SLC Processors

SLC Processors

The SLC processors offer a wide range of choices in memory, I/O capacity, instruction set, and communication ports to allow you to tailor a control system to your exact application requirements. These products have a strong reliability history covering hundreds of thousands of installations in a broad range of applications.

SLC 5/01 processors let you configure modular controllers of up to 960 I/O and a 1K- or 4K-instruction memory capacity.

SLC 5/02 processors let you configure modular controllers of up to 4096 inputs plus 4096 outputs nominally and a 4K-instruction memory. By installing an optional scanner module into one of the 30 I/O module slots, you can add ControlNet I/O, DeviceNet I/O, or Universal Remote I/O to the system. They offer 19 additional instructions, including a message instruction for initiating peer-to peer communication.

SLC 5/03 processors let you configure modular controllers of up to 4096 inputs plus 4096 outputs and a memory of 8K, 16K, or 32K words. In addition to the features of the SLC 5/02, they have a second built-in communication port—an RS-232-C port that can be configured for ASCII or DF1 protocol, and can be configured for connection to a 1761-NET-AIC converter to provide access to a DH-485 network. SLC 5/03 processors provide bit-instruction execution times of 0.44 ms and an overall system throughput of up to 10 times faster than competitive processors. Additional capabilities include: floating-point math, online programming and run-time editing, flash memory upgrades, built-in key-switch, and a built-in real-time clock and calendar.

SLC 5/04 and 5/05 processors let you configure modular controllers of up to 4096 inputs plus 4096 outputs and a memory of either 16K, 32K, or 64K words. They have all the features of the SLC 5/03 processors, plus a faster communication port and shorter execution times (bit-instruction execution times of 0.37ms). Instead of a DH-485 port, the SLC 5/04 has a built-in DH+ port for communication with other SLC 5/04 and PLC processors, operator interfaces, and programming terminals. Communication via the DH+ network is three times faster than DH-485 communication. SLC 5/05 processors provide a 10/100BASE-T, 10 or 100 Mbps Ethernet port.


Benefits


Specifications

Battery, SLC 5/01, 5/02, 5/03, 5/04, 5/05 1747-BA
Module Compatibility •SLC 5/01 processors are not compatible with 1746-BLM, 1746-BTM, 1746-MPM, 1746-HS, 1746-HSCE, 1746-QV, 1747-SN, 1747-SDN, and 1747-SCNR15 modules
•SLC 5/02 processors are not compatible with 1746-BLM and 1746-MPM modules
Operating Shock 30 g (modular hardware)
Vibration
Displacement
0.015 inches peak-to-peak at 5…57 Hz
Acceleration
2.5 g at 57…2000 Hz
Duration
1 hr per axis (x, y, z) (fixed hardware)
Environmental conditions
Operating Temperature
0…60 °C (32…140 °F)
Nonoperating Temperature
-40…85 °C (-40…185 °F)
Relative Humidity
5…95% noncondensing
Programming devices RSLogix 500 Software
  

Selecting the Processor Category

Processor Category I/O, Max. I/O Communication User Memory, Max. General
Communication Ports
SLC 5/01 960 •Processor-resident local I/O •1K or 4K instructions •DH-485 (cannot initiate messages)
SLC 5/02 4096 in + 4096 out •Processor-resident local I/O
•I/O at remote locations⋆ 
•4K instructions •DH-485
SLC 5/03 4096 in + 4096 out •Processor-resident local I/O
•I/O at remote locations⋆ 
•8K, 16K, or 32K words total •DH-485
•RS-232‡ 
SLC 5/04 4096 in + 4096 out •Processor-resident local I/O
•I/O at remote locations⋆ 
•16K, 32K, or 64K words total •DH+
•RS-232‡ 
SLC 5/05 4096 in + 4096 out •Processor-resident local I/O
•I/O at remote locations⋆ 
•16K, 32K, or 64K words total •Ethernet
•RS-232‡ 
     
⋆ This type of I/O in this type of controller system requires a separate I/O scanner installed in an I/O module slot to provide a ControlNet, DeviceNet, or Universal Remote I/O port.
‡ Configurable for communication through a 1761-NET-AIC in a DH-485 network or through a 1761-NET-DNI in a DeviceNet network.

SLC Processors


Cat. No. User Memory, Max. Number of I/O Local Analog I/O, Max. Program Scan Time/Kword I/O Scan Time
SLC 5/01 Processor
1747-L511 1K instructions 960 absolute maximum (local) 480 8 ms (typ) 2.6 ms (typ)
1747-L514 4K instructions
SLC 5/02 Processor
1747-L524 4K instructions 4096 in + 4096 out
absolute maximum‡ § 
480 4.8 ms (typ) 1.6 ms (typ)
SLC 5/03 Processor⋆ 
1747-L531 8K words total
(4K words for data or prog.)
(4K words for data only)
4096 in + 4096 out
absolute maximum‡ § 
480 1 ms (typ) 0.225 ms (typ)
1747-L532 16K words total
(12K words for data or prog.)
(4K words for data only)
1747-L533 32K words total
(28K words for data or prog.)
(4K words for data only)
SLC 5/04 Processor
1747-L541 16K words total
(12K words for data or prog.)
(4K words for data only)
4096 in + 4096 out
absolute maximum‡ § 
480 0.9 ms (typ) 0.225 ms (typ)
1747-L542 32K words total
(28K words for data or prog.)
(4K words for data only)
1747-L543 64K words total
(60K words for data or prog.)
(4K words for data only)
SLC 5/05 Processor ♣ 
1747-L551 16K words total
(12K words for data or prog.)
(4K words for data only)
4096 in + 4096 out
absolute maximum‡ § 
480 0.9 ms (typ) 0.225 ms (typ)
1747-L552 32K words total
(28K words for data or prog.)
(4K words for data only)
1747-L553 64K words total
(60K words for data or prog.)
(4K words for data only)
  
⋆ Modbus slave protocol is embedded in the RTU-5/03 processors available from an Encompass partner. The Modbus slave protocol is supported on the RS-232 port (channel0). For information on the Encompass program visit: www.rockwellautomation.com/encompass/.
‡ The absolute maximum number of I/O for these processors only reflects the I/O addressing capability. It does not take into account the amount of memory that may be required for a ladder-logic program to monitor and control the I/O. The practical ratio of memory per I/O is totally dependant upon your specific application.
§ You cannot configure this number of I/O for these processors with local I/O only. To configure this number of I/O for these processors, you must add a 1747-SN Remote I/O Scanner module to configure I/O on a Universal Remote I/O link, add a 1747-SDN DeviceNet Scanner module to configure I/O on a DeviceNet network and/or add a 1747-SCNR ControlNet Scanner module to configure I/O on a ControlNet network.
♣ The 5/05 Series C processors can communicate to 100 Mbps and support increased Ethernet connections: 1747-L551=32 connections; 1747-L552=48 connections; 1747-L553=64 connections.

SLC Processors (continued)

Cat. No. No. of Local I/O Chassis, Max. No. of I/O Module Slots in the Local I/O Chassis, Max. Communication
Ports
Backup
Memory
Battery-backed
RAM
Backplane
Current Load
SLC 5/01 Processor
1747-L511
1747-L514
3 30 DH-485‡  EEPROM Option 350 mA at 5V DC
105 mA at 24V DC
SLC 5/02 Processor
1747-L524 3⋆  30 DH-485 EEPROM Standard 350 mA at 5V DC
105 mA at 24V DC
SLC 5/03 Processor
1747-L531
1747-L532
1747-L533
3⋆  30 DH-485
RS-232§ 
Flash Standard 500 mA at 5V DC
175 mA at 24V DC
SLC 5/04 Processor
1747-L541
1747-L542
1747-L543
3⋆  30 DH+
RS-232♣ 
Flash Standard 1 A at 5V DC
0 A at 24V DC∆ 
SLC 5/05 Processor
1747-L551
1747-L552
1747-L553
3⋆  30 Ethernet
RS-232♣ 
Flash Standard 1 A at 5V DC
0 A at 24V DC
  
⋆ With this processor, you can also install a 1747-SN Remote I/O Scanner module to configure I/O on a Universal Remote I/O link and/or add a 1747-SDN DeviceNet Scanner module to configure I/O on a DeviceNet network. You can configure 32 I/O chassis per Universal Remote I/O scanner using complementary I/O. If you don’t use complementary I/O, you can configure 16 I/O chassis per Universal Remote I/O scanner. With the DeviceNet scanner, you can address a maximum of 63 DeviceNet devices over the DeviceNet network.
‡ An SLC 5/01 processor can only receive messages and send reply messages to command messages sent from other nodes on the DH-485 network; it cannot initiate communication.
§ The SLC 5/03 has an RS-232 port, which can also be configured for a DH-485 network, enabling the SLC-5/03 to connect to two DH-485 networks simultaneously.
♣ The SLC 5/04 and SLC 5/05 have an RS-232 port, which can also be configured for a DH-485 network.
∆ SLC 5/04 processors manufactured prior to April 2002 draw 200 mA @ 24V DC. Check the processor label to verify current draw.

Memory Devices

Cat. No. Description For this Product Function Memory Size
1747-M1 EEPROM SLC 5/01 Program and data table storage 8 Kbytes, 1K instructions
1747-M2 EEPROM SLC 5/01, 5/02 Program and data table storage 32 Kbytes, 4K instructions
1747-M13 Flash SLC 5/03, 5/04, 5/05 Program and data table storage 64 Kbyte