Introduction Environmentals and Certifications Digital I/O Modules Analog I/O Modules Specialty I/O Modules Accessories—I/O Modules DeviceNet I/O Adapter Module
DeviceNet I/O Adapter Module

An I/O adapter module installed at the left end of the first bank of I/O modules interfaces these I/O modules with a DeviceNet link for communication with a DeviceNet scanner port at another location. The 1769-ADN DeviceNet I/O adapter module can interface 1, 2, or 3 banks of 1769 I/O modules for a maximum total of 30 I/O modules at a DeviceNet node. A single bank can consist of a maximum of 12 I/O modules.

The adapter supports a total of 180 words of input data and 180 words of output data from the I/O modules. The adapter supports a total of 724 words of configuration data for the I/O modules. The adapter also supports change-of-state, cyclic, and polling modes. Each bank of I/O modules must include a 1769 power supply. You connect the banks of I/O modules with 1769 expansion cables.

Note that since the MicroLogix 1500 controller and CompactLogix L20, L30, L321, L32E and L35E controller can be used with the 1769-SDN DeviceNet scanner, the 1769-ADN DeviceNet I/O adapter module can be used to interface remotely located 1769 I/O modules.


Typical Configuration

Click to enlarge - 1769TypicalConfig_4C


Specifications

Cat. No. 1769-ADN
Backplane Current at 5V 500 mA
I/O Capacity 30 modules
DeviceNet Communication Rate 125 Kbps
250 Kbps
500 Kbps
DeviceNet Power Requirements 90 mA at 24V DC
Class 2/SELV
DeviceNet Cable Allen-Bradley part no. 1485C-P1-Cxxx.‡ 
Power supply distance rating 5 modules ⋆ 
Isolation Voltage 30V (continuous), Basic Insulation Type, DeviceNet to Backplane
Type tested at 710V DC for 60 s
Dimensions (HxWxD), Approx. 118 x 50 x 87 mm§  (4.65 x 1.97 x 3.43 in♣ )
Weight 0.28 kg (0.61 lb)
Agency Certification
(When product is marked.)
c-UL-us certified for Class I, Division 2, Groups A…D Hazardous Locations
CE compliant for all applicable directives
C-Tick Australian Radio communications Act, compliant with: AS/NZS 2064; Industrial Emissions
DeviceNet: ODVA conformance tested to ODVA DeviceNet specifications
Hazardous Environment Class Class I, Division 2, Hazardous Location, Groups A, B, C, D certified for U.S. and Canada
⋆ The adapter must not be more than 5 modules away from the 1769 power supply in the bank of 1769 I/O modules.
‡ Refer to publication DN-2.5 for more information.
§ Height including mounting tabs is 138 mm.