The ArmorPoint analog I/O modules support:
- 4…20 mA inputs and outputs
- 0…10 V inputs and outputs
- RTD inputs
- Thermocouple inputs
ArmorPoint Analog Input Modules
| Cat. No. | Inputs | Input Signal Range | Input Resolution | Absolute Accuracy¬ | Step Response, per Channel | Input Conversion Type | PointBus Current (mA) | External DC Supply Current, Nom. | Power Dissipation, Max. | Termination Type |
| 1738-IE2CM12 | 2 single-ended | 4…20 mA 0…20 mA |
16 bits - over 21 mA 0.32 mA/cnt |
0.1% Full Scale @ 25° C | 70 ms @ Notch = 60 Hz (default) 80 ms @ Notch = 50 Hz 16 ms @ Notch = 250 Hz 8 ms @ Notch = 500 Hz |
Delta Sigma | 75 mA | 10 mA @ 24V DC | 0.6 W @ 28.8V DC | DC Micro |
| 1738-IE4CM12 | 4 single-ended | 4…20 mA 0…20 mA |
16 bits - over 0…21 mA; 0.32 mA/cnt | 0.1% Full Scale @ 25°C | 50 ms @ Notch = 60 Hz (default) 60 ms @ Notch = 50 Hz 30 ms @ Notch = 100 Hz 25 ms @ Notch = 120 Hz 15 ms @ Notch = 200 Hz 12.5 ms @ Notch = 240 Hz 10 ms @ Notch = 300 Hz 7.5 ms @ Notch = 400 Hz 6.25 ms @ Notch = 480 Hz |
Sigma Delta | 75 mA | 15 mA @ 24V DC | 0.6 W @ 28.8V DC | |
| 1738-IE2VM12 | 2 single-ended | 0…10V ±10V |
15 bits plus sign 320 mV/cnt in unipolar or bipolar mode |
0.1% Full Scale @ 25° C | 70 ms @ Notch = 60 Hz (default) 80 ms @ Notch = 50 Hz 16 ms @ Notch = 250 Hz 8 ms @ Notch = 500 Hz |
Delta Sigma | 75 mA | 15 mA @ 24V DC | 0.75 W @ 28.8V DC | |
| 1738-IR2M12 | 2 single-ended RTD | 0…600 W | 16 bits 9.5 mV/cnt 0.03 °C/cnt (pt 385 @ 25 °C) |
0.1% Full Scale @ 25° CT | 60 ms @ Notch = 50 Hz 50 ms @ Notch = 60 Hz 30 ms @ Notch = 100 Hz 25 ms @ Notch = 120 Hz 15 ms @ Notch = 200 Hz 13 ms @ Notch = 240 Hz 10 ms @ Notch = 300 Hz 8 ms @ Notch = 400 Hz 6 ms @ Notch = 480 Hz |
— | 220 mA | 15 mA @ 24V DC | 1.0 W | |
| 1738-IT2IM12 | 2 single-ended Thermocouple, Millivolt |
±75 mV | 15 bits plus sign 2.5 mV per count |
0.1% Full Scale @ 25° CT | 175 mA | — | 1.0 W | |||
| ¬ Includes offset, gain, nonlinearity, and repeatability error terms. T Analog and temperature input modules support these configurable parameters and diagnostics: open-wire with LED and electronic reporting; four-alarm and annunciation set-points; calibration mode and electronic reporting; under- and over-range and electronic reporting; channel signal range and update rate and on-board scaling; filter-type; temperature scale; channel update rate. See Temperature and RTD Input Modules—Additional Specifications. |
||||||||||
Temperature and RTD Input Modules—Additional Specifications
| 1738-IR2M12 | 1738-IT2IM12 | |
| Number of Inputs | 2 single-ended RTD | 2 single-ended Isolated Thermocouple, Millivolt |
| Thermocouple Resolution | — | Type B, 30…1820° C, 3 counts/ ° C Type C, 0…2315° C, 6 counts/ ° C Type E, -270…1000° C, 24 counts/ ° C Type J, -210…1200° C, 21 counts/ ° C Type K, -270…1372° C, 13 counts/ ° C Type N, -270…1300° C, 11 counts/ ° C Type R, -50…1768.1° C, 4 counts/ ° C Type S, -50...1768.1° C, 4 counts/ ° C Type T, -270…400° C, 15 counts/ ° C |
| Cold Junction Compensation Range | — | 0…70 °C |
| Input Update Rate, per Module | 20 ms @ Notch = 50 Hz 17 ms @ Notch = 60 Hz (default) 10 ms @ Notch = 100 Hz 8 ms @ Notch = 120 Hz 5 ms @ Notch = 200 Hz 4 ms @ Notch = 240 Hz 3 ms @ Notch = 300 Hz 3 ms @ Notch = 400 Hz 2 ms @ Notch = 480 Hz |
20 ms @ Notch = 50 Hz 17 ms @ Notch = 60 Hz (default) 10 ms @ Notch = 100 Hz 8 ms @ Notch = 120 Hz 5 ms @ Notch = 200 Hz 4 ms @ Notch = 240 Hz 3 ms @ Notch = 300 Hz 3 ms @ Notch = 400 Hz 2 ms @ Notch = 480 Hz |
| Data Format | Signed integer | Signed integer |
ArmorPoint Analog Output Modules
| Cat. No. | Outputs | Output Signal Range | Output Resolution | Absolute Accuracy |
Step Response to 63% of FS |
Output Conversion Rate | PointBus Current (mA) | External DC Supply Current, Nom. | Power Dissipation, Max. | Termination Type |
| 1738-OE2CM12 | 2 single-ended | 4…20 mA 0…20 mA |
13 bits - over 21 mA 2.5 mA/cnt |
0.1% Full Scale @ 25° C¬ T | 24 ms | 16 ms | 75 mA | 50 mA @ 24V DC (including outputs @ 20 mA) | 1.0 W @ 28.8V DC | DC Micro (M12) |
| 1738-OE4CM12 | 4 single-ended | 4…20 mA 0…20 mA |
16 bits 0.32 mA/cnt |
0.1% Full Scale @ 25° C¬ T | 40 ms | 1 ms | 75 mA | 115 mA @ 24V DC (including outputs @ 20 mA) | 750 W load on each output: 1.86 W @ 28.8V DC 0 W load on each output: 2.15 W @ 28.8V DC |
|
| 1738-OE2VM12 | 2 single-ended | 0…10V ±10V |
14 bits (13 + sign) 1.28 mV/cnt in unipolar or bipolar mode |
0.1% Full Scale @ 25° C¬ T | 20 ms | 20 ms | 75 mA | 35 mA @ 24V DC (including outputs @ 3 mA) | 1.0 W @ 28.8V DC | |
| ¬ Includes offset, gain, non-linearity, and repeatability error terms. T Analog output modules support these configurable parameters and diagnostics: open-wire with LED and electronic reporting (OE2C only); fault mode; idle mode; alarms; channel signal range and on-board scaling. |
||||||||||
Mating Cables
The mating cables shown represent straight PVC models. For additional configurations, materials, and specifications, consult the On-Machine Connectivity catalog, publication M116-CA001.
ArmorPoint Analog Input Module Mating Cables
| ArmorPoint Cat. No. | End Device per Connector | Recommended Patchcord (Double-ended) | Recommended Male Cordset (Single-ended) | Recommended Field Attachable Connector |
| 1738-IE2CM12 1738-IE4CM12 1738-IE2VM12 1738-IR2M12 |
(1) DC Micro | 889D-F4SCDM—¯ | 889D-M4SC— | 889D-M4DC-SH |
| 1738-IT2IM12 | (1) DC Micro | — | — | 871A-TS4CJC-DM |
| ¯ = length in meters (1, 2, 3, 5, and 10 standard). = length in meters (2, 5, and 10 standard). |
||||
ArmorPoint Analog Output Module Mating Cables
| ArmorPoint Cat. No. | End Device per Connector | Recommended Patchcord (Double-ended) | Recommended Male Cordset (Single-ended) | Recommended Field Attachable Connector |
| 1738-OE2CM12 1738-OE4CM12 1738-OE2VM12 |
(1) DC Micro | 889D-F4SCDM—¯ | 889D-M4SC— | 889D-M4DC-SH |