On-Machine Distributed I/O

Catalogs > Automation Systems Catalog > I/O > On-Machine Distributed I/O > 1738 ArmorPoint I/O

1738 ArmorPoint I/O

Introduction Product Design Environmentals and Certifications Communication Adapter Modules Digital DC I/O Modules
Digital AC I/O Modules Analog I/O Modules Specialty I/O Modules Power Supplies Accessories
Digital DC I/O Modules

The 1738 digital I/O modules support:


ArmorPoint Digital DC Input Modules

General-purpose 24V DC inputs including 2- and 3-wire proximity sensors.

Cat. No. Inputs On-State Voltage, Nom. Voltage Range Input Delay Time, On to Off Current, On-State Input, Min. Current, On-State Input, Max. Current, Off-State Input, Max. PointBus Current (mA) Power Dissipation, Max. Termination Type
1738-IB2M12 2 current sinking 24V DC 10V DC…28.8V DC 0.5 ms hardware + (0…65 ms selectable) 2 mA 5 mA 1.5 mA 75 mA 0.7 W at 28.8V DC DC micro (M12)
1738-IB4M12 4 current sinking 1.0 W at 28.8V DC
1738-IB4DM12 4 current sinking, Diagnostic 11V DC…28.8V DC 0…65535 ms selectable in 1 ms intervals (rounded to nearest 333 ms) Default is 1000 ms 15 mA 50 mA 0.6 W max at 28.8V DC DC micro (M12)
1738-IB4M8 4 current sinking 10V DC…28.8V DC 0.5 ms hardware + (0…65 ms selectable) 5 mA 75 mA 1.0 W at 28.8V DC Pico 3-pin (M8)
1738-IB8M12 8 current sinking 1.6 W at 28.8V DC DC micro (M12)‡ 
1738-IB8M23 1.6 W at 28.8V DC M23
1738-IB8M8 1.6 W at 28.8V DC Pico 3-pin (M8)
1738-IB16DM12 16 current sinking, Diagnostic 2.7 W at 28.8V DC DC micro (M12)
1738-IV8M12 8 current sourcing 1.6 W at 28.8V DC DC micro (M12)
1738-IV8M23 1.6 W at 28.8V DC M23
1738-IV8M8 1.6 W at 28.8V DC Pico 3-pin (M8)
1738-IV4M12 4 current sourcing 1.0 W at 28.8V DC DC micro (M12)
‡ Quantity 4.

ArmorPoint Digital DC Output Modules

24V DC electronically protected output modules. The 1738-OB2EPM12 module has 24V DC electronically protected, fast-switching high-current outputs.

Cat. No. Outputs On-State Voltage, Nom. Voltage Range Output Current Rating, Max. PointBus Current (mA) Power Dissipation, Max. Termination Type
1738-OB2EM12 2 current sourcing 24V DC 10V DC…28.8V DC 2.0 A per module, 1.0 A per channel 75 mA 0.8 W at 28.8V DC DC micro (M12)
1738-OB2EPM12 4.0 A per module, 2.0 A per channel
1738-OB4EM12 4 current sourcing 3.0 A per module, 1.0 A per channel 1.2 W at 28.8V DC
1738-OB4EM8 Pico 3-pin (M8)
1738-OB8EM12 8 current sourcing 2.0 W at 28.8V DC DC micro (M12)‡ 
1738-OB8EM23 M23
1738-OB8EM8 Pico 3-pin (M8)
1738-OB16EM12 16 current sourcing 4.0 A per module
0.5 A per channel
150 mA 3.0 W at 28.8V DC DC micro (M12)
1738-OB16E25DS D-shell⋆ 
1738-OB16E19M23 M23
1738-OV4EM12 4 current sinking 4.0 A per module, 1.0 A per channel 75 mA 2.9 W at 28.8V DC DC micro (M12)
‡ Quantity 4.
⋆ Use the 1738-CBLM25DS 25-pin D-sub connector interface cable to connect the 1738-OB16E25DS module, or another I/O module that has a similar D-sub connector, to a pneumatic valve interface.

ArmorPoint Digital DC Configurable Modules

Modules offer eight configurable 24V DC I/O points, with sealed M8 (pico) or M23 style I/O connectors. A mounting base ships with each module. The 1738-8CFGDLXM8 and 1738-8CFGDLXM23 modules include DeviceLogix functionality.

Cat. No. Inputs/Outputs On-State Voltage On-State Current PointBus Current (mA) Power Dissipation, Max. Termination Type
1738-8CFGM8 8 configurable sinking inputs or sourcing outputs 11V min
30V max
2 mA min
15 mA max
75 1.0 W at 28.8V DC Pico 3-pin (M8)
1738-8CFGM23 M23
1738-8CFGDLXM8 8 configurable sinking inputs or sourcing outputs, with DeviceLogix Pico 3-pin (M8)
1738-8CFGDLXM23 M23

ArmorPoint Digital Contact Output Modules

Individually isolated contact output modules.

Cat. No. Outputs On-State Voltage, Nom. Output Delay Time, On to Off, Max.⋆  Contact Resistance, Initial Relay Output Current Rating, Max. Leakage Current, Off-State Output, Max PointBus Current (mA) Power Dissipation, Max. Termination Type
1738-OW4M12 4 Form A (N.O.) relays, isolated 24V DC 26 ms 30 mW 1.2 mA and bleed resistor thru snubber circuit @ 240V AC 80 mA 0.5 W DC micro (M12)
1738-OW4M12AC AC micro 4-pin♣ 
⋆ Time from valid output off signal to relay deenergization by module.
♣ Quantity 2.

Mating Cables

The mating cables listed represent straight PVC models. You can also use our Product Configuration Assistant for ArmorPoint digital I/O modules to find additional mating cables, network connections, and auxiliary power connections for the I/O module you need.

ArmorPoint Digital DC Input Module Mating Cables

ArmorPoint Cat. No. End Device per Connector Recommended Patchcord (Double-ended) Recommended Male Cordset (Single-ended) Recommended Field Attachable Connector
1738-IB8M12
1738-IV8M12
1738-IB16DM12
(2) DC Micro 879D-F4ACDM—#  879D-C3ACD4M—‡ 871A-VS4-DM
(2) Pico 3-Pin 879PZ-F3ABDM4—# 
(2) Pico 4-Pin 879PZ-F4ABDM—# 
(1) DC Micro 889D-F4ACDM—#  889D-M4AC—‡ 871A-TS4-DM
(1) Pico 3-Pin 889P-F3ABDM4—# 
(1) Pico 4-Pin 889P-F4ABDM—# 
1738-IB2M12
1738-IB4M12
1738-IB4DM12
1738-IV4M12
(1) DC Micro 889D-F4ACDM—#  889D-M4AC—‡ 871A-TS4-DM
(1) Pico 3-Pin 889P-F3ABDM4—# 
(1) Pico 4-Pin 889P-F4ABDM—# 
1738-IB4M8
1738-IB8M8
1738-IV8M8
1738-8CFGM8
1738-8CFGDLXM8
(1) DC Micro 889D-F4ABP3M—#  889P-M3AB—‡ 871A-TS3-PM
(1) Pico 3-Pin 889P-F3ABPM—# 
(1) Pico 4-Pin 889P-F4ABPM3—# 
1738-IB8M23
1738-IV8M23
1738-8CFGM23
1738-8CFGDLXM23
(1) M23 12-Pin 889M-F11RMMU—#  889M-U11RM—‡ 889M-M12AH-T
#  = length in meters (1, 2, 3, 5, and 10 standard).
‡ = length in meters (2, 5, and 10 standard).

ArmorPoint Digital DC Output Module Mating Cables

ArmorPoint Cat. No. End Device per Connector Recommended Patchcord (Double-ended) Recommended Male Cordset (Single-ended) Recommended Field Attachable Connector
1738-OB8EM12
1738-OB16EM12
(2) DC Micro 879D-F4ACDM—#  879D-C3ACD4M—‡ 871A-VS4-DM
(2) Pico 3-Pin 879PZ-F3ABDM4—# 
(2) Pico 4-Pin 879PZ-F4ABDM—# 
(1) DC Micro 889D-F4ACDM—#  889D-M4AC—‡ 871A-TS4-DM
(1) Pico 3-Pin 889P-F3ABDM4—# 
(1) Pico 4-Pin 889P-F4ABDM—# 
1738-OB2EM12
1738-OB2EP12
1738-OB4EM12
1738-OV4EM12
(1) DC Micro 889D-F4ACDM—#  889D-M4AC—‡ 871A-TS4-DM
(1) Pico 3-Pin 889P-F3ABDM4—# 
(1) Pico 4-Pin 889P-F4ABDM—# 
1738-OB4EM8
1738-OB8EM8
(1) DC Micro 889D-F4ABP3M—#  889P-M3AB—‡ 871A-TS3-PM
(1) Pico 3-Pin 889P-F3ABPM—# 
(1) Pico 4-Pin 889P-F4ABPM3—# 
1738-OB8EM23 (1) M23 12-Pin 889M-F11RMMU—#  889M-U11RM—‡ 889M-M12AH-T
1738-OB16E19M23 (1) M23 19-Pin 889M-F19RM—#  889M-U19RM—‡ 889M-M19AH-T
#  = length in meters (1, 2, 3, 5, and 10 standard).
‡ = length in meters (2, 5, and 10 standard).

ArmorPoint Digital Contact Output Module Mating Cables

ArmorPoint Cat. No. End Device per Connector Recommended Patchcord (Double-ended) Recommended Male Cordset (Single-ended) Recommended Field Attachable Connector
1738-OW4M12 (1) DC Micro 889D-F4ACDM—#  889D-M4AC—‡ 871A-TS4-DM
1738-OW4M12AC (1) AC Micro 4-Pin 889R-F4AERM—#  889R-M4AEA—‡
#  = length in meters (1, 2, 3, 5, and 10 standard).
‡ = length in meters (2, 5, and 10 standard).