SLC 500 System

Catalogs > Automation Systems Catalog > Programmable Controllers > SLC 500 System > I/O Modules and Hardware

I/O Modules and Hardware

I/O Adapter Modules Chassis and Hardware 1746 I/O Module Overview Digital I/O Modules
Analog I/O Modules Specialty I/O Modules Removable Terminal Blocks Distributed I/O
I/O Adapter Modules

1747 I/O adapter modules allow 1746 I/O modules in a remote chassis to be controlled by SLC and PLC processors. SLC processors require a scanner module to reside in the local chassis in order for the remote communication to occur. The adapter module must reside in the left-most slot of the remote chassis and can interface to a maximum of 30 1746 I/O modules residing in up to three interconnected chassis. There are three 1746 I/O adapter modules: the 1747-ASB for remote I/O communication, the 1747-ACN15 for remote communication via ControlNet, and the 1747-ACNR15 for remote communication via ControlNet with redundant media port.

Specifications

Cat. No. 1747-ACN15 1747-ACNR15 1747-ASB
Description Single-port non-redundant-media/redundant-media ControlNet I/O adapter module Universal Remote I/O adapter module
Port ControlNet I/O adapter port Universal Remote I/O adapter port
Communication Rate 5 Mbit/s •57.6 kbit/s
•115 kbit/s
•230 kbit/s
Connectors •1 BNC connector for non-redundant media operation
•1 NAP (RJ-45 8-pin with shield)
•2 BNC connectors for redundant media operation
•1 NAP (RJ-45 8-pin with shield)
6-pin Phoenix connector
Cable Quad-shield RG-6 coaxial cable Belden 9463
Backplane Current Load 900 mA @ 5V dc 375 mA @ 5V dc
Weight 0.2 kg (0.4 lb) 0.2 kg (0.5 lb) 0.2 kg (0.4 lb)
Shock, Operating 30 g (3 pulses, 11 ms)
Shock, Non-Operating 50 g (3 pulses, 11 ms)
Vibration 1.0 g @ 5…2000 Hz
Vibration, Non-Operating 2.5 g @ 5…2000 Hz
Operating Temperature 0…60 °C (32…140 °F)
Non-Operating Temperature -40…85 °C (-40…185 °F)
Relative Humidity 5…95% (without condensation)
Certifications¬  CSA Class I Div 2 Hazardous, UL, CE
  
¬ When product is marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

ControlNet Adapter Communication Capabilities

The table below indicates with a “ü“ which ControlNet controllers can communicate to the 1747-ACN via scheduled messaging.

Scheduled
Messaging
1747-SCNR 1771-PLC5C 1756-Lx via
1756-CNB
1784-KTCS
1747-ACN(R)15
Discrete I/O
ü ü   ü
1747-ACN(R)15
Analog I/O
ü ü