Catalogs > Automation Systems Catalog > I/O > In-Cabinet Distributed I/O > 1734 POINT I/O
1734 POINT I/O
| Introduction | Product Design | Environmentals and Certifications | I/O Adapter and Communication Interface Modules | 1734D POINTBlock I/O Modules |
| Digital I/O Modules | Analog I/O Modules | Specialty I/O Modules | Power Supplies | Terminal Base Assemblies and RTBs |
POINT I/O has three classes of communication interfaces.
An I/O adapter module provides an isolated DC/DC converter between field 24V DC and 5V backplane. You can connect up to 13 I/O modules and an I/O adapter with a maximum of 10 A field power. Additional I/O modules require the use of one or more POINT I/O 24V DC expansion power units. An I/O adapter supports up to a maximum of 63 I/O modules. The I/O adapter modules are available for ControlNet, DeviceNet (with and without subnet connectivity), EtherNet/IP, or PROFIBUS DP networks.
The DeviceNet Communication Interface module interfaces I/O modules to the DeviceNet link and converts field 24V DC power to 5V DC backplane power. The backplane power is derived from the DeviceNet network and is not isolated. I/O circuits require a power supply specified for the I/O module connected to the right of the communication interface module. You can connect up to 13 I/O modules to the DeviceNet Communication Interface module, with a maximum of 10 A field power.
A DeviceNet Communication Interface module with integrated I/O is also available (1734D POINTBlock). POINTBlock modules offer up to 16 integrated I/O circuits. A POINTBlock module interfaces the integrated I/O circuits and attached I/O modules to the DeviceNet link, and converts 24V DC DeviceNet power to 5V DC. The backplane power is derived from the DeviceNet network and is not isolated. I/O circuits require a power supply specified for the built-in I/O. You can connect up to 13 I/O modules to each POINTBlock module with a maximum of 350 mA field power.
|
|
I/O Adapter and Communication Interface Modules Product Selection
| Cat. No. | Description | Compatible with POINT Guard I/O | Supports Expansion Power Supplies | Number of I/O Points, Max.¬ |
| DeviceNet | ||||
| 1734-PDN | DeviceNet Communication Interface Each POINT I/O module counts as a node on the main DeviceNet network. Total backplane current of I/O modules cannot exceed 1.3 A. |
Yes | No | 136 |
| 1734D POINTBlock I/O | DeviceNet Communication Interface with Integrated I/O Includes up to 16 built-in I/O points. The DeviceNet interface presents the integrated I/O as a single DeviceNet node. Each POINT I/O module counts as a node on the main DeviceNet network. Total backplane current of I/O modules cannot exceed 1.0 A. |
No | No | 120 |
| 1734-ADN | DeviceNet I/O Adapter A total of 63 POINT I/O modules can be assembled on a single DeviceNet node. |
No | Yes | 504 |
| 1734-ADNX | DeviceNet I/O Adapter with Expansion Port A total of 63 POINT I/O modules can be assembled on a single DeviceNet node. Expansion network port allows for a DeviceNet subnet. Increases the reach of DeviceNet from 500 to 1500 meters. Increases nodes per DeviceNet scanner from 63 to more than 126 (dependent on DeviceNet scanner capacity). |
No | Yes | 504 |
| ControlNet | ||||
| 1734-ACNR | ControlNet I/O Adapter A total of 63 POINT I/O modules can be assembled on a single ControlNet node. Up to 25 direct connections and 5 rack connections are allowed. |
No | Yes | 504 |
| EtherNet/IP | ||||
| 1734-AENT | EtherNet/IP Twisted Pair Media I/O Adapter A total of 63 POINT I/O modules can be assembled on a single EtherNet/IP node. Refer to the User Manual to determine the ratings for direct and rack connections allowed. |
Yes | Yes | 504 |
| 1734-AENTR | 2-Port EtherNet/IP I/O Adapter Module Inlcudes 2 EtherNet/IP ports, configured as embedded switch. Supports star, tree, linear, and ring topologies. Up to 20 direct connections and 5 rack optimized connections (digital I/O only) are allowed. Total backplane current of I/O modules cannot exceed 0.8 A. |
Yes | Yes | 504 |
| PROFIBUS DP | ||||
| 1734-APB | PROFIBUS DP I/O Adapter A total of 63 POINT I/O modules can be assembled on a single PROFIBUS DP node. |
No | Yes | 504 |
| ¬ Using the eight-point digital I/O modules. | ||||
Specifications
| Cat. No. | Input Voltage Range | Field Side Power Requirements | Inrush Current | Power Consumption (W) at 24V | Power Dissipation, Max. | PointBus Current (mA) |
| 1734-PDN | 11…25V DC DeviceNet specification | 400 mA @ 24V DC (+4% = 25V DC) | 6 A for 5 ms | 8.0 W | 1.2 W @ 25V | 1300¬ |
| 1734D Series§ | 350 mA @ 24V DC (+4% = 25V DC) | 8.2 W | 2.0 W @ 24V | 1000 | ||
| 1734-ADN(X) | 10…28.8V DC | 400 mA @ 24V DC (+20% = 28.8V DC) | 6 A for 10 ms | 8.0 W | 2.8 W @ 28.8V | 1000T |
| 1734-ACNR | 425 mA @ 24V DC (+20% = 28.8V DC) | 8.0 W | 2.8 W @ 28.8V | 1000T | ||
| 1734-AENT | 400 mA @ 24V DC (+20% = 28.8V DC) | 4.5 W | 2.8 W @ 28.8V | 700 | ||
| 1734-AENTR | 400 mA @ 24V DC (+20% = 28.8V DC) | 10.4 W | 6.3 W @ 28.8V | 800 | ||
| 1734-APB | 400 mA @ 24V DC (+20% = 28.8V DC) | 8.0 W | 2.8 W @ 28.8V | 1000T | ||
| ¬ 1300 mA @ 5V DC ±5% (4.75…5.25V). T 1000 mA @ 5V DC ±5% (4.75…5.25V). 700 mA when input voltage < 17V DC. § See 1734D POINTBlock Modules selection table for integrated I/O information. |
||||||