In-Cabinet Distributed I/O

Catalogs > Automation Systems Catalog > I/O > In-Cabinet Distributed I/O > 1734 POINT I/O

1734 POINT I/O

Introduction Product Design Environmentals and Certifications I/O Adapter and Communication Interface Modules 1734D POINTBlock I/O Modules
Digital I/O Modules Analog I/O Modules Specialty I/O Modules Power Supplies Terminal Base Assemblies and RTBs
I/O Adapter and Communication Interface Modules

POINT I/O has three classes of communication interfaces.

An I/O adapter module provides an isolated DC/DC converter between field 24V DC and 5V backplane. You can connect up to 13 I/O modules and an I/O adapter with a maximum of 10 A field power. Additional I/O modules require the use of one or more POINT I/O 24V DC expansion power units. An I/O adapter supports up to a maximum of 63 I/O modules. The I/O adapter modules are available for ControlNet, DeviceNet (with and without subnet connectivity), EtherNet/IP, or PROFIBUS DP networks.

The DeviceNet Communication Interface module interfaces I/O modules to the DeviceNet link and converts field 24V DC power to 5V DC backplane power. The backplane power is derived from the DeviceNet network and is not isolated. I/O circuits require a power supply specified for the I/O module connected to the right of the communication interface module. You can connect up to 13 I/O modules to the DeviceNet Communication Interface module, with a maximum of 10 A field power.

A DeviceNet Communication Interface module with integrated I/O is also available (1734D POINTBlock). POINTBlock modules offer up to 16 integrated I/O circuits. A POINTBlock module interfaces the integrated I/O circuits and attached I/O modules to the DeviceNet link, and converts 24V DC DeviceNet power to 5V DC. The backplane power is derived from the DeviceNet network and is not isolated. I/O circuits require a power supply specified for the built-in I/O. You can connect up to 13 I/O modules to each POINTBlock module with a maximum of 350 mA field power.


Click to enlarge - 1734 I-O Adapter_BW


Click to enlarge - 1734PDNComms_BW


I/O Adapter and Communication Interface Modules Product Selection

Cat. No. Description Compatible with POINT Guard I/O Supports Expansion Power Supplies Number of I/O Points, Max.¬ 
DeviceNet
1734-PDN DeviceNet Communication Interface
• Each POINT I/O module counts as a node on the main DeviceNet network.
• Total backplane current of I/O modules cannot exceed 1.3 A.
Yes No 136
1734D POINTBlock I/O DeviceNet Communication Interface with Integrated I/O
• Includes up to 16 built-in I/O points.
• The DeviceNet interface presents the integrated I/O as a single DeviceNet node.
• Each POINT I/O module counts as a node on the main DeviceNet network.
• Total backplane current of I/O modules cannot exceed 1.0 A.
No No 120
1734-ADN DeviceNet I/O Adapter
• A total of 63 POINT I/O modules can be assembled on a single DeviceNet node.
No Yes 504
1734-ADNX DeviceNet I/O Adapter with Expansion Port
• A total of 63 POINT I/O modules can be assembled on a single DeviceNet node.
• Expansion network port allows for a DeviceNet subnet.
• Increases the reach of DeviceNet from 500 to 1500 meters.
• Increases nodes per DeviceNet scanner from 63 to more than 126 (dependent on DeviceNet scanner capacity).
No Yes 504
ControlNet
1734-ACNR ControlNet I/O Adapter
• A total of 63 POINT I/O modules can be assembled on a single ControlNet node.
• Up to 25 direct connections and 5 rack connections are allowed.
No Yes 504
EtherNet/IP
1734-AENT EtherNet/IP Twisted Pair Media I/O Adapter
• A total of 63 POINT I/O modules can be assembled on a single EtherNet/IP node.
• Refer to the User Manual to determine the ratings for direct and rack connections allowed.
Yes Yes 504
1734-AENTR 2-Port EtherNet/IP I/O Adapter Module
• Inlcudes 2 EtherNet/IP ports, configured as embedded switch.
• Supports star, tree, linear, and ring topologies.
• Up to 20 direct connections and 5 rack optimized connections (digital I/O only) are allowed.
• Total backplane current of I/O modules cannot exceed 0.8 A.
Yes Yes 504
PROFIBUS DP
1734-APB PROFIBUS DP I/O Adapter
• A total of 63 POINT I/O modules can be assembled on a single PROFIBUS DP node.
No Yes 504
¬ Using the eight-point digital I/O modules.

Specifications

Cat. No. Input Voltage Range Field Side Power Requirements Inrush Current Power Consumption (W) at 24V Power Dissipation, Max. PointBus Current (mA)
1734-PDN 11…25V DC DeviceNet specification 400 mA @ 24V DC (+4% = 25V DC) 6 A for 5 ms 8.0 W 1.2 W @ 25V 1300¬ 
1734D Series§  350 mA @ 24V DC (+4% = 25V DC) 8.2 W 2.0 W @ 24V 1000
1734-ADN(X) 10…28.8V DC 400 mA @ 24V DC (+20% = 28.8V DC) 6 A for 10 ms 8.0 W 2.8 W @ 28.8V 1000T 
1734-ACNR 425 mA @ 24V DC (+20% = 28.8V DC) 8.0 W 2.8 W @ 28.8V 1000T 
1734-AENT 400 mA @ 24V DC (+20% = 28.8V DC) 4.5 W 2.8 W @ 28.8V 700‡ 
1734-AENTR 400 mA @ 24V DC (+20% = 28.8V DC) 10.4 W 6.3 W @ 28.8V 800
1734-APB 400 mA @ 24V DC (+20% = 28.8V DC) 8.0 W 2.8 W @ 28.8V 1000T 
¬ 1300 mA @ 5V DC ±5% (4.75…5.25V).
T 1000 mA @ 5V DC ±5% (4.75…5.25V).
‡ 700 mA when input voltage < 17V DC.
§ See 1734D POINTBlock Modules selection table for integrated I/O information.