MicroLogix 1000 System

Catalogs > Automation Systems Catalog > Programmable Controllers > MicroLogix 1000 System > Communication Interfaces

Communication Interfaces

MicroLogix Communication Interfaces

Cat. No. Description Features
1761-NET-AIC AIC+ Advanced Interface Converter • Lets you connect a MicroLogix controller or other DH-485-capable RS232-C device to the DH-485 network
• Allows a MicroLogix controller to initiate or respond to communication with any other device (SLC 500 processors, other MicroLogix controllers, operator interfaces, or programming devices) on the network
1761-NET-DNI DeviceNet RS-232-C Interface • Lets you connect a MicroLogix controller or other DF1 full-duplex addressable RS-232-C device to the DeviceNet network.
• Allows a MicroLogix controller to function as a DeviceNet slave node to provide 16 words of input data and 16 words of output data that can be exchanged with the DeviceNet scanner.
• Supports peer-to peer messaging between controllers
• Lets you connect a computer to the DeviceNet network for peer-to-peer messaging, for programming, and for on-line monitoring
1761-NET-ENI EtherNet/IP RS-232-C Interface • Lets you connect a MicroLogix controller or other DF1 full-duplex addressable RS-232-C device to the EtherNet/IP network
• Supports program monitoring and upload/download
• Supports data collection from PCs or mainframe computers
• Supports controller peer-to-peer communication
• Supports e-mail messages via SMTP
• 1761-NET-ENIW Web-enabled module provides read/write data table access via a web browser
1761-NET-ENIW EtherNet/IP RS-232-C Interface, Web Enabled

Specifications

Specifications 1761-NET-AIC 1761-NET-DNI 1761-NET-ENI 1761-NET-ENIW
Description AIC+ advanced interface converter DeviceNet interface Ethernet interface Web-enabled Ethernet interface
Communication Interface • 2 RS-232 ports
• 1 DH-485 port
• DH-485 protocol on all ports for networking
• Dual-shielded twisted pair cable (DeviceNet network)
• DF1 full-duplex protocol on RS-232 port
• 10/100 Base-T (RJ45) port with embedded LEDs
• DF1 full-duplex protocol on RS-232 port
Power Supply DC Voltage Range ⋆  20.4…28.8V DC 11…25V DC 20.4…26.4V DC
Current Draw (mA) at 24V DC 120 mA 200 mA 50 mA
Inrush Current, Max. 200 mA @ 24V 400 mA at 24V 200 mA @ 24V
Isolation Voltage Tested at 500V DC for 60 s Tested at 500V DC for 60 s Tested at 710V DC for 60 s
Operating Temperature 0…60 °C (32…140 °F) 0…55 °C (32…131 °F)
Nonoperating Temperature -40…85 °C (-40…185 °F)
Relative Humidity 5…95% noncondensing
Vibration Operating: 10…500 Hz, 5.0 g, 0.030 in. peak-to-peak, 2 hour each axis Operating: 5…2000 Hz, 2.5 g, 0.015 in. peak-to-peak, 1 hour each axis
Non-operating: 5…2000 Hz, 5.0g, 0.030 in. peak-to-peak, 1 hour each axis
Operating: 10…500 Hz, 5.0 g, 0.030 in. peak-to-peak, 2 hour each axis
Operating Shock 30 g, ±3 times each axis
Nonoperating Shock 50 g, ±3 times each axis 35 g (DIN rail mount) 50 g (panel mount) ±3 times each axis
Certifications UL Listed Industrial Control Equipment for use in Class 1, Division 2, Hazardous Locations, Groups A, B, C, D.
c-UL Listed Industrial Control Equipment for use in Canada.
CE marked for all applicable directives.
C-Tick marked for all applicable acts
⋆  When the device is connected to a MicroLogix 1000, 1200, or 1500 controller, power is provided by the MicroLogix controller's communication port. Power is not supplied by the MicroLogix 1100 and 1400 controllers. External 24V DC module power must be supplied.