DeviceNet 24V DC I/O Blocks
| Cat. No. | Inputs (Sink) | Outputs (Source) | Max. Continuous Output Current Rating per Point/Module | Max. Surge/Inrush Output Current Rating per Point | Max. Current for Input Device Power per Point | Potential Max. Aux. Current per Module | Network Current Draw | I/O Connectors |
| 1732D-IB8M8 | 8 current sinking | 0 | — | — | 0.8 A | 0.45 A | 100 mA | (8) M8 |
| 1732D-IB8M12 | (4) M12 | |||||||
| 1732D-OB8EM8 | 0 | 8 current sourcing | 0.5 A/4.0 A | 1.2 A | — | 4.0 A | 100 mA | (8) M8 |
| 1732D-OB8EM12 | (4) M12 | |||||||
| 1732D-8CFGM8 | 8 self-configuring § | 0.5 A/4.0 A | 1.2 A | 0.8 A | 4.0 A | 100 mA | (8) M8 | |
| 1732D-8CFGM12 | (4) M12 | |||||||
| 1732D-IB16M12M12 | 16 current sinking | 0 | — | — | 0.8 A | 0.9 A | 75 mA | (8) M12 |
| 1732D-IB16M12MINI | ||||||||
| 1732D-OB16M12M12 | 0 | 16 current sourcing⋆ | 2.0 A/8.0 A⋆ | 4.8 A | — | 0.1 A/8.0 A | 100 mA | (8) M12 |
| 1732D-OB16M12MINI | ||||||||
| 1732D-16CFGM12M12 | 16 self-configuring § | 0.5 A/8.0 A (all outputs) | 1.2 A | 0.8 A | 0.9 A/8.0 A | 100 mA | (8) M12 | |
| 1732D-16CFGM12MN | ||||||||
| ⋆ Maximum current on all I/O connectors exceeds total for the module. Module operation power and input device power, from Auxiliary Power Connector pins 2 and 3, are separate and isolated from the I/O output power, from Auxiliary Power Connector pins 1 and 4. Both auxiliary power consumption totals need to be noted. § Each of the self-configuring I/O points can be either an input (sink) or an output (source), for example: 16 points: 13 in 3 out, 6 in 10 out, etc. or 8 points: 6 in 2 out, 1 in 7 out, etc. |
||||||||
DeviceNet 24V DC I/O Blocks with Network Powered I/O and Diagnostics
I/O diagnostics provide one fault bit per module to indicate a short circuit or overcurrent on any I/O point. Inputs and/or outputs are powered by network where noted.
| Cat. No. | Inputs (Sink) Powered by Network | Outputs (Source) | Max. Continuous Output Current Rating per Point/Module | Max. Surge/Inrush Output Current Rating per Point | Max. Current for Input Device Power per Point | Potential Max. Aux. Current per Module | Max. Network Current Draw for Module Operation Plus I/O | I/O Connectors |
| 1732D-8X81212D | 8 (2 each on 4 connectors) | 8 (2 each on 4 connectors) | 0.5 A/4.0 A | 1.2 A | 0.8 A | 4.0 A | 0.1 A + I/O (1.0 A max.) | (8) M12 |
| 1732D-8X81212HD | 8 (2 each on 4 connectors) | 8 (2 each on 4 connectors) | 1.4 A/8.0 A⋆ | 3.1 A | 0.8 A | 8.0 A | 0.1 A + I/O (1.0 A max.) | (8) M12 |
| 1732D-8I8O1212D | 8 (1 on each connector) | 8 (1 on each connector and powered by network) | 0.5 A/4.0 A | 1.2 A | 0.8 A | — | 0.1 A + I/O (5.0 A max.) | (8) M12 |
| 1732D-IB161212D | 16 powered by network | 0 | — | — | 0.8 A | — | 75 mA + I/O (0.95 A max.) | (8) M12 |
| ⋆ Maximum current on all I/O connectors exceeds total for the module. | ||||||||
EtherNet/IP 24V DC I/O Blocks
| Cat. No. | Inputs (Sink) | Outputs (Source) | Max. Continuous Output Current Rating per Point/Module | Max. Surge/Inrush Output Current Rating per Point | Max. Current for Input Device Power per Point | Potential Max. Aux. Current per Module ♣ | I/O Connectors | Quick Connect | Dual-port Support |
| 1732E-IB16M12 | 16 | 0 | — | — | 5 mA at 30V DC | 8.0 A | (8) M12 | — | — |
| 1732E-IB16M12DR | 16 inputs with diagnostics | 0 | — | — | 5 mA at 30V DC | 8.0 A | (8) M12 | — | 2 EtherNet/IP ports∆ |
| 1732E-IB16M12R | 16 | 0 | — | — | 5 mA at 30V DC | 8.0 A | (8) M12 | — | 2 EtherNet/IP ports∆ |
| 1732E-IB8M8SOER | 8 sequence of events inputs with diagnostics | 0 | — | — | 5 mA at 30V DC | 4.0 A | (8) M8 | — | 2 EtherNet/IP ports∆ |
| 1732E-IB16M12SOEDR | 16 sequence of events inputs with diagnostics | 0 | — | — | 5 mA at 30V DC | 8.0 A | (8) M12 | — | 2 EtherNet/IP ports∆ |
| 1732E-OB8M8SR | 0 | 8 | 0.5 A/4.0 A ⋆ | 1.2 A for 10 ms, repeatable every 2 s | — | 4.0 A | (8) M8 | — | 2 EtherNet/IP ports∆ |
| 1732E-OB16M12 | 0 | 16 | 2.0 A/8.0 A ⋆ | 4.8 A for 10 ms, repeatable every 2 s | — | 8.0 A | (8) M12 | — | — |
| 1732E-OB16M12DR | 0 | 16 outputs with diagnostics | 0.5 A/8.0 A | 1.2 A for 10 ms, repeatable every 2 s | — | 8.0 A | (8) M12 | — | 2 EtherNet/IP ports∆ |
| 1732E-OB16M12R | 0 | 16 | 2.0 A/8.0 A ⋆ | 4.8 A for 10 ms, repeatable every 2 s | — | 8.0 A | (8) M12 | — | 2 EtherNet/IP ports∆ |
| 1732E-12X4M12QCDR | 12 | 4 | 0.5 A/2.0 A | 1.2 A for 10 ms, repeatable every 2 s | 5 mA at 30V DC | 8.0 A | (8) M12 | Yes | 2 EtherNet/IP ports∆ |
| 1732E-8X8M12DR | 8 inputs with diagnostics | 8 outputs with diagnostics | 0.5 A/4.0 A | 1.2 A for 10 ms, repeatable every 2 s | 5 mA at 30V DC | 4.0 A | (8) M12 | — | 2 EtherNet/IP ports∆ |
| 1732E-8CFGM8R | 8 self-configuring § | 0.5 A/4.0 A | 1.2 A for 10 ms, repeatable every 2 s | 5 mA at 30V DC | 4.0 A | (8) M8 | — | 2 EtherNet/IP ports∆ | |
| 1732E-16CFGM12 | 16 self-configuring § | 0.5 A/8.0 A | 3.2 A for 10 ms, repeatable every 2 s | 5 mA at 30V DC | 8.0 A | (8) M12 | — | — | |
| 1732E-16CFGM12R | 16 self-configuring § | 0.5 A/8.0 A | 1.2 A for 10 ms, repeatable every 2 s | 5 mA at 30V DC | 8.0 A | (8) M12 | — | 2 EtherNet/IP ports∆ | |
| 1732E-16CFGM12QCR | 16 self-configuring § | 0.5 A /8.0 A | 1.2 A for 10 ms, repeatable every 2 s | 5 mA at 30V DC | 8.0 A | (8) M12 | Yes | 2 EtherNet/IP ports∆ | |
| ⋆ Maximum current on all I/O connectors exceeds total for the module. ♣ Pins 2, 3 for sensor source and module power plus pins 1, 4 for output loads. § Each of the self-configuring I/O points can be either an input (sink) or an output (source), for example: 16 points: 13 in 3 out, 6 in 10 out, etc. ∆ Configured as embedded switch. Supports star, tree, linear, and ring topologies. |
|||||||||
PROFIBUS DP 24V DC I/O Blocks
| Cat. No. | Inputs (Sink) | Outputs (Source) | Max. Continuous Output Current Rating per Point/Module | Max. Surge/Inrush Output Current Rating per Point | Max. Current for Input Device Power per Point | Potential Max. Aux. Current per Module | I/O Connectors |
| 1732P-8CFGM8 | 8 self-configuring § | 0.5 A/4.0 A | 1.2 A | 0.8 A | 4.0 A | (8) M8 | |
| 1732P-8CFGM12 | (4) M12 | ||||||
| 1732P-16CFGM12 | 16 self-configuring § | 0.5 A/8.0 A | 1.2 A | 0.8 A | 1.0 A/8.0 A | (8) M12 | |
| Module operation power and input device power, from Auxiliary Power Connector pins 2 and 3, are separate and isolated from the I/O output power, from Auxiliary Power Connector pins 1 and 4. Both auxiliary power consumption totals need to be noted. § Each of the self-configuring I/O points can be either an input (sink) or an output (source), for example: 16 points: 13 in 3 out, 6 in 10 out, etc. or 8 points: 6 in 2 out, 1 in 7 out, etc. |
|||||||