Catalogs > Automation Systems Catalog > I/O > On-Machine Distributed I/O > 1792 ArmorBlock MaXum I/O
1792 ArmorBlock MaXum I/O
| Introduction | Product Design | Communication | Specifications | Typical Configurations |
| ArmorBlock MaXum Digital I/O | ArmorBlock High-Current I/O | ArmorBlock MaXum Cable Bases | Mating Cables |
Digital Input Blocks
| Cat. No. | Number of Inputs | Number of Connectors | Diagnostics | Voltage, On-State Input, Nom. | Voltage, On-State Input, Range | Current, Off-State Input, Max. | DeviceNet Current (mA) |
| 1792D-16BVT0D | 16 Sink/Source | 8 | Connector-level | 24V DC | 10V DC…25V DC | 1.5 mA | 700 mA¬ |
| 1792D-16BVT0CD | Point-level | 650 mA¬ | |||||
| 1792D-8BVT0D | 8 Sink/Source | 4 | Connector-level | 470 mAT | |||
| 1792D-8BV0D | 8 | Point-level | 470 mAT | ||||
| 1792D-4BV0D | 4 Sink/Source | 4 | Point-level | 220 mA | |||
| 1792D-2BV0D | 2 Sink/Source | 2 | Point-level | 130 mA§ | |||
| ¬ DeviceNet Current specified with 16 sensors drawing 25 mA @ 24V DC. T DeviceNet Current specified with 8 sensors drawing 25 mA @ 24V DC. DeviceNet Current specified with 4 sensors drawing 25 mA @ 24V DC. § DeviceNet Current specified with 2 sensors drawing 25 mA @ 24V DC. |
|||||||
Digital Output Blocks
| Cat. No. | Number of Outputs | Number of Connectors | Diagnostics | Voltage, On-State Output, Nom. | Voltage, On-State Output, Range | Current, On-State Output, Max. | DeviceNet Current (mA) |
| 1792D-0B4D | 4 Source | 4 | Point-level | 24V DC | 10V DC dc…30V DC dc | 2.0 A | 80 mA |
| 1792D-0B8D | 8 Source | 8 | Point-level | 1.0 A | 80 mA | ||
| 1792D-0VT16E | 16 Sink | 8 | None | 0.3 A | 150 mA |
Digital Combination Blocks
| Cat. No. | Inputs | Outputs | DeviceNet Current (mA) | ||||||
| Number of Inputs | Number of Connections | Diagnostics | Operating Voltage | Current, Off-State Input, Max. | Number of Outputs | Operating Voltage | Current, On-State Output, Max. | ||
| 1792D-12BVT4D | 12 Sink/Source | 8 | Connector-level | 10V DC…25V DC | 1.5 mA | 4 Source | 10V DC dc…30V DC dc | 0.5 A | 570 mA |
| 1792D-12BT4PE | 12 Sink/Source | Connector-level | 2.0 A | 1.6 A¬ | |||||
| 1792D-8BVT8D | 8 Sink/Source | 8 | Connector-level | 8 Source | 0.5 A | 470 mA§ | |||
| 1792D-8BVT8CD | 8 | Point-level | 0.5 A | 470 mA§ | |||||
| 1792D-8BT8PE | 8 Sink/Source | 8 | Connector-level | 0.5 A | 1.4 AT | ||||
| 1792D-4BVT4D | 4 Sink/Source | 4 | Connector-level | 4 Source | 1.0 A | 220 mA§ | |||
| 1792D-4BV4D | 8 | Point-level | 1.0 A | 220 mA§ | |||||
| 1792D-2BVA2D | 2 Sink/Source | 4 | Connector-level | 2 Source | 1.0 A | 130 mAØ | |||
| 1792D-8BIO8E | 8 Sink | 8 | Block-level | 8 Source (powered by network) | 0.3 A | 470 mA§ | |||
| ¬ 175 mA max (no sensors), up to 1.6 A (12 sensors @ 50 mA per sensor) Refer to the graphs in the DeviceNet Power Supply Requirements section of the ArmorBlock MaXum I/O and ArmorBlock I/O Selection Guide, pub. no. 1792-SG001. T 175 mA max (no sensors), up to 1.4 A (8 sensors @ 50 mA per sensor) Refer to the graphs in the DeviceNet Power Supply Requirements section of the ArmorBlock MaXum I/O and ArmorBlock I/O Selection Guide, pub. no. 1792-SG001. DeviceNet Current specified with 12 sensors drawing 25 mA @ 24V DC. § DeviceNet Current specified with 8 sensors drawing 25 mA @ 24V DC. § DeviceNet Current specified with 4 sensors drawing 25 mA @ 24V DC. Ø DeviceNet Current specified with 2 sensors drawing 25 mA @ 24V DC. |
|||||||||