On-Machine Distributed I/O

Catalogs > Automation Systems Catalog > I/O > On-Machine Distributed I/O > 1799 Embedded I/O

1799 Embedded I/O

Introduction Product Design Communication Typical Configuration Specifications Embedded I/O Cards Accessory Products
Embedded I/O Cards

Digital dc Combination Cards

Mating connectors and mounting hardware for 1799 Embedded I/O cards must be ordered separately, except for the Zone Control I/O cards (1799-ZCIOB, 1799-ZCIOV, 1799-D10U10BZC, and 1799-D10U10VZC).

Input signal delay is user-selectable for 0, 2, 4, 8, or 16 ms, off-to-on or on-to-off. The delay time is set through RSNetWorx for DeviceNet, DeviceNetManager™ software or a similar configuration tool.


Cat. No. Operating Voltage Range Inputs Outputs Number of DeviceLogix Function Blocks DeviceNet Current (mA)
Number of Inputs Current, Off-State Input, Max. Number of Outputs Current, On-State Output, Max.
1799-D10U10B 10V DC30V DC 10 Sink/Source 1.5 mA 10 Source 0.5 A, short circuit protected, pilot duty 125 mA
1799-D10U10BL¬  10V DC30V DC 48
1799-D10U10V 10V DC30V DC 10 Sink/Source 1.5 mA 10 Source 0.5 A, short circuit protected, pilot duty 125 mA
1799-D10U10VL¬  10V DC30V DC 48
1799-D16U16B 10V DC30V DC 16 Sink/Source 1.5 mA 16 Sink/Source 0.5 A, short circuit protected 125 mA
1799-D16U16BL¬  10V DC30V DC 48
1799-D16U16V 10V DC30V DC 16 Sink/Source 1.5 mA 16 Sink/Source 0.5 A, short circuit protected 125 mA
1799-D16U16VL¬  10V DC30V DC 48
1799-D12G12GL¬  4.8V DC5.1V DC 12 TTL 0.6 mA 12 TTL 24 mA 72 450 mA
  
¬ Includes DeviceLogix Smart Component Technology (catalog numbers ending with L).

Digital dc Combination Cards with Analog I/O

Mating connectors and mounting hardware for 1799 Embedded I/O cards must be ordered separately.

Input signal delay is user-selectable for 0, 2, 4, 8, or 16 ms, off-to-on or on-to-off. The delay time is set through RSNetWorx for DeviceNet, DeviceNetManager™ software or a similar configuration tool.


Cat. No. Operating Voltage/Current Range Digital Inputs Digital Outputs Number of DeviceLogix Function Blocks DeviceNet Current (mA)
Number of Inputs Current, Off-State Input, Max. Number of Outputs Current, On-State Output, Max.
1799-D16U16BAGL 10V DC30V DC Digital: 16 Sink/Source 1.5 mA 16 Source 0.5 A, short circuit protected, pilot duty 120 digital 125 mA
0…20 mA
4…20 mA
Analog: 2 Current or Analog: 2 Current or 40 analog
0…10V dc 2 Voltage 2 Voltage
1799-D16U16VAGL 10V DC30V DC Digital: 16 Sink/Source 1.5 mA 16 Sink 0.5 A, short circuit protected, pilot duty 120 digital 125 mA
0…20 mA
4…20 mA
Analog: 2 Current or Analog: 2 Current or 40 analog
0…10V dc 2 Voltage 2 Voltage

Zone Control I/O Cards

Zone Control I/O cards include Zone Interlocking Parameters (ZIP) and DeviceLogix™ Smart Component Technology, and ship with a DeviceNet connector, auxiliary power connector, and mounting plate.

Input signal delay is user-selectable for 0, 2, 4, 8, or 16 ms, off-to-on or on-to-off. The delay time is set through RSNetWorx for DeviceNet, DeviceNetManager™ software or a similar configuration tool.


Cat. No. Operating Voltage Range Inputs Outputs Number of DeviceLogix Function Blocks DeviceNet Current (mA)
Number of Inputs Current, Off-State Input, Max. Number of Outputs Current, On-State Output, Max.
1799-ZCIOB 10V DC30V DC 10 Sink/Source 1.5 mA 10 Source 0.5 A, short circuit protected, pilot duty 72 125 mA
1799-ZCIOV 10 Sink
1799-D10U10BZC 10 Source
1799-D10U10VZC 10 Sink
  

Mounting a Zone Control I/O Card

Click to enlarge - 1799ZCIOmounting_BW
The ZCIO card comes with a mounting plate. You have the option to reset the DIN rail brackets (1799-BRKD) for mounting directly on a DIN rail. The card can also be mounted in an enclosure with pre-tapped holes.