On-Machine Distributed I/O

Catalogs > Automation Systems Catalog > I/O > On-Machine Distributed I/O > 1738 ArmorPoint I/O

1738 ArmorPoint I/O

Introduction Product Design Environmentals and Certifications Communication Adapter Modules Digital DC I/O Modules
Digital AC I/O Modules Analog I/O Modules Specialty I/O Modules Power Supplies Accessories
Power Supplies

ArmorPoint I/O adapters have built-in POINTBus power supplies. All ArmorPoint I/O modules are powered from the POINTBus by either an adapter or expansion power supply.

For power specifications see Communication Adapter Modules

Click to enlarge - 1738ArmorPointCommAdapMod_4C
An auxiliary 24V DC power supply provides power to the POINTBus backplane and I/O modules. You can connect up to 17 I/O modules and an adapter with a maximum of 10 A field power, using the auxiliary power.


ArmorPoint Expansion Power Unit

The ArmorPoint I/O Expansion Power Unit (1738–EP24DC) passes 24V DC field power to the I/O modules to the right of it. This unit extends the backplane bus power and creates a new field voltage partition segment for driving field devices for up to 17 I/O modules. The expansion power unit separates field power from I/O modules to the left of the unit, effectively providing functional and logical partitioning for:


Power to the POINTBus backplane and I/O modules is brought in through the auxiliary power connector. You can connect up to 12 I/O modules and an adapter with a maximum of 10 A field power, using the auxiliary power. Additional I/O modules require the use of one or more ArmorPoint I/O 24V DC expansion power units.

Click to enlarge - 1738ArmorPointSysw1738EP24DC_4C
The auxiliary power supports up to 17 I/O modules and an adapter with a maximum of 10 A field power. The 24V DC expansion power unit (1738-EP24DC) extends the backplane bus power to support up to 17 more I/O modules. Connect additional expansion power units to expand the I/O assembly up to the maximum of 63 I/O modules.


ArmorPoint Field Power Distributor

The ArmorPoint I/O Field Power Distributor Module (1738-FPD) passes through all ArmorPoint I/O backplane signals, but does not provide additional POINTBus backplane power. The field power distributor gives you the ability to change the field power distribution source for I/O modules to the right of the field power distributor. This facilitates logical or functional partitioning of low-channel count, high I/O mix applications using any of the communication adapters. Use the field power distributor with a broad range of voltage inputs including 5V DC to 250V DC and/or 24V AC to 240V AC applications and I/O modules.

Click to enlarge - 1738ArmorPointSysw1738FPD_4C
The ArmorPoint field power distributor (1738-FPD) discontinues the I/O circuit power bus in order to change the field power source for I/O modules to the right of it. This allows a broad range of voltage inputs in the I/O assembly.


Specifications

Cat. No. Power Input Voltage Range Field Side Power Requirements Inrush Current, Max. PointBus Output Current Rating Power Consumption, Max.
1738-EP24DC 10…28.8V DC 400 mA at 24V DC (+20% = 28.8V DC) 6 A for 10 ms 1.3 A 9.8 W at 28.8V DC
1738-FPD 5…150V DC
24…240V AC