MicroLogix 1000 System

Catalogs > Automation Systems Catalog > Programmable Controllers > MicroLogix 1000 System > MicroLogix 1000 Controllers

MicroLogix 1000 Controllers

Introduction Product Design Communication Typical Configurations Specifications
Specifications

General Specifications

24V DC Sensor Power 200 mA max. with 200 mF capacitive load max.
(for 1761-L10BWA, -L16NWA, -L16BWA, -L20BWA-5A, and -L32BWA only)
Power Cycles 50,000 minimum
Operating Temperature
Horizontal mounting
0…55 °C (32…131 °F)
Vertical mounting
0…40 °C (32…104 °F)
Nonoperating Temperature -40…85 °C (-40…185 °F)
Relative Humidity 5…95% noncondensing
Operating Shock 10 g peak acceleration (7.5g DIN rail mounted)⋆  (11±1 ms duration), 3 times each direction, each axis
Nonoperating Shock 20 g peak acceleration (11±1 ms duration), 3 times each direction, each axis
Vibration 5 Hz…2 kHz, 0.381 mm (0.015 in) peak-to-peak, 2.5 g panel mounted, 1 hr per axis
Vibration, Non-Operating 5 Hz…2 kHz, 0.762 mm (0.030 in) peak-to-peak, 5 g, 1 hr per axis
Terminal Screw Torque 0.9 N•m max (8.0 lb•in)
ESD Immunity 8 kV air (IEC801-2)
Radiated RF Immunity 10V/m, 27…1000 MHz, 3V/m, 87…108 MHz, 174…230 MHz, and 470…790 MHz (IEC801-3)
EFT/B Immunity 2 kV Power Supply, 1 kV I/O (IEC801-4)
Isolation Voltage 1500V AC
Memory Type EEPROM
Memory Size 1K words (approximately 737 instruction words, 437 data-table words)
Timers/Counters, Max. 40 timers; 32 counters (fixed)
Program Scan Time/Kword, Typical 2 ms
I/O Scan Time, Typical 0.21 ms
Communication Port RS-232-C (Can be configured for communication through 1761-NET-AIC in a DH-485 network)
  
⋆ Relays are derated an additional 2.5 g on 32 I/O controllers.
‡ DIN rail mounted controller is 1 g.

MicroLogix 1000 Controllers

Cat. No. I/O Digital Inputs Analog Inputs Digital Outputs Analog Outputs Real Input Power Apparent Input Power Transformer Load
1761-L10BWA 10 6 inputs
24V DC sink/source
0 4 contact outputs 0 13 W at 120V AC
14 W at 240V AC
24 VA at 120V AC
32 VA at 240V AC
33 VA at 120V AC
35 VA at 240V AC
1761-L10BWB 10 6 inputs
24V DC sink/source
0 4 contact outputs 0 5 W at 24V DC
1761-L10BXB 10 6 inputs
24V DC sink/source
0 2 contact outputs
2 source 24V DC outputs
0 5 W at 24V DC
1761-L16AWA 16 10 inputs
120V AC
0 6 contact outputs 0 7 W at 120V AC
8 W at 240V AC
15 VA at 120V AC
21 VA at 240 AC
18 VA at 120V AC
20 VA at 240V AC
1761-L32AWA 32 20 inputs
120V AC
0 12 contact outputs 0 9.1 W at 120V AC
10.6 W at 240V AC
19 VA at 120V AC
25 VA at 240V AC
23 VA at 120V AC
27 VA at 240V AC
1761-L16BWA 16 10 inputs
24V DC sink/source
0 6 contact outputs 0 14 W at 120V AC
15 W at 240V AC
26 VA at 120V AC
33 VA at 240V AC
35 VA at 120V AC
38 VA at 240V AC
1761-L16NWA 16 10 inputs
24V DC sink/source or 24V AC
0 6 contact outputs 0 14 W at 120V AC
15 W at 240V AC
26 VA at 120V AC
33 VA at 240V AC
35 VA at 120V AC
38 VA at 240V AC
1761-L32BWA 32 20 inputs
24V DC sink/source
0 12 contact outputs 0 15 W at 120V AC
16 W at 240V AC
29 VA at 120V AC
36 VA at 240V AC
38 VA at 120V AC
40 VA at 240V AC
1761-L32AAA 32 20 inputs
120V AC
0 10 triAC outputs, 120/240V AC
2 contact outputs
0 7 W at 120V AC
9 W at 240V AC
16 VA at 120V AC
22 VA at 240V AC
18 VA at 120V AC
23 VA at 240V AC
1761-L16BWB 16 10 inputs
24V DC sink/source
0 6 contact outputs 0 5 W at 24V DC
1761-L16NWB 16 10 inputs
24V DC sink/source or 24V AC
0 6 contact outputs 0 5 W at 24V DC
1761-L32BWB 32 20 inputs
24V DC sink/source
0 12 contact outputs 0 7 W at 24V DC
1761-L16BBB 16 10 inputs
24V DC sink/source
0 4 source 24V DC outputs
2 contact outputs
0 5 W at 24V DC
1761-L32BBB 32 20 inputs
24V DC sink/source
0 10 source 24V DC outputs
2 contact outputs
0 7 W at 24V DC
1761-L20AWA-5A 25 12 inputs
120V AC
2 voltage (±10V)
2 current (0…20 mA)
8 contact outputs 1 voltage/current
(0…10V, 4…20 mA)
12 W at 120V AC
13 W at 240V AC
20 VA at 120V AC
27 VA at 240V AC
30 VA at 120V AC
33 VA at 240V AC
1761-L20BWA-5A 25 12 inputs
24V DC sink/source
2 voltage (±10V)
2 current (0…20 mA)
8 contact outputs 1 voltage/current
(0…10V, 4…20 mA)
18 W at 120V AC
19 W at 240V AC
30 VA at 120V AC
38 VA at 240V AC
45 VA at 120V AC
48 VA at 240V AC
1761-L20BWB-5A 25 12 inputs
24V DC sink/source
2 voltage (±10V)
2 current (0…20 mA)
8 contact outputs 1 voltage/current
(0…10V, 4…20 mA)
7 W at 24V DC
  

Analog Input Specifications

Voltage Range ±10.5V -1LSB
Current Range 0…20 mA -1LSB
Data Format Natural binary 16-bit signed integer
Voltage Input Impedance 210 kW
Current Input Impedance 160 kW
Resolution 16 bits⋆ 
Overall Accuracy 0…55 °C ±0.7% of full scale
  
⋆ Also a function of the input filter selection.

Analog Output Specifications

Voltage Range 0…10V -1LSB
Current Range 4…20 mA -1LSB
Data Format Natural binary 16-bit signed integer
Step Response 2.5 ms at 95%±10.5V -1LSB
Load Range 0…500 W
Output Coding
(4…20 mA -1LSB, 0…10V -1LSB)
0…32,767
Resolution 15 bits
Overall Accuracy 0…55 °C ±1.0% of full scale