1738 ArmorPoint I/O

Click to enlarge - bullseye Hit The Point!    
Product Overview
  
Click to enlarge - 1738ArmPtAssy_angle_4C

ArmorPoint™ I/O

ArmorPoint is a 24V dc modular On-Machine™ I/O that extends the features and benefits of the POINT I/O™ IP20 system into an IP69K-compliant system. ArmorPoint I/O offers flexibility, ease of application, and just-what-you-need granularity in one to eight points to reduce system cost and size. 1738 ArmorPoint I/O is the foundation for the next generation of On-Machine products from Rockwell Automation.

Benefits


Product Design

1738 ArmorPoint I/O is the foundation for the next generation of On-Machine™ products from Rockwell Automation. The architecture of ArmorPoint is based on the POINT I/O system and reuses the circuitry of the adapter and I/O designs. The system is IP67-compliant and other certifications necessary to provide a complete On-Machine solution. ArmorPoint I/O modules offer one to eight points per module. Choose from many different I/O types with connector choices of M8, M12, or M23 quick-disconnect terminations.

The I/O modules are interfaced to a network through a communication adapter, which includes a built-in power supply that converts incoming 24V dc power to 5V dc backplane power. The I/O modules receive power from the power supply through the backplane. ArmorPoint I/O offers flexibility, supporting up to 63 I/O modules per network node. A bus extension module allows for separation of modules on the same node.

Four versions of DeviceNet communication adapters are available, along with ControlNet, EtherNet/IP, and PROFIBUS DP adapters. Each adapter supports a maximum of 13 to 17 I/O modules, with a maximum of 10 A field power. The family includes hardened power supplies to allow for isolation, i.e. AC from DC, analog from digital, inputs from outputs. Module replacement is easy since modules are held on the base by unique latching mechanisms—no screws needed. ArmorPoint connects directly to ArmorStart™ on the same network node.


Modular Design

ArmorPoint I/O has three major components:


Communication

Adapter modules are available for ControlNet, DeviceNet (with and without subnet connectivity), EtherNet/IP, or PROFIBUS DP networks. The DeviceNet adapters are available in four styles, based on connectivity: M12 micro terminations, mini passthrough terminations, mini drop termination, and adapter with subnet connectivity.

Power to the POINTBus backplane and I/O modules is brought in through the auxiliary power connector. You can connect up to 12 I/O modules and an adapter with a maximum of 10 A field power, using the auxiliary power. Additional I/O modules require the use of one or more ArmorPoint I/O 24V dc expansion power units. An I/O adapter supports up to a maximum of 63 I/O modules.


Specifications

Environmental Specifications

Enclosure Type Rating Meets IP65/66/67/69K (when marked) and NEMA 4X
Mounting Type On-Machine
Operating Temperature IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
-20 to 60°C (-4 to 140°F)
  1738-EP24DC
-20…85 °C (-4…185 °F)
Storage Temperature IEC 60068-2-1 (Test AB, Unpackaged Nonoperating Cold)
IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat):
-40…85 ℃ (-40…185〬F)
Relative Humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat):
5...95% noncondensing
Shock, Operating IEC 60068-2-27 (Test Ea, Unpackaged Shock):
30 g
  1738-OW4M12
IEC 60068-2-27 (Test Ea, Unpackaged Shock):
15 g peak acceleration
  1738-OW4M12AC
Shock, Non-Operating IEC 60068-2-27 (Test Ea, Unpackaged Shock):
50 g
Vibration IEC 60068-2-6 (Test Fc, Operating):
5 g @ 10…500 Hz
  1738-OW4M12
IEC 60068-2-6 (Test Fc, Operating):
2 g @ 10…500 Hz
  1738-OW4M12AC
CertificationsT  c-UL-us, CE, C-Tick, DeviceNet
  
¬ Except AC I/O modules, which are IP67.
T When product is marked. See the Product Certification link at www.ab.com for Declarations of Conformity, Certificates, and other certification details.

Dimensions and Weights

Cat. No. Weight Dimensions (HxWxD), Approx.
I/O Modules 0.29 kg (0.64 lb) 120 x 72 x 42 mm (includes I/O module and mounting base) (4.72 x 2.83 x 1.65 in (includes I/O module and mounting base))
Communication Adapter
Modules
0.36 kg (0.80 lb) 112 x 72 x 65 mm (4.41 x 2.83 x 2.56 in)
  

Communication Adapter Modules and Mating Cables

An ArmorPoint I/O communication interface module provides the interface between a fieldbus network and the ArmorPoint I/O backplane (POINTBus™). A terminating base, used with the last I/O module, ships with the adapter. An I/O adapter supports up to a maximum of 63 I/O modules.

Adapter modules are available for ControlNet, DeviceNet (with and without subnet connectivity), EtherNet/IP, or PROFIBUS DP networks. The DeviceNet adapters are available in four styles, based on connectivity: DC micro (M12) terminations, mini passthrough terminations, mini drop termination, and adapter with subnet connectivity.


Communication Adapter Modules

Cat. No. Termination Type Input Voltage Range Field Side Power Requirements Inrush Current Power Consumption (W) at 24V Power Dissipation, Max.
1738-ADN12 M12 Quick-Disconnect 10…28.8V dc 24V dc (+20% = 28.8V dc) @ 400 mA 6 A for 10 ms 8.0 W 2.8 W @ 28.8V
1738-ADN18 Mini Connector - Drop - Drop 24V dc (+20% = 28.8V dc) @ 400 mA
1738-ADN18P Mini Connector - Pass-through - Pass-through 24V dc (+20% = 28.8V dc) @ 400 mA
1738-ADNX M12 Quick-Disconnect 24V dc (+4% = 25V dc) @ 30 mA
1738-ACNR TNC Connector 24V dc (+20% = 28.8V dc) @ 425 mA
1738-AENT M12 Quick-Disconnect 24V dc (+4% = 25V dc) @ 30 mA 4.5 W
1738-APB M12 Quick-Disconnect 24V dc (+20% = 28.8V dc) @ 400 mA 8.0 W
 

ArmorPoint I/O Communication Adapters

Cat. No. Description Number of I/O Points, Max.¬ 
DeviceNet
1738-ADN12 DeviceNet I/O Adapter
  • A total of 63 ArmorPoint I/O modules can be assembled on a single DeviceNet node

  • Expansion power supplies may be used to provide additional POINTBus backplane current

  • 252
    1738-ADN18
    1738-ADN18P
    1738-ADNX DeviceNet I/O Adapter with Expansion Port
  • A total of 63 ArmorPoint I/O modules can be assembled on a single DeviceNet node

  • Expansion power supplies may be used to provide additional POINTBus backplane current

  • Expansion network port allows for a DeviceNet subnet

  • Increases the reach of DeviceNet from 500 to 1500 meters

  • Increases nodes per DeviceNet scanner from 63 to more than 126 (dependent on DeviceNet scanner capacity)
  • 252
    ControlNet
    1738-ACNR ControlNet I/O Adapter
  • A total of 63 ArmorPoint I/O modules can be assembled on a single ControlNet node

  • Expansion power supplies may be used to provide additional POINTBus backplane current

  • Up to 25 direct connections and 5 rack connections are allowed
  • 252
    EtherNet/IP
    1738-AENT EtherNet/IP Twisted Pair Media I/O Adapter
  • A total of 63 ArmorPoint I/O modules can be assembled on a single EtherNet/IP node

  • Expansion power supplies may be used to provide additional POINTBus backplane current

  • Refer to the User Manual to determine the ratings for direct and rack connections allowed
  • 252
    PROFIBUS DP
    1738-APB PROFIBUS DP I/O Adapter
  • A total of 63 ArmorPoint I/O modules can be assembled on a single PROFIBUS DP node

  • Expansion power supplies may be used to provide additional POINTBus backplane current
  • 252
    ¬ Using the eight-point digital I/O modules.

    Mating Cables

    The mating cables shown represent straight PVC models. For additional configurations, materials, and specifications, consult the On-Machine Connectivity catalog, publication M116-CA001.

    ArmorPoint Network Adapter Mating Cables

    Cat. No. Network Flat Media Thick Round Thin Round
    1738-ADN12
    1738-ADNX
    DeviceNet 1485K-P§F5-R5 1485R-P§M5-R5 1485R-P§R5-D5
    1738-ADN18P
    1738-ADN18
    DeviceNet 1485K-P§F5-N5 1485R-P§N5-M5 1485R-P§D5-N5
    1738-ACNR ControlNet 1786-TPST2T
    1786-TPRT2T
    1738-AENT EtherNet/IP 1585D-M4DC-H
    1738-APB PROFIBUS DP
    ¯ = length in meters (1, 2, 3, 5, and 10 standard).
    ‡ = length in meters (2, 5, and 10 standard).
    § = length in meters (1, 2, 3, 4, 5, and 6 standard).
    µ = length in feet (6, 12, and 20 standard).

    ArmorPoint Auxiliary Power Mating Cables

      Flat Media Round Media
    Cat. No. Auxiliary Power Flat Media Connection Cordset (Single-ended) Patchcord (Double-ended)
    1738-ADN12
    1738-ADNX
    1738-ADN18P
    1738-ADN18
    1738-ACNR
    1738-AENT
    1738-APB
    1485T-P1E4-C§-N4 889N-F4AFC-µF 889N-F4AFNM-¯
    ¯ = length in meters (1, 2, 3, 5, and 10 standard).
    ‡ = length in meters (2, 5, and 10 standard).
    § = length in meters (1, 2, 3, 4, 5, and 6 standard).
    µ = length in feet (6, 12, and 20 standard).

    Digital dc I/O Modules and Mating Cables

    The 1738 digital I/O modules support:


    ArmorPoint Digital dc Input Modules

    General-purpose 24V dc inputs including 2- and 3-wire proximity sensors.

    Cat. No. Number of Inputs Voltage, On-State Input, Nom. Operating Voltage Range Input Delay Time, ON to OFF¬  Current, On-State Input, Min. Current, On-State Input, Max. Current, Off-State Input, Max. PointBus Current (mA) Power Dissipation, Max. Termination Type
    1738-IB2M12 2 Sink 24V dc 10V dc…28.8V dc 0.5 ms hardware + (0…65 ms selectable) 2 mA 5 mA 1.5 mA 75 0.7 W @ 28.8V dc DC micro (M12)
    1738-IB4M12 4 Sink 1.0 W @ 28.8V dc
    1738-IB4M8 Pico 3-pin (M8)
    1738-IB8M12 8 Sink 1.6 W @ 28.8V dc DC micro (M12)T 
    1738-IB8M23 M23
    1738-IB8M8 Pico 3-pin (M8)
    1738-IV8M12 8 Source DC micro (M12)
    1738-IV8M23 M23
    1738-IV8M8 Pico 3-pin (M8)
    1738-IV4M12 4 Source 1.0 W @ 28.8V dc DC micro (M12)
    ¬ Input ON-to-OFF delay time is the time from a valid input signal to recognition by the module.
    T Quantity 4.

    ArmorPoint Digital dc Output Modules

    24V dc electronically protected output modules. The 1738-OB2EPM12 module has 24V dc electronically protected, fast-switching high-current outputs.

    Cat. No. Number of Outputs Voltage, On-State Output, Nom. Voltage, On-State Output, Range Output Current Rating, Max. PointBus Current (mA) Power Dissipation, Max. Termination Type
    1738-OB2EM12 2 Source 24V dc 10V dc…28.8V dc 2.0 A per module, 1.0 A per channel 75 0.8 W @ 28.8V dc DC micro (M12)
    1738-OB2EPM12 4.0 A per module, 2.0 A per channel
    1738-OB4EM12 4 Source 3.0 A per module, 1.0 A per channel 1.2 W @ 28.8V dc
    1738-OB4EM8 Pico 3-pin (M8)
    1738-OB8EM12 8 Source 2.0 W @ 28.8V dc DC micro (M12)T 
    1738-OB8EM23 M23
    1738-OB8EM8 Pico 3-pin (M8)
    1738-OV4EM12 4 Sink 4.0 A per module, 1.0 A per channel 2.9 W @ 28.8V dc DC micro (M12)
    T Quantity 4.

    ArmorPoint Digital Contact Output Modules

    Individually isolated contact output modules.

    Cat. No. Number of Outputs Voltage, On-State Output, Nom. Output Delay Time, ON to OFF, Max.¬  Contact Resistance, Initial Relay Output Current Rating, Max. Leakage Current, Off-State Output, Max PointBus Current (mA) Power Dissipation, Max. Termination Type
    1738-OW4M12 4 Form A (N.O.) relays, isolated 24V dc 26 ms 30 mW 1.2 mA and bleed resistor thru snubber circuit @ 240V ac 80 0.5 W DC micro (M12)
    1738-OW4M12AC AC micro 4-pin§ 
    ¬ Time from valid output off signal to relay deenergization by module.
    § Quantity 2.

    Mating Cables

    The mating cables shown represent straight PVC models. For additional configurations, materials, and specifications, consult the On-Machine Connectivity catalog, publication M116-CA001.

    ArmorPoint Digital dc Input Module Mating Cables

    ArmorPoint Cat. No. End Device per Connector Recommended Patchcord (Double-ended) Recommended Male Cordset (Single-ended) Recommended Field Attachable Connector
    1738-IB8M12
    1738-IV8M12
    (2) DC Micro 879D-F4ACDM—* 879D-C3ACD4M—‡ 871A-VS4-DM
    (2) Pico 3-Pin 879PZ-F3ABDM4—*
    (2) Pico 4-Pin 879PZ-F4ABDM—*
    (1) DC Micro 889D-F4ACDM—* 889D-M4AC—‡ 871A-TS4-DM
    (1) Pico 3-Pin 889P-F3ABDM4—*
    (1) Pico 4-Pin 889P-F4ABDM—*
    1738-IB2M12
    1738-IB4M12
    1738-IV4M12
    (1) DC Micro 889D-F4ACDM—* 889D-M4AC—‡ 871A-TS4-DM
    (1) Pico 3-Pin 889P-F3ABDM4—*
    (1) Pico 4-Pin 889P-F4ABDM—*
    1738-IB4M8
    1738-IB8M8
    1738-IV8M8
    (1) DC Micro 889D-F4ABP3M—* 889P-M3AB—‡ 871A-TS3-PM
    (1) Pico 3-Pin 889P-F3ABPM—*
    (1) Pico 4-Pin 889P-F4ABPM3—*
    1738-IB8M23
    1738-IV8M23
    (1) M23 12-Pin 889M-F11RMMU—* 889M-U11RM—‡ 889M-M12AH-T
    ¯ = length in meters (1, 2, 3, 5, and 10 standard).
    ‡ = length in meters (2, 5, and 10 standard).

    ArmorPoint Digital dc Output Module Mating Cables

    ArmorPoint Cat. No. End Device per Connector Recommended Patchcord (Double-ended) Recommended Male Cordset (Single-ended) Recommended Field Attachable Connector
    1738-OB8EM12 (2) DC Micro 879D-F4ACDM—¯ 879D-C3ACD4M—‡ 871A-VS4-DM
    (2) Pico 3-Pin 879PZ-F3ABDM4—¯
    (2) Pico 4-Pin 879PZ-F4ABDM—¯
    (1) DC Micro 889D-F4ACDM—¯ 889D-M4AC—‡ 871A-TS4-DM
    (1) Pico 3-Pin 889P-F3ABDM4—¯
    (1) Pico 4-Pin 889P-F4ABDM—¯
    1738-OB2EM12
    1738-OB2EP12
    1738-OB4EM12
    1738-OV4EM12
    (1) DC Micro 889D-F4ACDM—¯ 889D-M4AC—‡ 871A-TS4-DM
    (1) Pico 3-Pin 889P-F3ABDM4—¯
    (1) Pico 4-Pin 889P-F4ABDM—¯
    1738-OB4EM8
    1738-OB8EM8
    (1) DC Micro 889D-F4ABP3M—¯ 889P-M3AB—‡ 871A-TS3-PM
    (1) Pico 3-Pin 889P-F3ABPM—¯
    (1) Pico 4-Pin 889P-F4ABPM3—¯
    1738-OB8EM23 (1) M23 12-Pin 889M-F11RMMU—¯ 889M-U11RM—‡ 889M-M12AH-T
    ¯ = length in meters (1, 2, 3, 5, and 10 standard).
    ‡ = length in meters (2, 5, and 10 standard).

    ArmorPoint Digital Contact Output Module Mating Cables

    ArmorPoint Cat. No. End Device per Connector Recommended Patchcord (Double-ended) Recommended Male Cordset (Single-ended) Recommended Field Attachable Connector
    1738-OW4M12 (1) DC Micro 889D-F4ACDM—¯ 889D-M4AC—‡ 871A-TS4-DM
    1738-OW4M12AC (1) AC Micro 4-Pin 889R-F4AERM—¯ 889R-M4AEA—‡
    ¯ = length in meters (1, 2, 3, 5, and 10 standard).
    ‡ = length in meters (2, 5, and 10 standard).

    Digital ac I/O Modules and Mating Cables

    The 1738 digital I/O modules support:


    ArmorPoint Digital ac Input Modules

    General-purpose ac inputs including 2- and 3-wire proximity sensors.

    Cat. No. Number of Inputs Voltage, On-State Input, Nom. Voltage, On-State Input, Range Input Delay Time, ON to OFF¬  Current, On-State Input, Min. Current, Off-State Input, Max. Input Impedance, Nom. PointBus Current (mA) Power Dissipation, Max. Termination Type
    1738-IA2M12AC3 2 120V ac 65V ac…132V ac 20 ms hardware filter plus 0…65 ms digital filter programmable in increments of 1 ms 3.7 mA 2.5 mA 10.6 kW 75 0.7 W @ 132V ac AC micro 3-pinT 
    1738-IA2M12AC4 AC micro 4-pinT 
    ¬ Input ON-to-OFF delay time is the time from a valid input signal to recognition by the module.
    T Quantity 2.

    ArmorPoint Digital ac Output Modules

    General purpose ac outputs.

    Cat. No. Number of Outputs Voltage, On-State Output, Nom. Voltage, On-State Output, Range Output Current Rating PointBus Current (mA) Power Dissipation, Max. Termination Type
    1738-OA2M12AC3 2 120V/220V ac 74V ac…264V ac 1.5 A (2 channels @ 0.75 A each) 75 0.8 W @ 28.8V dc AC 3-pinT 
    T Quantity 2.

    Mating Cables

    The mating cables shown represent straight PVC models. For additional configurations, materials, and specifications, consult the On-Machine Connectivity catalog, publication M116-CA001.

    ArmorPoint Digital ac Input Module Mating Cables

    ArmorPoint Cat. No. End Device per Connector Recommended Patchcord (Double-ended) Recommended Male Cordset (Single-ended) Recommended Field Attachable Connector
    1738-IA2M12AC3 (1) AC Micro 3-Pin 889R-F3AERM—¯ 889R-M3AEA—‡ 871A-TS3-RM
    1738-IA2M12AC4 (1) AC Micro 4-Pin 889R-F4AERM—¯ 889R-M4AEA—‡
    ¯ = length in meters (1, 2, 3, 5, and 10 standard).
    ‡ = length in meters (2, 5, and 10 standard).

    ArmorPoint Digital ac Output Module Mating Cables

    ArmorPoint Cat. No. End Device per Connector Recommended Patchcord (Double-ended) Recommended Male Cordset (Single-ended) Recommended Field Attachable Connector
    1738-OA2M12AC3 (1) AC Micro 3-Pin 889R-F3AERM—¯ 889R-M3AEA—‡ 871A-TS3-RM
    ¯ = length in meters (1, 2, 3, 5, and 10 standard).
    ‡ = length in meters (2, 5, and 10 standard).

    Analog I/O Modules and Mating Cables

    The ArmorPoint analog I/O modules support:


    ArmorPoint Analog Input Modules

    Cat. No. Number of Inputs Input Signal Range Input Resolution Absolute Accuracy¬  Step Response, per Channel Input Conversion Type PointBus Current (mA) External DC Supply Current, Nom. Power Dissipation, Max. Termination Type
    1738-IE2CM12 2 single-ended  4…20 mA
    0…20 mA
    16 bits - over 21 mA
    0.32 mA/cnt
    0.1% Full Scale @ 25° C 70 ms @ Notch = 60 Hz (default)
    80 ms @ Notch = 50 Hz
    16 ms @ Notch = 250 Hz
    8 ms @ Notch = 500 Hz
    Delta Sigma 75 10 mA @ 24V dc 0.6 W @ 28.8V dc DC Micro
    1738-IE2VM12 2 single-ended  0…10V
    ±10V
    15 bits plus sign
    320 mV/cnt in unipolar or bipolar mode
    0.1% Full Scale @ 25° C 15 mA @ 24V dc 0.75 W @ 28.8V dc
    1738-IR2M12‡  2 single-ended RTD 0…600 W 16 bits
    9.5 mV/cnt
    0.03 °C/cnt (pt 385 @ 25 °C)
    0.1% Full Scale @ 25° CT  60 ms @ Notch = 50 Hz
    50 ms @ Notch = 60 Hz
    30 ms @ Notch = 100 Hz
    25 ms @ Notch = 120 Hz
    15 ms @ Notch = 200 Hz
    13 ms @ Notch = 240 Hz
    10 ms @ Notch = 300 Hz
    8 ms @ Notch = 400 Hz
    6 ms @ Notch = 480 Hz
    220 15 mA @ 24V dc 1.0 W
    1738-IT2IM12‡  2 single-ended 
    Thermocouple, Millivolt
    ±75 mV 15 bits plus sign
    2.5 mV per count
    0.1% Full Scale @ 25° CT  60 ms @ Notch = 50 Hz
    50 ms @ Notch = 60 Hz
    30 ms @ Notch = 100 Hz
    25 ms @ Notch = 120 Hz
    15 ms @ Notch = 200 Hz
    13 ms @ Notch = 240 Hz
    10 ms @ Notch = 300 Hz
    8 ms @ Notch = 400 Hz
    6 ms @ Notch = 480 Hz
    175 1.0 W
    ¬ Includes offset, gain, nonlinearity, and repeatability error terms.
    T Analog and temperature input modules support these configurable parameters and diagnostics: open-wire with LED and electronic reporting; four-alarm and annunciation set-points; calibration mode and electronic reporting; under- and over-range and electronic reporting; channel signal range and update rate and on-board scaling; filter-type; temperature scale; channel update rate.
    ‡ See Temperature and RTD Input Modules—Additional Specifications.

    Temperature and RTD Input Modules—Additional Specifications

      1738-IR2M12 1738-IT2IM12
    Number of Inputs 2 single-ended  RTD 2 single-ended  Isolated Thermocouple, Millivolt
    Thermocouple Resolution Type B, 30…1820° C, 3 counts/ ° C
    Type C, 0…2315° C, 6 counts/ ° C
    Type E, -270…1000° C, 24 counts/ ° C
    Type J, -210…1200° C, 21 counts/ ° C
    Type K, -270…1372° C, 13 counts/ ° C
    Type N, -270…1300° C, 11 counts/ ° C
    Type R, -50…1768.1° C, 4 counts/ ° C
    Type S, -50...1768.1° C, 4 counts/ ° C
    Type T, -270…400° C, 15 counts/ ° C
    Cold Junction Compensation Range 0…70 °C
    Input Update Rate, per Module 20 ms @ Notch = 50 Hz
    17 ms @ Notch = 60 Hz (default)
    10 ms @ Notch = 100 Hz
    8 ms @ Notch = 120 Hz
    5 ms @ Notch = 200 Hz
    4 ms @ Notch = 240 Hz
    3 ms @ Notch = 300 Hz
    3 ms @ Notch = 400 Hz
    2 ms @ Notch = 480 Hz
    20 ms @ Notch = 50 Hz
    17 ms @ Notch = 60 Hz (default)
    10 ms @ Notch = 100 Hz
    8 ms @ Notch = 120 Hz
    5 ms @ Notch = 200 Hz
    4 ms @ Notch = 240 Hz
    3 ms @ Notch = 300 Hz
    3 ms @ Notch = 400 Hz
    2 ms @ Notch = 480 Hz
    Data Format Signed integer Signed integer
      
     

    ArmorPoint Analog Output Modules

    Cat. No. Number of Outputs Output Signal Range Output Resolution Absolute Accuracy
    Step Response to 63% of FS
    Output Conversion Rate PointBus Current (mA) External DC Supply Current, Nom. Power Dissipation, Max. Termination Type
    1738-OE2CM12 2 single-ended  4…20 mA
    0…20 mA
    13 bits - over 21 mA
    2.5 mA/cnt
    0.1% Full Scale @ 25° C¬  T  Current Output: 24 ms 16 ms 75 50 mA @ 24V dc (including outputs @ 20 mA) 1.0 W @ 28.8V dc DC Micro (M12)
    1738-OE2VM12 2 single-ended  0…10V
    ±10V
    14 bits (13 plus sign)
    1.28 mV/cnt in unipolar or bipolar mode
    0.1% Full Scale @ 25° C¬  T  Voltage Output: 20 ms 20 ms 35 mA @ 24V dc (including outputs @ 3 mA)
    ¬ Includes offset, gain, non-linearity, and repeatability error terms.
    T Analog output modules support these configurable parameters and diagnostics: open-wire with LED and electronic reporting (OE2C only); fault mode; idle mode; alarms; channel signal range and on-board scaling.

    Mating Cables

    The mating cables shown represent straight PVC models. For additional configurations, materials, and specifications, consult the On-Machine Connectivity catalog, publication M116-CA001.

    ArmorPoint Analog Input Module Mating Cables

    ArmorPoint Cat. No. End Device per Connector Recommended Patchcord (Double-ended) Recommended Male Cordset (Single-ended) Recommended Field Attachable Connector
    1738-IE2CM12
    1738-IE2VM12
    1738-IR2M12
    (1) DC Micro 889D-F4SCDM—¯ 889D-M4SC—‡ 889D-M4DC-SH
    1738-IT2IM12 (1) DC Micro 871A-TS4CJC-DM
    ¯ = length in meters (1, 2, 3, 5, and 10 standard).
    ‡ = length in meters (2, 5, and 10 standard).

    ArmorPoint Analog Output Module Mating Cables

    ArmorPoint Cat. No. End Device per Connector Recommended Patchcord (Double-ended) Recommended Male Cordset (Single-ended) Recommended Field Attachable Connector
    1738-OE2CM12
    1738-OE2VM12
    (1) DC Micro 889D-F4SCDM—¯ 889D-M4SC—‡ 889D-M4DC-SH
    ¯ = length in meters (1, 2, 3, 5, and 10 standard).
    ‡ = length in meters (2, 5, and 10 standard).

    Specialty I/O Modules and Mating Cables


    ArmorPoint Counter Modules

    The input voltage range is 5V DC (1738–IJ) or 15…24V DC (1738–VHSC24). The module returns the count or frequency in the form of a 24-bit binary number (0…16,777,215) expressed in a 32-bit word. Each counter has a user-selectable preset and rollover value associated with it.

    The operation of the counter and encoder modes is nearly identical. The difference between the two modes is in the type of feedback (one-phase versus two-phase) for the count direction (up or down). In encoder mode, a transition is expected on B for counting to proceed in a direction, whereas, in counter mode, the B input may be left at a static level. All operating modes are selected by writing appropriate configuration data to the module.


    Cat. No. Number of Counters Voltage, On-State Input, Nom. Field Power Bus Number of Compare Windows Output Groups Input Frequency, Max. Output Delay Time, OFF to ON Current, On-State Input, Min. PointBus Current (mA) Termination Type
    1738-IJM23 1 5V dc Voltage dependent on field power source¬  1.0 MHz counter and encoder X1 configurations (no filter)
    500 kHz encoder X2 configuration (no filter)
    250 kHz encoder X4 configuration (no filter)
    ³5 mA 160 M23
    1738-VHSC24M23 1 24V dc 4 1 group of 2 25 ms (load dependent)T  110 M23
    ¬ Field power source via the field power connection on the network adapter, 1738–EP24DC, or 1738–FPD.
    T OFF to ON delay is time from a valid output “on” signal to output energization.

    ArmorPoint Serial I/O Modules

    ArmorPoint Synchronous Serial Interface Modules

    The Synchronous Serial Interface Absolute Encoder Module collects serial data from industrial absolute position encoding sensors that use standard SSI protocol, including linear, rotary, and optical distance measuring devices. The module is inserted into an ArmorPoint I/O terminal base that provides common power, communications, and wiring connections for the SSI sensors. The module converts a serial data stream from an SSI sensor into absolute position data readable as a 32-hexadecimal value. Gray or binary-code capable with gray to binary conversion, increasing or decreasing SSI count indication, 2 SSI word comparator values, and SSI word latching with I1 input.

    ArmorPoint Serial Interface Modules

    The 1738–232ASCM12 and 1738–485ASCM12 serial-interface modules offer a serial-link communication interface solution for peripheral products with RS–232 (use the 1738–232ASCM12), RS–485, and RS–422 ports (use the 1738–485ASCM12). These modules allow a device with serial-interface output (i.e., bar code readers) to communicate up to 128 bytes of ASCII data onto any network supported by ArmorPoint I/O. Each module is a single-channel, full-duplex interface and is rated for up to 38.4k baud. LED indicators on the modules offer diagnostics for the module, POINTBus backplane, and transmit/receive status indication.

    ArmorPoint Serial I/O Modules

    Cat. No. Inputs/Outputs PointBus Current (mA) External DC Power Supply Power Dissipation, Max. Termination Type
    1738-SSIM23 1  Synchronous Serial Interface channel 110 10…28V dc
    0.75 A max.
    0.94 W M23
    1738-232ASCM12 1 Serial Interface channel, RS232 75 10…28.8V dc
    1.0 A max.
    1.75 W @ 28.8V dc DC Micro (M12)
    1738-485ASCM12 1 Serial Interface channel, RS485, RS422 75 10…28.8V dc
    1.0 A max.
    1.75 W @ 28.8V dc

    Mating Cables

    The mating cables shown represent straight PVC models. For additional configurations, materials, and specifications, consult the On-Machine Connectivity catalog, publication M116-CA001.

    ArmorPoint Counter Modules Mating Cables

    ArmorPoint Cat. No. End Device per Connector Recommended Patchcord (Double-ended) Recommended Male Cordset (Single-ended) Recommended Field Attachable Connector
    1738-IJM23
    1738-VHSC24M23
    (1) M23 12-pin 889D-F4SCDM—¯ 889D–M4SC—‡ 889D-M4DC-SH
    ¯ = length in meters (1, 2, 3, 5, and 10 standard).
    ‡ = length in meters (2, 5, and 10 standard).

    ArmorPoint Serial I/O Mating Cables

    ArmorPoint Cat. No. End Device per Connector Recommended Patchcord (Double-ended) Recommended Male Cordset (Single-ended) Recommended Field Attachable Connector
    1738–SSIM23 (1) M23 12-Pin 889M–M12AH–T
    1738–232ASCM12
    1738–485ASCM12
    (1) DC Micro 889D–F4SCDM—¯ 889D–M4SC—‡ 889D–M4DC–SH
    ¯ = length in meters (1, 2, 3, 5, and 10 standard).
    ‡ = length in meters (2, 5, and 10 standard).

    Power Supplies

    ArmorPoint I/O adapters (1738–ADN12, –ADN18, –ADN18P, –ADNX, –ACNR, –AENT, –APB) have built-in POINTBus power supplies. All ArmorPoint I/O modules are powered from the POINTBus by either an adapter or expansion power supply.

    For power specifications see Communication Adapter Modules and Mating Cables

    Click to enlarge - 1738ArmorPointCommAdapMod_4C
    An auxiliary 24V dc power supply provides power to the POINTBus backplane and I/O modules. You can connect up to 17 I/O modules and an adapter with a maximum of 10 A field power, using the auxiliary power.


    ArmorPoint Expansion Power Unit

    The ArmorPoint I/O Expansion Power Unit (1738–EP24DC) passes 24V DC field power to the I/O modules to the right of it. This unit extends the backplane bus power and creates a new field voltage partition segment for driving field devices for up to 17 I/O modules. The expansion power unit separates field power from I/O modules to the left of the unit, effectively providing functional and logical partitioning for:


    Power to the POINTBus backplane and I/O modules is brought in through the auxiliary power connector. You can connect up to 12 I/O modules and an adapter with a maximum of 10 A field power, using the auxiliary power. Additional I/O modules require the use of one or more ArmorPoint I/O 24V DC expansion power units.

    Click to enlarge - 1738ArmorPointSysw1738EP24DC_4C
    The auxiliary power supports up to 17 I/O modules and an adapter with a maximum of 10 A field power. The 24V dc expansion power unit (1738-EP24DC) extends the backplane bus power to support up to 17 more I/O modules. Connect additional expansion power units to expand the I/O assembly up to the maximum of 63 I/O modules.


    ArmorPoint Field Power Distributor

    The ArmorPoint I/O Field Power Distributor Module (1738-FPD) passes through all ArmorPoint I/O backplane signals, but does not provide additional POINTBus backplane power. The field power distributor gives you the ability to change the field power distribution source for I/O modules to the right of the field power distributor. This facilitates logical or functional partitioning of low-channel count, high I/O mix applications using any of the communication adapters. Use the field power distributor with a broad range of voltage inputs including 5V dc to 250V dc and/or 24V ac to 240V ac applications and I/O modules.

    Click to enlarge - 1738ArmorPointSysw1738FPD_4C
    The ArmorPoint field power distributor (1738-FPD) discontinues the I/O circuit power bus in order to change the field power source for I/O modules to the right of it. This allows a broad range of voltage inputs in the I/O assembly.


    Specifications

    Cat. No. Power Input Voltage Range Field Side Power Requirements Inrush Current, Max. PointBus Output Current Rating Power Consumption, Max.
    1738-EP24DC 10…28.8V dc 24V dc (+20% = 28.8V dc max.) @ 400 mA 6 A for 10 ms 1.3 A 9.8 W @ 28.8V dc
    1738-FPD 5…150V dc
    24…240V ac

    Accessories, Cables and Cordsets

    Bus Extension Bases (1738-EXT1, -EXT3)

    An ArmorPoint I/O bus extension base allows the backplane to be extended to additional I/O or the ArmorStart IP 67 motor starter. May require the addition of an auxiliary power module. Refer to the installation manual (publication 1738–IN018A) to determine if a 1738–EP24DC or 1738–FPD is needed after a bus extension base.

    Click to enlarge - 1738ExtendingBase_4C


    ArmorPoint Bus Extension Bases

    Cat. No. Description
    1738-EXT1 ArmorPoint 1 meter bus extension base
    1738-EXT3 ArmorPoint 3 meter bus extension base

    ArmorPoint to ArmorStart Bus Extension Bases

    Cat. No. Description
    280A-EXT1 ArmorPoint to ArmorStart 1 meter bus extension base

    For More Information

    These and other publications are available for download from the Rockwell Automation Literature Library.

    Related Publications Publication Number
    Distributed In-Cabinet I/O
    POINT I/O Selection Guide 1734-SG001
    FLEX I/O and FLEX Ex I/O Selection Guide 1794-SG002
    FLEX Ex System Certification Reference Manual 1797-6.5.6
    Distributed I/O for On-Machine Applications
    ArmorBlock MaXum I/O and ArmorBlock I/O Selection Guide 1792-SG001
    ArmorPoint I/O Selection Guide 1738-SG001
    Embedded I/O for DeviceNet Technical Data 1799-TD001
    Cables and Cordsets
    On-Machine Connectivity Catalog M116-CA001
    On-Machine Solutions Selection Guide ONMACH-SG001