Catalogs > Automation Systems Catalog > Networks and Communication > DH-485 Network Overview > DH-485 PC Interfaces
DH-485 PC Interfaces
DH-485 PC Interfaces | Cat. No. | Function | Communication Interface | Communication Rates (bit/s) | Current Load | |
| 1784-PKTX, 1784-PKTXD |
PKTx Communication Card | Performs data transmission, management, and local network diagnostics for SLC processors over the DH-485 link. | PKTX: 1 DH+ or Remote I/O and 1 DH-485 port PKTXD: 2 DH+ / 2 remote I/O ports and 1 DH-485 port PKTS: 1 remote I/O port |
DH-485: 1200, 2400, 4800, 9600, 19,200 | 0.8A @ 5V dc |
| 1784-KTX | ¬ Comm. Interface Card | Provides a programming interface between 16-bit ISA/ EISA-bus PCs and programmable controllers on the DH+, DH-485, and Remote I/O networks. | DH-485 DH+ |
DH-485: 1200, 2400, 4800, 9600, and 19,200 | 1.75A max. @ +5V dc 0.1A @ ±12V dc |
| 1784-KTXD | ¬ Comm. Interface Card | Provides a networking interface that lets one workstation communicate with processors on multiple networks simultaneously. | DH-485 DH+ |
DH-485: 1200, 2400, 4800, 9600, and 19200 | 1.75A max. @ +5V dc 0.1A @ ±12V dc |
| 1784-PCMK | PCMCIA Comm. Interface | Lets you program SLC 500 controllers using a Windows 95-compatible notebook computer and RSLogix 500 programming software; lets a DH+ host with RSLinx software communicate directly with DH+ stations; lets you communicate with SLC processors via the DH-485 network. | 1784-PCM4 cable to SLC 5/01, 5/02, or 5/03 processors, or other devices connected to the DH-485 network using 1747-AIC Isolated Link Couplers | DH-485: 1200, 2400, 4800, 9600, and 19200 | In accordance with Release 2.1 of the PCMCIA standard |
| 1785-KA5 | DH+/DH-485 Comm. Adapter Module | Interfaces a DH+ link to a DH-485 link (for 1771 chassis). | 2 ports: DH+ DH-485 |
DH+: 57,600 DH-485: 300, 600, 1200, 2400, 4800, 9600, 19200 |
2.0A @ 5V dc |
| 1785-KA5P | DH+/DH-485 Comm. Adapter | Interfaces a DH+ link to a DH-485 link (for panel-mounting). | 2 ports: DH+ DH-485 |
DH+: 57,600 DH-485: 300, 600, 1200, 2400, 4800, 9600, 19200 |
2.0A @ 5V dc |
| 1747-AIC | Isolated Link Coupler | Provides the connection for SLC processors and other DH-485 devices to the DH-485 network. | Shielded twisted-pair | — | 0.085A @ 24V dc |
| 1747-UIC | USB to DH-485 Interface Converter | Provides an interface between a computer's universal serial port (USB) and DH-485 ports on SLC500, MicroLogix, CompactLogix, PanelView, AIC and AIC+ products. | 2 ports: USB DH-485 (RJ-45 or 9-pin D-shell, switch selectable) |
19200 | Powered by computer's USB port |
| 1746-BAS | BASIC Module | Runs user-written BASIC programs independent of the processor. | 2 peripheral ports configurable for: RS-422 RS-485 RS-232/423 compatible: 1 DH-485 port |
300 600 1200 2400 4800 9600 19200 |
0.150A @ 5V dc 0.040A @ 24V dc |
| 1747-KE | RS-232-C / DH-485 Interface Module | Chassis-resident module that interfaces the SLC processor to an RS-232 device, like a modem. Communication between the processor and the 1747-KE occurs via a DH-485 network (and not over the backplane). | 3 ports: 1 DH-485 1 DF1 1 configuration DF1 and configuration ports accommodate RS-422, RS-485, and RS-232/423 communication configurations |
DH-485: 1200, 2400, 4800, 9600, and 19200 DF1 and configuration ports: 300, 600, 1200, 2400, 4800, 9600, and 19200 |
0.150A @ 5V dc 0.040A @ 24V dc |
| 1761-NET-AIC | AIC+ Advanced Interface Converter | Provides an interface between a DH-485 link and an RS-232 link. In some configurations, it can be powered from the RS-232 device. | 3 ports: 2 RS-232 1 DH-485 |
600 1200 2400 4800 9600 14400 19200 |
120 mA @ 24V dc 200 mA inrush at power turn-on |
| ¬ Requires a 1747-AIC Link Coupler. | |||||
For 1746-BAS, see Basic Module and Development Software Product Data, publication 1746-2.33; for 1747-KE, see DH-485/RS-232-C KE Module Product Data, publication 1747-2.37.