| DeviceNet WeldBlocks, 24V dc, 16 Point
|
| Cat. No.
|
Inputs (Sink) Powered by Network
|
Outputs (Source)
|
Max. Continuous Output Current Rating per Point/Module
|
Max. Surge/Inrush Output Current Rating per Point
|
Max. Current for Input Device Power per Point
|
Potential Max. Aux. Current per Module
|
Network Current Draw
|
I/O Connectors
|
| 1732D-IB161212W
|
16 Sink
|
0
|
—
|
—
|
0.8 A
|
0.9 A
|
75 mA
|
(8) M12
|
| 1732D-16CFG1212W
|
16 self-configuring
|
0.5/8.0 A
|
1.2 A
|
0.8 A
|
0.9/8.0 AT
|
100 mA
|
(8) M12
|
T Module operation power and input device power, from Auxiliary Power Connector pins 2 and 3, are separate and isolated from the I/O output power, from Auxiliary Power Connector pins 1 and 4. Both auxiliary power consumption totals need to be noted. Each of the self-configuring I/O points can be either an input (sink) or an output (source), for example: 16 points: 13 in 3 out, 6 in 10 out, etc. or 8 points: 6 in 2 out, 1 in 7 out, etc.
|
| EtherNet/IP WeldBlocks, 24V dc, 16 Point
|
| Cat. No.
|
Inputs (Sink) Powered by Network
|
Outputs (Source)
|
Max. Continuous Output Current Rating per Point/Module
|
Max. Surge/Inrush Output Current Rating per Point
|
Max. Current for Input Device Power per Point
|
Potential Max. Aux. Current per Module
|
I/O Connectors
|
| 1732E-IB16M12W
|
16 Sink
|
0
|
—
|
—
|
0.8 A
|
1.1 A
|
(8) M12
|
| 1732E-16CFGM12W
|
16 self-configuring
|
0.5/8.0 A
|
1.2 A
|
0.8 A
|
1.5/8.0 AT
|
(8) M12
|
T Module operation power and input device power, from Auxiliary Power Connector pins 2 and 3, are separate and isolated from the I/O output power, from Auxiliary Power Connector pins 1 and 4. Both auxiliary power consumption totals need to be noted. Each of the self-configuring I/O points can be either an input (sink) or an output (source), for example: 16 points: 13 in 3 out, 6 in 10 out, etc. or 8 points: 6 in 2 out, 1 in 7 out, etc.
|