MicroLogix 1000 Controllers
| Product Overview |
System Overview
|
The MicroLogix 1000 family provides small, economical programmable controllers. They are available in configurations of 10 digital I/O (6 inputs and 4 outputs), 16 digital I/O (10 inputs and 6 outputs), 25 I/O (12 digital inputs, 4 analog inputs, 8 digital outputs, and 1 analog output), or 32 digital I/O (20 inputs and 12 outputs) in multiple electrical configurations of digital I/O. The I/O options and electrical configurations make them ideal for many applications.
Benefits
- Compact design—Lets the MicroLogix 1000 controller thrive in limited panel space.
- Choice of communication networks—An RS-232-C communication port is configurable for: DF1 protocol for direct connection to a programming device or operator interface; DH-485 networking through a 1761-NET-AIC converter; DeviceNet networking through a 1761-NET-DNI interface; EtherNet/IP networking through a 1761-NET-ENI interface; or for half-duplex slave protocol in SCADA applications.
- Simple programming with your choice of programming device—You can program these controllers in familiar ladder logic with MicroLogix 1000 A.I. Series Software®, PLC 500 A. I. Series Programming Software, RSLogix 500™ Windows Programming Software, or the MicroLogix Hand-Held Programmer (1761-HHP-B30). This symbolic programming language is based on relay ladder wiring diagrams that simplify the creation and troubleshooting of your control program.
- Comprehensive instruction set—Over 65 instructions including simple bit, timer, and counter instructions, as well as instructions for powerful applications like sequencers, high-speed counter, and shift registers.
- Fast—Execution time for a typical 500-instruction program is only 1.56 ms.
- Choice of languages—Software and documentation are available in 5 languages. The hand-held programmer has 6 languages built in.
Product Design
The MicroLogix 1000 controller contains the power supply, processor, and all its I/O circuits packaged in a single unit.
- Four I/O sizes (10, 16, 25, and 32) cover many applications.
- Various electrical configurations of digital I/O offer you a controller that meets your electrical requirements:
- 24V DC inputs and relay outputs with a 24V DC power supply.
- 24V DC inputs and 24V DC FET and relay outputs with a 24V DC power supply.
- 24V DC inputs and relay outputs with a 120/240V AC power supply.
- 24V AC inputs and relay outputs with a 120/240V AC power supply.
- 120V AC inputs and relay outputs with a 120/240V AC power supply.
- 120V AC inputs and triAC and relay outputs with a 120/240V AC power supply.
- 24V DC inputs and relay outputs with a 24V DC power supply.
- Isolated relay contact outputs (at least two per controller). Allow outputs on the same unit to switch different control voltages.
- The 25-I/O models include 4 analog inputs and an analog output in addition to the 12 digital inputs and the 8 digital (contact) outputs.
Communication
- Point-to-Point—RS-232 communication port configurable for direct connection to your programming device.
- DH-485—RS-232 communication port configurable for DH-485 communication through an AIC+ (1761-NET-AIC) converter. Lets you communicate with SLC 500 processors, other MicroLogix controllers, operator interfaces, or programming devices in a DH-485 network.
- EtherNet/IP—RS-232 communication port configurable for EtherNet/IP communication through an EtherNet/IP-to-RS-232 interface (1761-NET-ENI). The 1761-NET-ENI supports program monitoring and upload/download, data collection from PCs or mainframes, and controller peer-to-peer communication. It can also send e-mail messages via SMTP (Simple Mail Transfer Protocol), and can display status and configuration information through a built-in Internet server.
- DeviceNet—RS-232 communication port configurable for communication through a DeviceNet interface (1761-NET-DNI) lets the controller function as a slave node in a DeviceNet network or as a peer to other controllers also using the 1761-NET-DNI interface.
- DF1, half-duplex—RS-232 communication port configurable for DF1 half-duplex slave protocol for connection to a modem in SCADA applications.
|
|
Typical Configurations
|
|
|
|
|
Specifications
General Specifications
| 24V DC Sensor Power | 200 mA max. with 200 mF capacitive load max. (for 1761-L10BWA, -L16NWA, -L16BWA, -L20BWA-5A, and -L32BWA only) |
| Power Cycles | 50,000 minimum |
| Temperature, operating | |
| 0…55 °C (32…131 °F) | |
| 0…40 °C (32…104 °F) | |
| Temperature, nonoperating | -40…85 °C (-40…185 °F) |
| Humidity | 5…95% (without condensation) |
| Shock, operating | 10 g peak acceleration (7.5g DIN rail mounted)¬ (11±1 ms duration), 3 times each direction, each axis |
| Shock, nonoperating | 20 g peak acceleration (11±1 ms duration), 3 times each direction, each axis |
| Vibration | 5 Hz to 2 kHz, 0.381 mm (0.015 in) peak-to-peak / 2.5 g panel mountedT , 1hr per axis |
| Vibration, Non-Operating | 5 Hz to 2 kHz, 0.762 mm (0.030 in) peak-to-peak / 5 g panel mounted, 1hr per axis |
| Terminal Screw Torque | 0.9 N-m maximum (8.0 pound-inch) |
| Electrostatic Discharge | IEC801-2 @ 8 KV |
| Radiated Susceptibility | IEC801-3 @ 10V/m, 27…1000 MHz 3V/m, 87…108 MHz, 174…230 MHz, and 470…790 MHz |
| Fast Transient | IEC801-4 @ 2 KV Power Supply, 1 KV I/O |
| Isolation | 1500V AC |
| Memory Type | EEPROM |
| Memory Size | 1K words (approximately 737 instruction words, 437 data-table words) |
| Timers/Counters, Max. | 40 timers; 32 counters (fixed) |
| Program Scan Time/Kword, Typical | 2 ms |
| I/O Scan Time, Typical | 0.21 ms |
| Communication Port | RS-232-C (Can be configured for communication through 1761-NET-AIC in a DH-485 network) |
| ¬ Relays are derated an additional 2.5g on 32 I/O controllers. T DIN rail mounted controller is 1g. |
|
MicroLogix 1000 Controllers
| Cat. No. | I/O | Digital Inputs | Analog Inputs |
Digital Outputs | Analog Outputs | Real Input Power |
Apparent Input Power |
Transformer Load |
| 1761-L10BWA | 10 | 6 inputs 24V DC sink/source |
0 | 4 contact outputs | 0 | 13W @ 120V AC 14W @ 240V AC |
24 VA @ 120V AC 32 VA @ 240V AC |
33 VA @ 120V AC 35 VA @ 240V AC |
| 1761-L10BWB | 10 | 6 inputs 24V DC sink/source |
0 | 4 contact outputs | 0 | 5W @ 24V DC | — | — |
| 1761-L10BXB | 10 | 6 inputs 24V DC sink/source |
0 | 2 contact outputs 2 source 24V DC outputs |
0 | 5W @ 24V DC | — | — |
| 1761-L16AWA | 16 | 10 inputs 120V AC |
0 | 6 contact outputs | 0 | 7W @ 120V AC 8W @ 240V AC |
15 VA @ 120V AC 21 VA @ 240 AC |
18 VA @ 120V AC 20 VA @ 240V AC |
| 1761-L32AWA | 32 | 20 inputs 120V AC |
0 | 12 contact outputs | 0 | 9.1W @ 120V AC 10.6W @ 240V AC |
19 VA @ 120V AC 25 VA @ 240V AC |
23 VA @ 120V AC 27 VA @ 240V AC |
| 1761-L16BWA | 16 | 10 inputs 24V DC sink/source |
0 | 6 contact outputs | 0 | 14W @ 120V AC 15W @ 240V AC |
26 VA @ 120V AC 33 VA @ 240V AC |
35 VA @ 120V AC 38 VA @ 240V AC |
| 1761-L16NWA | 16 | 10 inputs 24V DC sink/source or 24V AC |
0 | 6 contact outputs | 0 | 14W @ 120V AC 15W @ 240V AC |
26 VA @ 120V AC 33 VA @ 240V AC |
35 VA @ 120V AC 38 VA @ 240V AC |
| 1761-L32BWA | 32 | 20 inputs 24V DC sink/source |
0 | 12 contact outputs | 0 | 15W @ 120V AC 16W @ 240V AC |
29 VA @ 120V AC 36 VA @ 240V AC |
38 VA @ 120V AC 40 VA @ 240V AC |
| 1761-L32AAA | 32 | 20 inputs 120V AC |
0 | 10 triAC outputs, 120/240V AC 2 contact outputs |
0 | 7W @ 120V AC 9W @ 240V AC |
16 VA @ 120V AC 22 VA @ 240V AC |
18 VA @ 120V AC 23 VA @ 240V AC |
| 1761-L16BWB | 16 | 10 inputs 24V DC sink/source |
0 | 6 contact outputs | 0 | 5W @ 24V DC | — | — |
| 1761-L16NWB | 16 | 10 inputs 24V DC sink/source or 24V AC |
0 | 6 contact outputs | 0 | 5W @ 24V DC | — | — |
| 1761-L32BWB | 32 | 20 inputs 24V DC sink/source |
0 | 12 contact outputs | 0 | 7W @ 24V DC | — | — |
| 1761-L16BBB | 16 | 10 inputs 24V DC sink/source |
0 | 4 source 24V DC outputs 2 contact outputs |
0 | 5W @ 24V DC | — | — |
| 1761-L32BBB | 32 | 20 inputs 24V DC sink/source |
0 | 10 source 24V DC outputs 2 contact outputs |
0 | 7W @ 24V DC | — | — |
| 1761-L20AWA-5A | 25 | 12 inputs 120V AC |
2 voltage (±10V) 2 current (0…20 mA) |
8 contact outputs | 1 voltage/current (0…10V, 4…20 mA) |
12W @ 120V AC 13W @ 240V AC |
20 VA @ 120V AC 27 VA @ 240V AC |
30 VA @ 120V AC 33 VA @ 240V AC |
| 1761-L20BWA-5A | 25 | 12 inputs 24V DC sink/source |
2 voltage (±10V) 2 current (0…20 mA) |
8 contact outputs | 1 voltage/current (0…10V, 4…20 mA) |
18W @ 120V AC 19W @ 240V AC |
30 VA @ 120V AC 38 VA @ 240V AC |
45 VA @ 120V AC 48 VA @ 240V AC |
| 1761-L20BWB-5A | 25 | 12 inputs 24V DC sink/source |
2 voltage (±10V) 2 current (0…20 mA) |
8 contact outputs | 1 voltage/current (0…10V, 4…20 mA) |
7W @ 24V DC | — | — |
Analog Input Specifications
| Voltage Range | ±10.5V -1LSB |
| Current Range | 0…20 mA -1LSB |
| Data Format | Natural binary 16-bit signed integer |
| Voltage Input Impedance | 210 kW |
| Current Input Impedance | 160 kW |
| Resolution | 16 bits¬ |
| Overall Accuracy 0…55 °C | ±0.7% of full scale |
| ¬ Also a function of the input filter selection. | |
Analog Output Specifications
| Voltage Range | 0…10V -1LSB |
| Current Range | 4…20 mA -1LSB |
| Data Format | Natural binary 16-bit signed integer |
| Step Response | 2.5 ms @ 95% |
| Load Range | 0…500W |
| Current Output Coding (4…20 mA -1LSB, 0…10V -1LSB) |
0…32,767 |
| Resolution | 15 bits |
| Overall Accuracy 0…55 °C | ±1.0% of full scale |