Catalogs > Automation Systems Catalog > Programmable Controllers > MicroLogix 1000 System > Communication Interfaces
Communication Interfaces
MicroLogix Communication Interfaces| Cat. No. | Description | Features |
| 1761-NET-AIC | AIC+ Advanced Interface Converter | Lets you connect a MicroLogix controller or other DH-485-capable RS232-C device to the DH-485 network Allows a MicroLogix controller to initiate or respond to communication with any other device (SLC 500 processors, other MicroLogix controllers, operator interfaces, or programming devices) on the network |
| 1761-NET-DNI | DeviceNet RS-232-C Interface |
Lets you connect a MicroLogix controller or other DF1 full-duplex addressable RS-232-C device to the DeviceNet network. Allows a MicroLogix controller to function as a DeviceNet slave node to provide 16 words of input data and 16 words of output data that can be exchanged with the DeviceNet scanner. Supports peer-to peer messaging between controllers Lets you connect a computer to the DeviceNet network for peer-to-peer messaging, for programming, and for on-line monitoring |
| 1761-NET-ENI | EtherNet/IP RS-232-C Interface |
Lets you connect a MicroLogix controller or other DF1 full-duplex addressable RS-232-C device to the EtherNet/IP network Supports program monitoring and upload/download Supports data collection from PCs or mainframe computers Supports controller peer-to-peer communication Supports e-mail messages via SMTP 1761-NET-ENIW Web-enabled module provides read/write data table access via a web browser |
| 1761-NET-ENIW | EtherNet/IP RS-232-C Interface, Web Enabled |
Specifications
| Specifications | 1761-NET-AIC | 1761-NET-DNI | 1761-NET-ENI | 1761-NET-ENIW |
| Description | AIC+ advanced interface converter | DeviceNet interface | Ethernet interface | Web-enabled Ethernet interface |
| Communication Interface | 2 RS-232 ports 1 DH-485 port DH-485 protocol on all ports for networking |
Dual-shielded twisted pair cable (DeviceNet network) DF1 full-duplex protocol on RS-232 port |
10/100 Base-T (RJ45) port with embedded LEDs DF1 full-duplex protocol on RS-232 port |
|
| Power Supply DC Voltage Range ¬ | 20.4…28.8V DC | 11…25V DC | 20.4…26.4V DC | |
| Current Draw (mA) at 24V DC | 120 mA | 200 mA | 50 mA | |
| Inrush Current, Max. | 200 mA @ 24V | 400 mA at 24V | 200 mA @ 24V | |
| Isolation Voltage | Tested at 500V DC for 60 s | Tested at 500V DC for 60 s | Tested at 710V DC for 60 s | |
| Operating Temperature | 0…60 °C (32…140 °F) | 0…55 °C (32…131 °F) | ||
| Nonoperating Temperature | -40…85 °C (-40…185 °F) | |||
| Relative Humidity | 5…95% noncondensing | |||
| Vibration | Operating: 10…500 Hz, 5.0 g, 0.030 in. peak-to-peak, 2 hour each axis | Operating: 5…2000 Hz, 2.5 g, 0.015 in. peak-to-peak, 1 hour each axis Non-operating: 5…2000 Hz, 5.0g, 0.030 in. peak-to-peak, 1 hour each axis |
Operating: 10…500 Hz, 5.0 g, 0.030 in. peak-to-peak, 2 hour each axis | |
| Operating Shock | 30 g, ±3 times each axis | |||
| Nonoperating Shock | 50 g, ±3 times each axis | 35 g (DIN rail mount) 50 g (panel mount) ±3 times each axis | ||
| Certifications | UL Listed Industrial Control Equipment for use in Class 1, Division 2, Hazardous Locations, Groups A, B, C, D. | |||
| c-UL Listed Industrial Control Equipment for use in Canada. | ||||
| CE marked for all applicable directives. | ||||
| C-Tick marked for all applicable acts | ||||
| ¬ When the device is connected to a MicroLogix 1000, 1200, or 1500 controller, power is provided by the MicroLogix controller's communication port. Power is not supplied by the MicroLogix 1100 and 1400 controllers. External 24V DC module power must be supplied. | ||||