Catalogs > Automation Systems Catalog > Programmable Controllers > MicroLogix 1500 System > 1769 Compact I/O
1769 Compact I/O
| Introduction | Environmentals and Certifications | Digital I/O Modules | Analog I/O Modules | Specialty I/O Modules | Accessories—I/O Modules | DeviceNet I/O Adapter Module |
An I/O adapter module installed at the left end of the first bank of I/O modules interfaces these I/O modules with a DeviceNet link for communication with a DeviceNet scanner port at another location. The 1769-ADN DeviceNet I/O adapter module can interface 1, 2, or 3 banks of 1769 I/O modules for a maximum total of 30 I/O modules at a DeviceNet node. A single bank can consist of a maximum of 12 I/O modules.
The adapter supports a total of 180 words of input data and 180 words of output data from the I/O modules. The adapter supports a total of 724 words of configuration data for the I/O modules. The adapter also supports change-of-state, cyclic, and polling modes. Each bank of I/O modules must include a 1769 power supply. You connect the banks of I/O modules with 1769 expansion cables.
Note that since the MicroLogix 1500 controller and CompactLogix L20, L30, L321, L32E and L35E controller can be used with the 1769-SDN DeviceNet scanner, the 1769-ADN DeviceNet I/O adapter module can be used to interface remotely located 1769 I/O modules.
Typical Configuration
|
Specifications
| Cat. No. | 1769-ADN |
| Backplane Current at 5V | 500 mA |
| I/O Capacity | 30 modules |
| DeviceNet Communication Rate | 125 Kbps 250 Kbps 500 Kbps |
| DeviceNet Power Requirements | 90 mA at 24V DC Class 2/SELV |
| DeviceNet Cable | Allen-Bradley part no. 1485C-P1-Cxxx. |
| Power supply distance rating | 5 modules ⋆ |
| Isolation Voltage | 30V (continuous), Basic Insulation Type, DeviceNet to Backplane Type tested at 710V DC for 60 s |
| Dimensions (HxWxD), Approx. | 118 x 50 x 87 mm§ (4.65 x 1.97 x 3.43 in♣ ) |
| Weight | 0.28 kg (0.61 lb) |
| Agency Certification (When product is marked.) |
c-UL-us certified for Class I, Division 2, Groups A…D Hazardous Locations CE compliant for all applicable directives C-Tick Australian Radio communications Act, compliant with: AS/NZS 2064; Industrial Emissions DeviceNet: ODVA conformance tested to ODVA DeviceNet specifications |
| Hazardous Environment Class | Class I, Division 2, Hazardous Location, Groups A, B, C, D certified for U.S. and Canada |
| ⋆ The adapter must not be more than 5 modules away from the 1769 power supply in the bank of 1769 I/O modules. Refer to publication DN-2.5 for more information. § Height including mounting tabs is 138 mm. ♣ Height including mounting tabs is 5.43 in. |
|