In-Cabinet Distributed I/O

Catalogs > Automation Systems Catalog > I/O > In-Cabinet Distributed I/O > 1734 POINT I/O

1734 POINT I/O

Introduction Product Design Environmentals and Certifications I/O Adapter and Communication Interface Modules 1734D POINTBlock I/O Modules
Digital I/O Modules Analog I/O Modules Specialty I/O Modules Power Supplies Terminal Base Assemblies and RTBs
Digital I/O Modules

The 1734 digital I/O modules support:


POINT Digital AC Input Modules

Cat. No. Inputs Voltage Category Input Delay Time, On to Off¬  On-State Current, Min. Input Impedance, Nom. Off-State Current, Max. PointBus Current (mA) Power Dissipation, Max. Terminal Base Unit
1734-IA2 2 Non-isolated, Sink 120V AC (65V AC…132V AC) 20 ms hardware filter plus 1…64 ms digital filter programmable in increments of 1 ms 4.0 mA @ 65V AC, 60 Hz 10.6 kW 2.7 mA @ 43V AC 75 mA 0.1 W @ 132V AC 1734-TB, 1734-TBS, 1734-TOP, or 1734-TOPS
1734-IA4 4 Non-isolated, Sink
1734-IM2 2 Non-isolated, Sink 220V AC (159V AC…264V AC) 6.2 mA @ 159V AC, 60 Hz 22.3 kW 2.9 mA @43V AC
1734-IM4 4 Non-isolated, Sink
¬ On-to-Off delay is the time from the signal dropping below valid to recognition by the module.

POINT Digital AC Output Modules

Cat. No. Outputs Voltage Category Output Current Rating PointBus Current (mA) Power Dissipation, Max. Terminal Base Unit
1734-OA2 2 Non-isolated, Source 120/220V AC (74V AC…264V AC) 1.5 A (2 channels @ 0.75 A each) 75 mA 2 W @ 264V AC 1734-TB, 1734-TBS, 1734-TOP, or 1734-TOPS
1734-OA4 4 Non-isolated, Source 2.0 A (750 mA per output) 3.5 W @ 264V AC

POINT Digital DC Input Modules

The 1734-IB4D module is a 4-channel 24V DC input module with short-circuit and open-wire diagnostics. Catalog numbers ending with "S" are safety-rated.

Cat. No. Inputs Voltage Category Input Delay Time, On to Off On-State Current, Min. On-State Current, Max. Off-State Current, Max. PointBus Current (mA) Power Dissipation, Max. Terminal Base Unit
1734-IB2 2 Sink 24V DC (10V DC…28.8V DC) 0.5 ms hardware + (0…65 ms selectable)¬  2 mA 5 mA 1.5 mA 75 mA 0.7 W @ 28.8V DC 1734-TB or 1734-TBS
1734-IB4 4 Sink 1.0 W @ 28.8V DC 1734-TB, 1734-TBS, 1734-TB3, or 1734-TB3ST 
1734-IB4D 4 Sink, diagnostic 24V DC (11V DC…28.8V DC) 2 mA 15 mA 50 mA 0.6 W max @ 28.8V DC 1734-TB, 1734-TBS, 1734-TOP, or 1734-TOPS
1734-IB8 8 Sink 24V DC (10V DC28.8V DC) 0.5 ms hardware + (0…65 ms selectable)¬  2 mA 5 mA 1.5 mA 75 mA 1.6 W @ 28.8V DC 1734-TB or 1734-TBS
1734-IB8S 8 Sink, safety-rated 24V DC (11V DC28.8V DC) 16.2 ms max¬  3.3 mA 5 mA 1.3 mA 175 mA 1.4 W 1734-TB, 1734-TOP, 1734-TOP3
1734-IV2 2 Source 24V DC (10V DC…28.8V DC) 0.5 ms hardware + (0…65 ms selectable)¬  2 mA 5 mA 1.5 mA 75 mA 0.7 W @ 28.8V DC 1734-TB or 1734-TBS
1734-IV4 4 Source 1.0 W @ 28.8V DC 1734-TB, 1734-TBS, 1734-TB3, or 1734-TB3ST 
1734-IV8 8 Source 1.6 W @ 28.8V DC 1734-TB or 1734-TBS
¬ Input On-to-Off delay time is the time from a valid input signal to recognition by the module.
T 1734-TB3 or 1734-TB3S recommended.

POINT Digital DC Output Modules

Catalog numbers ending with "E" are electronically protected. Catalog numbers ending with "S" are safety-rated. The 1734-OB2EP module has 24V DC electronically protected, fast-switching high-current outputs.

Cat. No. Outputs Voltage Category Output Current Rating, Max. PointBus Current (mA) Power Dissipation, Max. Terminal Base Unit
1734-OB2 2 Source 24V DC (10V DC28.8V DC) 2.0 A per module, 1.0 A per channel 75 mA 0.8 W @ 28.8V DC 1734-TB or 1734-TBS
1734-OB2E 2 Source, electronically protected 24V DC (10V DC…28.8V DC) 2.0 A per module, 1.0 A per channel 75 mA 0.8 W @ 28.8V DC 1734-TB or 1734-TBS
1734-OB2EP 2 Source, electronically protected, fast-switching high-current 24V DC (10V DC…28.8V DC) 4.0 A per module, 2.0 A per channel 75 mA 3.4 W @ 28.8V DC 1734-TB or 1734-TBS
1734-OB4 4 Source 24V DC (10V DC28.8V DC) 3.0 A per module, 1.0 A per channel 75 mA 1.2 W @ 28.8V DC 1734-TB or 1734-TBS
1734-OB4E 4 Source, electronically protected 24V DC (10V DC…28.8V DC) 3.0 A per module, 1.0 A per channel 75 mA 1.2 W @ 28.8V DC 1734-TB, 1734-TBS
1734-OB8 8 Source 24V DC (10V DC28.8V DC) 3.0 A per module, 1.0 A per channel 75 mA 2.0 W @ 28.8V DC 1734-TB or 1734-TBS
1734-OB8E 8 Source, electronically protected 24V DC (10V DC28.8V DC) 3.0 A per module, 1.0 A per channel 75 mA 2.0 W @ 28.8V DC 1734-TB, 1734-TBS
1734-OB8S 8 Source, safety-rated 24V DC (10V DC28.8V DC) 1 A max per point 190 mA 1.9 W 1734-TB, 1734-TOP, 1734-TOP3
1734-OV2E 2 Sink, electronically protected 24V DC (10V DC…28.8V DC) 2.0 A max per module, 1.0 A per output 75 mA 0.8 W max @ 28.8V DC 1734-TB or 1734-TBS
1734-OV4E 4 Sink, electronically protected 24V DC (10V DC…28.8V DC) 3.0 A max per module
1.0 A per output
75 mA 1.2 W max @ 28.8V DC 1734-TB or 1734-TBS
1734-OV8E 8 Sink, electronically protected 24V DC (10V DC28.8V DC) 3.0 A per module, 1.0 A per channel 75 mA 2.0 W max @ 28.8V DC 1734-TB, 1734-TBS

POINT Digital DC Configurable Input/Output Module

The 1734-8CFG module is a 24V DC I/O module with 8 self-configuring points. The 1734-8CFGDLX module offers 8 self-configuring points and DeviceLogix capabilities. Each of the I/O points can be a DC input or output.

Cat. No. Inputs/Outputs Voltage Category Input Voltage Range Output Voltage Range PointBus Current (mA) Power Dissipation, Max. Terminal Base Unit
1734-8CFG 8, self-configuring 24V DC 11V DC…28.8V DC 10V DC28.8V DC 100 mA 2.6 W @ 28.8V DC 1734-TB, 1734-TBS, 1734-TOP, 1734-TOPS
1734-8CFGDLX 8, self-configuring, with DeviceLogix

POINT Digital Contact Output Modules

Cat. No. Outputs Voltage Range Output Delay Time, On to Off, Max.¬  Contact Resistance, Initial Output Current Rating, Max. Leakage Current, Off-State Output, Max PointBus Current (mA) Power Dissipation, Max. Terminal Base Unit
1734-OW2 2 Form A N.O. relays 5…28.8V DC @ 2.0 A resistive
48V DC @ 0.5 A resistive
125V DC @ 0.25 A resistive
125V DC @ 2.0 A resistive
240V DC @ 2.0 A resistive
26 ms 30 mW 2.0 A per channel 1.2 mA and bleed resistor thru snubber circuit @ 240V AC 80 mA 0.5 W 1734-TB or 1734-TBS
1734-OW4 4 Form A N.O. relays
1734-OX2 2 Form C isolated N.O./N.C. relays 10 ms 30 mW 2.0 A per channel 2.0 mA and bleed resistor thru snubber circuit @ 240V AC 100 mA
¬ Time from valid output off signal to relay deenergization by module.