Catalogs >
Automation Systems Catalog >
Operator Interface >
Graphic Terminals >
PanelView Plus Terminals
PanelView Plus Terminals
Communication
All PanelView Plus terminals come standard with Ethernet and RS-232 serial ports. The Ethernet port supports EtherNet/IP and Ethernet options using KEPServer drivers. The RS-232 port supports DF1 serial, DH-485 serial, and multi-vendor serial drivers. An optional ControlNet, DH+, DH-485, or Isolated RS-232 communication module can be added or changed after installation, except on the PanelView Plus Compact terminals which do not have a communication interface.
| Communication Port
|
Communication Modules for PanelView Plus Terminals
|
|
|
400
|
600
|
700
|
1000
|
1250
|
1500
|
| RS-232 only
|
Base unit
|
Base unit
|
N/A
|
N/A
|
N/A
|
N/A
|
| Ethernet and RS-232
|
Base unit
|
Base unit
|
Base unit
|
Base unit
|
Base unit
|
Base unit
|
| RS-232 Isolated¬
|
2711P-RN22C
|
2711P-RN22C
|
N/A
|
N/A
|
N/A
|
N/A
|
| DH-485¬
|
2711P-RN3
|
2711P-RN3
|
2711P-RN6
|
2711P-RN6
|
2711P-RN6
|
2711P-RN6
|
| DH+¬
|
2711P-RN8
|
2711P-RN8
|
2711P-RN6
|
2711P-RN6
|
2711P-RN6
|
2711P-RN6
|
| ControlNet¬
|
2711P-RN15C
|
2711P-RN15C
|
2711P-RN15S
|
2711P-RN15S
|
2711P-RN15S
|
2711P-RN15S
|
|
|
| ¬ A base unit with Ethernet and RS-232 is required to support this communication module.
|