Catalogs > Automation Systems Catalog > I/O > In-Cabinet Distributed I/O > 1794 FLEX I/O
1794 FLEX I/O
| Introduction | Product Design | Typical Configurations | Specifications | I/O Communication Adapters | Digital I/O Modules |
| Analog, Thermocouple, and RTD I/O Modules | Specialty I/O Modules | HART Smart Instrumentation | Terminal Bases and Accessories | Power Supplies | Encompass Partner Products |
A FLEX I/O adapter module interfaces FLEX I/O modules to an I/O scanner port across a communication network. The FLEX I/O adapter module contains a built-in power supply that converts 24V DC to 5V DC for the backplane to power the FLEX I/O modules. One adapter communicates with up to eight I/O modules, allowing connection to 256 digital input/output points, or 64 analog input points/32 analog output points, or a mix to meet your needs. Conformal coated versions of standard modules have the letter K in the last position of the catalog number, before the series designation. Extreme environment versions have the letters XT in this position.
| 1794-AENT | 1794-ACN15, 1794-ACNR15♠ , 1794-ACN15K, 1794-ACNR15XT∆ |
1794-ADN, 1794-ADNK♠ |
1794-ASB, 1794-ASBK♠ , 1794-ASBLT♣ |
1794-ASB2, 1794-ASB2K♠ |
1794-APB | 1794-APBDPV1 | 1794-FLA§ | |
| Network | EtherNet/IP | ControlNet | DeviceNet | Universal Remote I/OUniversal Remote I/O | Universal Remote I/O | PROFIBUS DP | PROFIBUS DP | Local I/O to a FlexLogix controller |
| I/O Module Capacity | 8 | 8 | 8 | 8 | 2 | 8 | 8 | 8 |
| Communication Rate | 10/100 Mbps | 5 Mbps | 125 Kbps 250 Kbps 500 Kbps |
57.6 Kbps 115.2 Kbps 230.4 Kbps |
All rates up to 12.0 Mbps | — | ||
| Thermal Dissipation, Max. | 24.9 BTU/hr at 24.0V DC | 15.7 BTU/hr at 19.2V DC | 26 BTU/hr at 19.2V DC | 1.7 BTU/hr at 31.2V DC | 26 BTU/hr at 19.2V DC | 25.6 BTU/hr at 19.2V DC | ||
| Power Dissipation, Max. | 7.3 W at 19.2V DC | 6.6 W at 19.2V DC | 7.6 W at 19.2V DC | 4.6 W | 7.68 W at 19.2V DC | 4.2 W at 19.2V DC | — | |
| Power Supply 24V Current Load (mA) | 440 mA | 400 mA | 300 mA | 330 mA | 330 mA | 330 mA | 309 mA | — |
| Power Supply Input Voltage, Nom. | 24V DC | |||||||
| Operating Voltage Range | 19.2…31.2V DC (includes 5% AC ripple) | |||||||
| ♠ Catalog numbers ending with (K) = Conformal Coated. ∆ Catalog numbers ending with XT = Extreme environment version. The 1794-ACNR15 and 1794-ACNR15XT adapters accept redundant ControlNet cable media. The 1794-ACN15 and 1794-ACN15K are non-redundant. § The 1794-FLA is an extended local adapter for a FlexLogix controller. ♣ Use the 1794-ASBLT Series D adapter when communicating with Classic PLC-5/15 or PLC-5/25 via Remote I/O. The 1794-ASBLT Series D adapter is a replacement for the 1794-ASB Series D adapter only when communicating with PLC-5/15 or PLC-5/25. |
||||||||
DeviceNet Straight 5-pin Open Plug to 5-pin Micro Male Connector
|
The DeviceNet straight 5-pin open plug to 5-pin micro male connector can be used in place of the 5-position open style plugs for DeviceNet, making it easier to connect I/O modules to the network, as well as reducing potential for miswiring and saving wiring time.
The DeviceNet straight 5-pin open plug to 5-pin micro male connector is compatible with:
- 1734D POINTBlock I/O
- 1790 CompactBlock LDX I/O
- 1791D CompactBlock I/O
- 1794-ADN FLEX I/O DeviceNet adapter
- 1799 Embedded I/O
| Cat. No. | Description |
| 1799-DNC5MMS | Female Open-style DeviceNet Y Adapter (Qty. 5) |
| 1799-DNC100MMS | DeviceNet straight 5-pin open plug to 5-pin micro male connector (Qty. 100) |