Catalogs > Automation Systems Catalog > Operator Interface > Graphic Terminals > PanelView Plus Terminals
PanelView Plus Terminals
| Introduction | Product Design | PanelView Plus 400 and 600 Terminals | PanelView Plus and PanelView Plus CE 700-1500 Terminals | Communication |
| Specifications | Software | Accessories | For More Information |
PanelView Plus and PanelView Plus CE terminals communicate to Rockwell Automation devices over these networks:
- EtherNet/IP
- ControlNet
- DeviceNet
- Remote I/O
- DH-485
- DH+
- RS-232 (DF1, DH-485, and multivendor drivers)
All PanelView Plus terminals come standard with an Ethernet and RS-232 serial ports. The Ethernet port supports EtherNet/IP and Ethernet options using KEPServer drivers. The RS-232 port supports DF1 serial, DH-485 serial, and multi-vendor serial drivers. An optional ControlNet, DeviceNet, or DH+/DH-485/Remote I/O communication module can be added or changed after installation. Or, you can order a terminal with ControlNet or DH+/DH-485/Remote I/O as a pre-assembled option.
| Communication Port | Pre-Assembled PanelView Plus and PanelView Plus CE Terminals | Communication Module | |||||
| 400 | 600 | 700 | 1000 | 1250 | 1500 | ||
| RS-232 only (base) | Yes | Yes | N/A | N/A | N/A | N/A | |
| Ethernet & RS-232 (base) | Yes | Yes | Yes | Yes | Yes | Yes | |
| RS-232 Isolated | ¬ | ¬ | N/A | N/A | N/A | N/A | 2711P-RN22C (400 and 600) |
| DH-485 | Yes | Yes | Yes | Yes | Yes | Yes | 2711P-RN3 (400 and 600) 2711P-RN6 (700-1500) |
| DH+ | YesT | Yes | Yes | Yes | Yes | Yes | 2711P-RN8 (400 and 600) 2711P-RN6 (700-1500) |
| Remote I/O§ | YesT | Yes | Yes | Yes | Yes | Yes | 2711P-RN1 (400 and 600) 2711P-RN6 (700-1500) |
| ControlNet | | | Yes | Yes | Yes | Yes | 2711P-RN15C (400 and 600) 2711P-RN15S (700-1500) |
| DeviceNet | | | | | | | 2711P-RN10C (400 and 600) 2711P-RN10H (700-1500) |
| ¬ PanelView Plus 400 and 600 offer an isolated RS-232 communication module. This option is not pre-assembled. Select the Ethernet & RS-232 base unit (2711P-xxx20x) and the 2711P-RN22C module. T PanelView Plus 400 supports DH+ and Remote I/O communication. These options are not pre-assembled. Select the Ethernet & RS-232 base unit (2711P-K4M20x) and the DH+ (2711P-RN8) or Remote I/O (2711P-RN1) communication module. PanelView Plus 400 and 600 terminals are not available with ControlNet and DeviceNet as pre-assembled options. Select a base unit and the ControlNet (2711P-RN15C) or DeviceNet (2711P-RN10C) communication module. PanelView Plus/PanelView Plus CE 700 to 1500 terminals are not available with DeviceNet as a pre-assembled option. Select a base unit and the DeviceNet communication module (2711P-RN10H). § PanelView Plus 400 and 600 terminals support single rack Remote I/O communication. |
|||||||