Catalogs > Automation Systems Catalog > I/O > In-Cabinet Distributed I/O > 1797 FLEX Ex I/O
1797 FLEX Ex I/O
| Introduction | Product Design | Typical Configurations | Specifications | Communications Adapter | Digital I/O Modules |
| Analog I/O Modules | Counter I/O Modules | HART Smart Instrumentation | Terminal Bases | Power Supplies | Accessory Products |
HART (Highway Addressable Remote Transmitter) is an open protocol designed to connect analog devices. For HART connectivity, select from products available from Rockwell Automation and our Encompass partners.
Select a HART Interface
| For Your Application | Select | Description |
| 1794 FLEX I/O 1797 FLEX Ex I/O |
FLEX I/O and FLEX Ex modules designed for distributed HART systems. | |
| 1756-IF8H 1756-OF8H |
Rockwell Automation analog I/O modules for use in ControlLogix chassis | |
| MVI56-HART | Prosoft interface | |
HART Interface Modules
FLEX and FLEX Ex HART analog modules (IE8H and OE8H) are ideal for use in applications that need connection with FDT (Field Device Tool) compatible asset management software, such as the Rockwell Software FieldCare HART Communication bundle or Endress + Hauser Fieldcare. Device Type Management (DTM) programs and drivers are provided on the website.
- FLEX HART analog modules can be used on ControlNet or EtherNet/IP. The FLEX Ethernet adapter requires firmware v3.1, which is flash upgradeable, to support these modules.
- Each HART field device is wired to its own input or output channel:
- 8 single-ended channels
- does not support multi-drop
- 2- or 3-wire devices
- 8 single-ended channels
- For use with FlexLogix, the modules must be used on distributed rail with ControlNet adatper and not on local rail.
- HART commands can be transmitted by unscheduled message::
- sample RLL subroutines available
- currently limited to of one instance of RLL subroutine per module, one channel at at time
- sample RLL subroutines available
HART Analog Input Module
| Cat. No. | Number of Inputs | Input Signal Range⋆ | Update Time, Module from Adapter | Step Response to 99% of Full Scale | Power Dissipation, Max. | Terminal Base Unit |
| 1797-IE8H | 8 single-ended | 0…20 mA | 200…1600 ms | 80 ms | 5.2 W | 1797-TB3, 1797-TB3S |
| ⋆ Each module's channels are selectable. Supports pass-through of HART commands as unscheduled ControlNet messages. Compatible with FDT software packages. |
||||||
HART Analog Output Module
| Cat. No. | Number of Outputs | Output Signal Range⋆ | Step Response to 99% of Full Scale | Power Dissipation, Max. | Terminal Base Unit |
| 1797-OE8H | 8 single-ended | 4…20 mA | 4 ms | 6.1 W | 1797-TB3, 1797-TB3S |
| ⋆ Each module's channels are selectable. Supports pass-through of HART commands as unscheduled ControlNet messages. Compatible with FDT software packages. |
|||||
1797-OE8 and -OE8H Output Voltage/Current Capability
|
Certifications
| Cat. No. | Certifications⋆ |
| 1797-IE8H | CENELEC: II (1) 2G EEx ia/ib IIB/IIC T4 II (1D) (2D) UL, C-UL: Class I Division 1 Groups A...D T4 Class I Zone 1 AEx ib/[ia] IIC T4 Class II Division 1 Groups E, F, G; Class III FM: Class I Division 1 Groups A...D T4 Class I Zone 1 AEx ib/[ia] IIC T4 |
| 1797-OE8H | CENELEC: II (1) 2G EEx ia/ib IIB/IIC T4, II (1D)(2D) |
| ⋆ See the Product Certification link at http://www.ab.com for declarations of Conformity, Certificates, and other certification details. For additional certification information, see the FLEX Ex System Certification manual, publication 1797-6.5.6. | |