ControlNet Network

Catalogs > Automation Systems Catalog > Networks and Communication > ControlNet Network > ControlNet Physical Media

ControlNet Physical Media

Media Repeaters Tools
Repeaters

Repeater modules can be used to extend the length of the network, create a point-to-point, star, or ring topology, or perform network media conversion from copper (coaxial) media to fiber media, and vice versa.

Cat. No. Product Used With Description
ControlNet Repeater Modules
See the following for more information:
ControlNet Fiber Media Planning & Installation Guide, publication CNET-IN001.

ControlNet Ex Media Plannng & Installation Guide, publication CNET-IN003.
1786-RPCD Coaxial Repeater
• 2 coaxial segments per module
• point-to-point and star topologies
RG6 copper coax Extend the physical length of the ControlNet network up to 1 km
1786-RPFS Short-distance Fiber Repeater
• 2 fiber segments per module
• point-to-point and star topologies
V-pin (use pre-made 1786-FSxx 10-300 m cables) Optically isolate and extend the physical length of the ControlNet network up to 300 m
1786-RPFM Medium-distance Fiber Repeater
• 2 fiber segments per module
• point-to-point and star topologies
ST 62.5/125 um multimode fiber Optically isolate and extend the physical length of the ControlNet network up to 3 km
1786-RPFRL/B Long-distance Fiber Ring Repeater
• 2 fiber segments per module
• point-to-point, star, and ring topologies
• Fault Relay for runtime diagnostics
ST 62.5/125 um multimode fiber Optically isolate and provide fiber ring media redundancy
or
Extend the physical length of the ControlNet network up to 10 km
1786-RPFRXL/B Extra-long-distance Fiber Ring Repeater
• 2 fiber segments per module
• point-to-point, star, and ring topologies
• Fault Relay for runtime diagnostics
ST 62.5/125 um multimode fiber
or
ST 9/125 um single mode fiber
Optically isolate and provide fiber ring media redundancy
or
Extend the physical length of the ControlNet network up to 20 km
1797-RPFM Intrinsically Safe Medium-distance Repeater
• 2 fiber segments per module
• point-to-point and star topologies
• connect the 1797-RPFM repeater module (in an intrinsically safe area) to the 1786-RPFM repeater module (in a non-intrinsically safe area) using fiber
ST 62.5/125 um multimode fiber Optically isolate for intrinsically safe areas
or
Extend the physical length of the ControlNet network up to 3 km
ControlNet Repeater Adapters
See the following for more information:
ControlNet Fiber Media Planning & Installation Guide, publication CNET-IN001.

ControlNet Ex Media Plannng & Installation Guide, publication CNET-IN003.
1786-RPA/B Modular Repeater Adapter
• supplies power for up to 4 repeater modules (1786-RPCD, -RPFS, and -RPFM)
• supplies power for up to 2 repeater modules (1786-RPFRL, -RPFXL)
• one coax BNC connection
RG6 copper coax Use with these repeater modules:
1786-RPCD
1786-RPFS
1786-RPFM
1786-RPFRL
1786-RPFRXL
1797-RPA Intrinsically Safe Modular Repeater Adapter
• supplies power for up to 2 repeater modules (1797-RPFM)
• one coax BNC connection
RG6 copper coax Use with these repeater modules:
1797-RPFM