On-Machine Distributed I/O

Catalogs > Automation Systems Catalog > I/O > On-Machine Distributed I/O > 1792 ArmorBlock MaXum I/O

1792 ArmorBlock MaXum I/O

Introduction Product Design Communication Specifications Typical Configurations
ArmorBlock MaXum Digital I/O ArmorBlock High-Current I/O ArmorBlock MaXum Cable Bases Mating Cables
Specifications

General Specifications

  ArmorBlock MaXum High-Current ArmorBlock
Enclosure Type Rating IP67, NEMA 4X and 6P IP52, NEMA Type 5 and Type 12
Mounting Type On-Machine Panel
Operating Temperature -25…60 °C (-13…140 °F) -20…60 °C (-4…140 °F)
Nonoperating Temperature -25…80 °C (-13…176 °F) -40…85 °C (-40…185 °F)
Relative Humidity 5…95% noncondensing 5…95% noncondensing
Operating Shock 30 g peak acceleration, 11(±1) ms pulse width
Nonoperating Shock 50 g peak acceleration, 11(±1) ms pulse width
Vibration 10 g at 10…500 Hz
Certifications⋆  CSA, CE, C-Tick, ODVA CSA, CE, C-Tick, ODVA
  
⋆ When product is marked. See the Product Certification link at www.ab.com for Declarations of Conformity, Certificates, and other certification details.

Dimensions and Weights

Cat. No. Dimensions (HxWxD), Approx. Weight
8-connector I/O blocks 48.26 x 68.6 x 174 mm⋆ 
(1.9 x 2.7 x 6.85 in⋆ )
0.6 kg
(1.3 lb)
4-connector I/O blocks 48.26 x 68.6 x 120 mm⋆ 
(1.9 x 2.7 x 4.7 in⋆ )
0.5 kg
(1.1 lb)
2-connector block 48.26 x 68.6 x 120 mm⋆ 
(1.9 x 2.7 x 4.7 in⋆ )
0.5 kg
(1.1 lb)
High-Current block 67 x 197 x 78 mm
(2.7 x 7.8 x 3.1 in)
0.7 kg
(1.5 lb)
Cable bases   0.2 kg
(0.5 lb)