Catalogs > Automation Systems Catalog > I/O > On-Machine Distributed I/O > 1732 ArmorBlock and 1732D/E Armor WeldBlock I/O
1732 ArmorBlock and 1732D/E Armor WeldBlock I/O
| Introduction | Product Design | Typical Configuration | Specifications |
| ArmorBlock Digital I/O Blocks | Armor WeldBlock Digital I/O Blocks | Mating Cables | For More Information |
DeviceNet Digital I/O Blocks
| DeviceNet, 24V dc, 8 and 16 Point | ||||||||
| Cat. No. | Inputs (Sink) | Outputs (Source) | Max. Continuous Output Current Rating per Point/Module | Max. Surge/Inrush Output Current Rating per Point | Max. Current for Input Device Power per Point | Potential Max. Aux. Current per Module | Network Current Draw | I/O Connectors |
| 1732D-IB8M8 | 8 Sink | 0 | — | — | 0.8 A | 0.45 A | 100 mA | (8) M8 |
| 1732D-IB8M12 | (4) M12 | |||||||
| 1732D-OB8EM8 | 0 | 8 Source | 0.5/4.0 A | 1.2 A | — | 4.0 A | 100 mA | (8) M8 |
| 1732D-OB8EM12 | (4) M12 | |||||||
| 1732D-8CFGM8 | 8 self-configuring | 0.5/4.0 A | 1.2 A | 0.8 A | 4.0 A | 100 mA | (8) M8 | |
| 1732D-8CFGM12 | (4) M12 | |||||||
| 1732D-IB16M12M12 | 16 Sink | 0 | — | — | 0.8 A | 0.9 A | 75 mA | (8) M12 |
| 1732D-IB16M12MINI | ||||||||
| 1732D-OB16M12M12 | 0 | 16 Source¬ | 2.0/8.0 A¬ | 4.8 A | — | 0.1/8.0 AT | 100 mA | (8) M12 |
| 1732D-OB16M12MINI | ||||||||
| 1732D-16CFGM12M12 | 16 self-configuring | 0.5/8.0 A | 1.2 A | 0.8 A | 0.9/8.0 A | 100 mA | (8) M12 | |
| 1732D-16CFGM12MN | ||||||||
| ¬ Maximum current on all I/O connectors exceeds total for the module. T Module operation power and input device power, from Auxiliary Power Connector pins 2 and 3, are separate and isolated from the I/O output power, from Auxiliary Power Connector pins 1 and 4. Both auxiliary power consumption totals need to be noted. Each of the self-configuring I/O points can be either an input (sink) or an output (source), for example: 16 points: 13 in 3 out, 6 in 10 out, etc. or 8 points: 6 in 2 out, 1 in 7 out, etc. |
||||||||
DeviceNet Digital I/O Blocks with Network Powered I/O and Diagnostics
I/O diagnostics provide one fault bit per modules to indicate a short circuit or overcurrent on any I/O point. Inputs and/or outputs powered by network where noted.
| DeviceNet, 24V dc, 16 Point | ||||||||
| Cat. No. | Inputs (Sink) Powered by Network | Outputs (Source) | Max. Continuous Output Current Rating per Point/Module | Max. Surge/Inrush Output Current Rating per Point | Max. Current for Input Device Power per Point | Potential Max. Aux. Current per Module | Max. Network Current Draw for Module Operation Plus I/O | I/O Connectors |
| 1732D-8X81212D | 8 (2 each on 4 connectors) | 8 (2 each on 4 connectors) | 0.5/4.0 A | 1.2 A | 0.8 A | 4.0 A | 0.1 A + I/O (1.0 A max.) | (8) M12 |
| 1732D-8X81212HD | 8 (2 each on 4 connectors) | 8 (2 each on 4 connectors) | 1.4/8.0 A¬ | 3.1 A | 0.8 A | 8.0 A | 0.1 A + I/O (1.0 A max.) | (8) M12 |
| 1732D-8I8O1212D | 8 (1 on each connector) | 8 (1 on each connector and powered by network) | 0.5/4.0 A | 1.2 A | 0.8 A | — | 0.1 A + I/O (5.0 A max.) | (8) M12 |
| 1732D-IB161212D | 16 powered by network | 0 | — | — | 0.8 A | — | 75 mA + I/O (0.95 A max.) | (8) M12 |
| ¬ Maximum current on all I/O connectors exceeds total for the module. | ||||||||
EtherNet/IP and PROFIBUS DP Digital I/O Blocks
| EtherNet/IP, 24V dc, 8 and 16 Point | |||||||
| Cat. No. | Inputs (Sink) | Outputs (Source) | Max. Continuous Output Current Rating per Point/Module | Max. Surge/Inrush Output Current Rating per Point | Max. Current for Input Device Power per Point | Potential Max. Aux. Current per Module | I/O Connectors |
| 1732E-IB16M12 | 16 Sink | 0 | — | — | 0.8 A | 1.1 A | (8) M12 |
| 1732E-OB16M12 | 0 | 16 Source | 2.0/8.0 A¬ | 4.8 A | — | 1.5/8.0 AT | (8) M12 |
| 1732E-16CFGM12 | 16 self-configuring | 0.5/8.0 A | 1.2 A | 0.8 A | 1.5/8.0 AT | (8) M12 | |
| ¬ Maximum current on all I/O connectors exceeds total for the module. T Module operation power and input device power, from Auxiliary Power Connector pins 2 and 3, are separate and isolated from the I/O output power, from Auxiliary Power Connector pins 1 and 4. Both auxiliary power consumption totals need to be noted. Each of the self-configuring I/O points can be either an input (sink) or an output (source), for example: 16 points: 13 in 3 out, 6 in 10 out, etc. or 8 points: 6 in 2 out, 1 in 7 out, etc. |
|||||||
| PROFIBUS DP, 24V dc, 8 and 16 Point | |||||||
| Cat. No. | Inputs (Sink) | Outputs (Source) | Max. Continuous Output Current Rating per Point/Module | Max. Surge/Inrush Output Current Rating per Point | Max. Current for Input Device Power per Point | Potential Max. Aux. Current per Module | I/O Connectors |
| 1732P-IB8M8 | 8 Sink | 0 | — | — | 0.8 A | 0.45 A | (8) M8 |
| 1732P-IB8M12 | (4) M12 | ||||||
| 1732P-OB8EM8 | 0 | 8 Source | 0.5/4.0 A | 1.2 A | — | 4.0 A | (8) M8 |
| 1732P-OB8EM12 | (4) M12 | ||||||
| 1732P-8CFGM8 | 8 self-configuring | 0.5/4.0 A | 1.2 A | 0.8 A | 4.0 A | (8) M8 | |
| 1732P-8CFGM12 | (4) M12 | ||||||
| 1732P-IB16M12 | 16 Sink | 0 | — | — | 0.8 A | 1.0 A | (8) M12 |
| 1732P-OB16M12 | 0 | 16 Source¬ | 2.0/8.0 A¬ | 4.8 A | — | 0.2/8.0 AT | (8) M12 |
| 1732P-16CFGM12 | 16 self-configuring | 0.5/8.0 A | 1.2 A | 0.8 A | 1.0/8.0 AT | (8) M12 | |
| ¬ Maximum current on all I/O connectors exceeds total for the module. T Module operation power and input device power, from Auxiliary Power Connector pins 2 and 3, are separate and isolated from the I/O output power, from Auxiliary Power Connector pins 1 and 4. Both auxiliary power consumption totals need to be noted. Each of the self-configuring I/O points can be either an input (sink) or an output (source), for example: 16 points: 13 in 3 out, 6 in 10 out, etc. or 8 points: 6 in 2 out, 1 in 7 out, etc. |
|||||||