Universal Remote I/O Link

Catalogs > Automation Systems Catalog > Networks and Communication > Universal Remote I/O Link > Universal Remote I/O Interfaces

Universal Remote I/O Interfaces

Universal Remote I/O Interfaces

Cat. No. Function Communication Interface Communication Rates
Supported (bit/s)
Current Load
1771-AF Fiber-Optic Converter Module Allows Universal Remote I/O and DH+ signals to travel over fiber-optic cable for routing through electrically noisy environments; converts twinax electrical signals to light (for transmission over fiber-optic cable), and then converts the light back to electrical signals (for transmission on twinax). • Twinax (Universal Remote I/O link)
• Fiber-optic pre-terminated cables 1771-PT1, -PT2, -PT3, -PT4 (Universal Remote I/O link)
• Universal Remote I/O: 57,600 and 115,200 600 mA
1771-AF1 Fiber-Optic Converter (Stand-alone) • Twinax (Universal Remote I/O link)
• Fiber-optic pre-terminated cables 1771-PT1, -PT2, -PT3, -PT4 (Universal Remote I/O link)
• Universal Remote I/O: 57,600 and 115,200 1A @ ±5V dc
1756-DHRIO DH+/RIO Communication Interface Module •Provides gateway functionality between ControlNet, Ethernet, and DH+ networks.
•Provides scanner functionality to Universal Remote I/O links adapters.
2 ports:
• DH+ or Universal Remote I/O
• DH+ or Universal Remote I/O
• For DH+: 57,600, 115,200, or 230,400
• For Universal Remote I/O: 57,600, 115,200, or 230,400
• 710 mA @ 5V dc
• 1.7 mA @ 24V dc
1784-KTX Communication Interface Card Provides a programming interface between 16-bit ISA / EISA-bus PCs and programmable controllers on the DH+, DH-485, and Universal Remote I/O networks. • Twinax (Universal Remote I/O link) • Universal Remote I/O: 57,600, 115,200, and 230,400 • 1.75A max. @ +5V dc
• 0.1A @ ±12V dc
1784-KTXD Communication Interface Card Provides a networking interface that lets one workstation communicate with processors on multiple networks simultaneously. • Twinax (Universal Remote I/O link) • Universal Remote I/O: 57,600, 115,200, and 230,400 • 1.75A max. @ +5V dc
• 0.1A @ ±12V dc
1784-KTS Communication Interface Card Provides an interface that allows direct communication between a 16-bit ISA / EISA-bus PC and A-B Universal Remote I/O devices. • Twinax (Universal Remote I/O link) • Universal Remote I/O: 57,600, 115,200, and 230,400 • 1.75A max. @ +5V dc
• 0.1A @ ±12V dc
1784-PKTX, 1784-PKTXD,
1784-PKTS
PKTx Communication Card Performs data transmission, management, and local network diagnostics for PLC-5 processors over the Universal Remote I/O link. • Twinax (Universal Remote I/O link) • Universal Remote I/O: 57,600, 115,200, and 230,400 0.8A @ 5V dc
6008-SV2R, 6008-SV1R VMEbus Remote I/O Scanner Module Gives a VME master processor direct access to adapter devices on the Universal Remote I/O link. • Twinax (Universal Remote I/O link) • Universal Remote I/O: 57,600, 115,200, and 230,400 2.5A @ 5V dc (max.)
  

For more information, see Fiber Optic Converter (stand-alone) Product Data, publication 1771-2.100.

Or for more guidelines, see the PLC-5 Design Manual, publication 1785-6.2.1.