MicroLogix 1500 System

Catalogs > Automation Systems Catalog > Programmable Controllers > MicroLogix 1500 System > System Overview

System Overview

Introduction System Components Product Design Communication Typical Configurations General Specifications Additional Resources
General Specifications

These specifications cover the base unit, the processor module, real-time-clock/memory module, and data access tool.

Temperature, nonoperating -40…85 °C (-40…185 °F)
Temperature, operating 0…55 °C (32…131 °F)
Operating Humidity 5…95% (without condensation)
Operating Altitude 2,000 m (6,561 ft) max.
Vibration
Operating
10…500 Hz, 5g, 0.030 inch maximum peak-to-peak
Relay Operation
2g
Shock (Without Data Access Tool installed)
Operating
30g panel mounted (15g DIN Rail mounted)
Relay Operation
7.5g panel mounted (5g DIN Rail mounted)
Non-Operating
40g panel mounted (30g DIN Rail mounted)
Shock (With Data Access Tool installed)
Operating
20g panel mounted (15g DIN Rail mounted)
Relay Operation
7.5g panel mounted (5g DIN Rail mounted)
Non-Operating
30g panel mounted (20g DIN Rail mounted)
Weight 0.9 kg (2.0 lb)
Agency Certification C-UL certified (under CSA C22.2 No. 142)
UL 508 listed
CE compliant for all applicable directives
Hazardous Environment Class Class I, Division 2, Hazardous Location, Groups A, B, C, D (UL 1604, C-UL under CSA C22.2 No. 213)
Radiated and Conducted Emissions EN50081-2 Class A
Electrical and EMC: The module has passed testing at the following levels:
ESD Immunity (IEC1000-4-2) 4 kV contact, 8 kV air, 4 kV indirect
Radiated immunity (IEC1000-4-3) 10V/m, 80…1000 MHz, 80% amplitude modulation, +900 MHz keyed carrier
Fast Transient Burst (IEC1000-4-4) 2 kV, 5 kHz
Surge Immunity (IEC1000-4-5) 2 kV common mode, 1 kV differential mode
Conducted Immunity (IEC1000-4-6) 10V, 0.15…80 MHz¬ 
  
¬ Conducted immunity frequency range may be 150 kHz…30 MHz if the radiated immunity frequency range is 30 MHz…1000 MHz.