. The motor will coast to
a stop unless the AFD fault is cleared and the AFD is restarted. To prevent
a shutdown of the AFD when the motor is operating as a generator (regeneration),
the voltage being stored on the filter capacitor can be controlled by
discharging that stored energy through a power consuming path. Typically,
an electronically switched resistor is connected across the filter capacitor
of the AFD (Dynamic Braking Module). When the voltage on the capacitor
reaches a present value, the resistor is connected across the filter circuit.
When the voltage drops below a lower present value, the resistor is disconnected
from the filter circuit. This action can continue until there is no more
energy to dissipate and the voltage on the filter capacitor remains below
the present value.
Energy Storage component
As a source for the distribution system, the standard
PWM, AFD is prevented from sending energy back to the distribution system.
This is due to the 3 phase, full wave bridge rectifier on the input circuit
of the AFD. In the event of a fault on the input to the AFD, no energy
can flow from the AFD to the distribution system. Unlike other power converters
like dc motor controllers, Current Source Inverters and arc Furnaces,
the PWM, AFD can only transfer energy from the input supply to the motor.
Per IEEE standard 141-1993
(Redbook), section 4.2.5, adjustable speed drives can contribute current
from the motor to a short circuit... . Based on the preceding statement,
it would be nature that the following questions would be raised. What
percent FLA of the motor load would adjustable speed drives allow? What
are the drive’s let through values? Are these maximum permissible short
circuit values indicated on the drive’s label? Is the maximum rated short
circuit number and interrupting rating for the drive indicated on the
drive’s label?
Other power converters
can feed energy back to the distribution system, however that energy can
be controlled and in most cases can only contribute a very small portion
of energy to the fault condition when comparing to the energy that can
be provided by transformers and line operated motors. In all cases where
AC drives or DC drives are applied, the value of rms current that is transferred
from the ac supply to the motor or from the motor to the ac supply will
be limited to the maximum ratings of the AC drive or DC drive.
Of VSDs, only DC drives
and Current Source Inverters (AC Drives) have the natural capability to
feed current back to the ac line and thus contribute to shorts on the
ac line. However, in the case of short circuit on the line side of the
drive, it is most likely that these drives would detect that condition
and terminate operation.
In terms of maximum permissible
short circuit values, only the DC drive lacks the capability of electronically
controlling the instantaneous value of the current. The DC drive is typically
a line commutated, 3 phase rectifier which connects the ac line to the
armature of the dc motor. With a 60 Hz supply, the connections from the
ac line to the motor can be commutated (turned off) every 8.3 milliseconds
or approximately one-half cycle. Since the dc motor is providing the current,
the question of how much current will the dc motor contribute to the line
short will depend on the motor’s ability to increase in armature current
during that 8.3 milliseconds. In the event of a short on the ac line,
the dc motor can continue to send current out of the motor back to the
shorted line as long as the field of the dc motor is energized and the
motor is rotating. Due to the variations that would exist, it would be
difficult to predict a maximum value. In practice, the characteristics
of the incoming fuses are used to define the maximum let through value.
The I^2T rating of the fuse defines when the fuse should open.
In Current Source AC drives
(CSIs), the current path can be controlled electronically. The inverter
or output section of the CSI can interrupt the flow of current and limit
the let through current. Once again, it is likely that the CSI will detect
the fault condition on the ac line and terminate operation, thus limiting
how much current flows back to the ac line. Like the DC motor, the ac
motor used with a CSI drive must maintain it’s magnetic field if it is
to send current back to the ac line. Unlike the dc motor which has a separately
excited field, the ac motor depends on the CSI drive to electronically
maintain its magnetic field. A major difference between the DC drive and
the CSI drive is the large reactor that exists between the ac line and
the ac motor in the CSI drive. This link reactor will prevent current
from changing rapidly and will limit the current that the CSI drive can
contribute to the ac line fault. In practice, it is normal to use the
I^2T value of the line side fuses to define the maximum let through current.
In actual operation, the value of current that can be contributed by a
CSI drive is less than the FLA of the motor and will not be sustained
for more than one half cycle of the supply frequency.
With PWM, voltage source
AC drives (AFDs), no energy can be returned to the distribution system
unless the AFD is a special line Regenerative type drive. In the event
of a short circuit on the ac line, the input supply voltage to the drive
is reduced to a single phase supply. Since the motor is buffered from
the conditions on the ac line by the filter section of the drive, it continues
to operate in a controlled manner. Current will not increase in the motor
since the motor believes that nothing has happened to it’s voltage supply
to cause any changes. If motor current does not increase, than there will
be no change reflected to the incoming supply line and thus no contribution
to the short circuit condition on the ac line.
Summary
Some types of adjustable speed drives can contributed
to the fault current on a ac line short. PWM adjustable (frequency) speed
drives do not contributed to ac line shorts. The typical PWM, AFD is designed
to transfer power from the ac line to the ac motor. In doing so, improvements
in power factor result which reduce the value of total current that the
distribution system must handle. Energy flow is a one way process so PWM
AFDs can not add energy to faults that occur on the distribution system.
By optimizing the voltage applied to the motor for many applications,
a general reduction in total energy consumption will occur. In many applications,
modifying the operating parameters of the application can result in overall
energy savings.
|