PLC-5 System

Catalogs > Automation Systems Catalog > Programmable Controllers > PLC-5 System > PLC-5 Processors

PLC-5 Processors

PLC-5 Processors Overview Specifications Selecting the Processor Category PLC-5 Processors PLC-5 Processor Backup System
PLC-5 Processors

Standard PLC-5 Processors


Cat. No. Processor User Memory Words, Max.¬  Memory Types Total I/O, Max. Analog I/O, Max. I/O Scan Time per Rack§ 
Standard PLC-5 Processors
1785-L11B PLC-5/11 8K •Battery-backed static RAM
•EEPROM program backup option using:
1785-ME16, -ME32, -ME64, and -M100
•512 (any mix) or
•384 in + 384 out (complementary)
512 •10 ms @ 57.6 kbit/s
•7 ms @ 115.2 kbit/s
•3 ms @ 230.4 kbit/s
1785-L20B PLC-5/20 16K •Battery-backed static RAM
•EEPROM program backup option using:
1785-ME16, -ME32, -ME64, and -M100
•512 (any mix) or
•512 in + 512 out (complementary)
512 •10 ms @ 57.6 kbit/s
•7 ms @ 115.2 kbit/s
•3 ms @ 230.4 kbit/s
1785-L30B PLC-5/30 32K •Battery-backed static RAM
•EEPROM program backup option using:
1785-ME16, -ME32, -ME64, and -M100
•1024 (any mix) or
•1024 in and 1024 out (complementary)
1024 •10 ms @ 57.6 kbit/s
•7 ms @ 115.2 kbit/s
•3 ms @ 230.4 kbit/s
1785-L40B PLC-5/40 48KT  •Battery-backed static RAM
•EEPROM program backup option using:
1785-ME16, -ME32, -ME64, and -M100
•2048 (any mix) or
•2048 in + 2048 out (complementary)
2048 •10 ms @ 57.6 kbit/s
•7 ms @ 115.2 kbit/s
•3 ms @ 230.4 kbit/s
1785-L40L PLC-5/40L 48KT  •Battery-backed static RAM
•EEPROM program backup option using:
1785-ME16, -ME32, -ME64, and -M100
•2048 (any mix) or
•2048 in + 2048 out (complementary)
2048 •0.5 ms (ext. local)
•10 ms @ 57.6 kbit/s
•7 ms @ 115.2 kbit/s
•3 ms @ 230.4 kbit/s
1785-L60B PLC-5/60 64K‡  •Battery-backed static RAM
•EEPROM program backup option using:
1785-ME16, -ME32, -ME64, and -M100
•3072 (any mix) or
•3072 in + 3072 out (complementary)
3072 •10 ms @ 57.6 kbit/s
•7 ms @ 115.2 kbit/s
•3 ms @ 230.4 kbit/s
1785-L60L PLC-5/60L 64K‡  •Battery-backed static RAM
•EEPROM program backup option using:
1785-ME16, -ME32, -ME64, and -M100
•3072 (any mix) or
•3072 in + 3072 out (complementary)
3072 •0.5 ms (ext. local)
•10 ms @ 57.6 kbit/s
•7 ms @ 115.2 kbit/s
•3 ms @ 230.4 kbit/s
1785-L80B PLC-5/80 100K§  •Battery-backed static RAM
•EEPROM program backup option using:
1785-ME16, -ME32, -ME64, and -M100
•3072 (any mix) or
•3072 in + 3072 out (complementary)
3072 •10 ms @ 57.6 kbit/s
•7 ms @ 115.2 kbit/s
•3 ms @ 230.4 kbit/s
Standard PLC-5 Processors with Protected Memories
1785-L26B PLC-5/26 16K •Battery-backed static RAM
•EEPROM program backup option using:
1785-ME16, -ME32, -ME64, and -M100
•Protected
•512 (any mix) or
•512 in + 512 out (complementary)
512 •10 ms @ 57.6 kbit/s
•7 ms @ 115.2 kbit/s
•3 ms @ 230.4 kbit/s
1785-L46B PLC-5/46 48KT  •Battery-backed static RAM
•EEPROM program backup option using:
1785-ME16, -ME32, -ME64, and -M100
•Protected
•2048 (any mix) or
•2048 in + 2048 out (complementary)
2048 •10 ms @ 57.6 kbit/s
•7 ms @ 115.2 kbit/s
•3 ms @ 230.4 kbit/s
1785-L86B PLC-5/86 100K§  •Battery-backed static RAM
•EEPROM program backup option using:
1785-ME16, -ME32, -ME64, and -M100
•Protected
•3072 (any mix) or
•3072 in + 3072 out (complementary)
3072 •10 ms @ 57.6 kbit/s
•7 ms @ 115.2 kbit/s
•3 ms @ 230.4 kbit/s
  
¬ Max. number of data table words and max. number of timers and counters are user-configured.
T Limit of 32K words per data table file.
‡ Limit of 32K words per data table file and 56K words per program file.
§ Limit of 32K words per data table file and a total data table size of 64K words. Limit of 56K words per program file.
§ In a single chassis, extended-local or remote. For Universal Remote I/O unless otherwise specified.

Standard PLC-5 Processors (continued)

Cat. No. Processor Universal Remote / Extended Local-I/O / DH+ Ports (Mode) Number of I/O Chassis, Max. RS-232-C / 422-A / 423-A PortsT  Backplane Current Load @ 5V
Total Extended Local Universal Remote¬ 
Standard PLC-5 Processors
1785-L11B PLC-5/11 1 DH+/Remote I/O (Adap or Scan) 5 0 4 1 2.3 A
1785-L20B PLC-5/20 1 DH+
1 DH+/Remote I/O (Adap or Scan)
13 0 12 2.3 A
1785-L30B PLC-5/30 2 DH+/Remote I/O (Adap or Scan) 29 0 28 2.3 A
1785-L40B PLC-5/40 4 DH+/Remote I/O (Adap or Scan) 61 0 32 max. per I/O link 3.3 A
1785-L40L PLC-5/40L 2 DH+/Remote I/O (Adap or Scan)
1 Extended Local I/O
61 16 32 max. per I/O link 3.3 A
1785-L60B PLC-5/60 4 DH+/Remote I/O (Adap or Scan) 93 0 32 max. per I/O link 3.3 A
1785-L60L PLC-5/60L 2 DH+/Remote I/O (Adap or Scan)
1 Extended Local I/O
81 16 32 max. per I/O link 3.3 A
1785-L80B PLC-5/80 4 DH+/Remote I/O (Adap or Scan) 93 0 32 max. per I/O link 3.3 A
Standard PLC-5 Processors with Protected Memories
1785-L26B PLC-5/26 1 DH+
1 DH+/Remote I/O (Adap or Scan)
13 0 12 1 2.3 A
1785-L46B PLC-5/46 4 DH+/Remote I/O (Adap or Scan) 61 0 32 max. per I/O link 1 3.3 A
1785-L86B PLC-5/86 4 DH+/Remote I/O (Adap or Scan) 93 0 32 max. per I/O link 1 3.3 A
  
¬ Universal Remote I/O Chassis — any device with a remote I/O adapter port compatible with the Allen-Bradley Universal Remote I/O link. This includes 1771 I/O chassis, 1791 I/O blocks, PanelView displays, RediPANEL displays, Dataliner displays, 1336 drives.
T RS-422-A and RS-423-A both have a cable length limitation of 61 m (200 ft).

Ethernet and ControlNet PLC-5 Processors


Cat. No. Processor User Memory Words, Max.¬  Memory Types Total I/O, Max. Analog I/O, Max. I/O Scan Time per Rack§ 
Ethernet PLC-5 Processors
1785-L20E PLC-5/20E 16K •Battery-backed static RAM
•EEPROM program backup option using 1785-ME16, -ME32, and -ME64
•512 (any mix) or
•512 in + 512 out (complementary)
512 •10 ms @ 57.6 kbit/s
•7 ms @ 115.2 kbit/s
•3 ms @ 230.4 kbit/s
1785-L40E PLC-5/40E 48KT  •Battery-backed static RAM
•EEPROM program backup option using 1785-ME16, -ME32, and -ME64
•2048 (any mix) or
•2048 in + 2048 out (complementary)
2048 •10 ms @ 57.6 kbit/s
•7 ms @ 115.2 kbit/s
•3 ms @ 230.4 kbit/s
1785-L80E PLC-5/80E 100K‡  •Battery-backed static RAM
•EEPROM program backup option using 1785-ME16, -ME32, -ME64, -M100
•3072 (any mix) or
•3072 in + 3072 out (complementary)
3072 •10 ms @ 57.6 kbit/s
•7 ms @ 115.2 kbit/s
•3 ms @ 230.4 kbit/s
ControlNet PLC-5 Processors
1785-L20C15 PLC-5/20C 16K •Battery-backed static RAM
•EEPROM program backup option using 1785-ME32, -ME64, and -M100
Forcible
•512 (any mix) or
•512 in + 512 out (complementary)
Non-forcibleØ 
•32000
Forcible
•512
Non-
forcibleØ 
•32000
ControlNet I/O
•0.5 ms (average)z 
Universal Remote I/O
•10 ms @ 57.6 kbit/s
•7 ms @ 115.2 kbit/s
•3 ms @ 230.4 kbit/s
1785-L40C15 PLC-5/40C 48KT  •Battery-backed static RAM
•EEPROM program backup option using 1785-ME32, -ME64, and -M100
Forcible
•2048 (any mix) or
•2048 in + 2048 out (complementary)
Non-forcibleØ 
•48000
Forcible
•2048
Non-
forcibleØ 
•48000
ControlNet I/O
•0.5 ms (average)z 
Universal Remote I/O
•10 ms @ 57.6 kbit/s
•7 ms @ 115.2 kbit/s
•3 ms @ 230.4 kbit/s
1785-L80C15 PLC-5/80C 100K‡  •Battery-backed static RAM
•EEPROM program backup option using 1785-ME32, -ME64, and -M100
Forcible
•3072 (any mix) or
•3072 in + 2048 out (complementary)
Non-forcibleØ 
•50176
Forcible
•3072
Non-
forcibleØ 
•50176
ControlNet I/O
•0.5 ms (average)z 
Universal Remote I/O
•10 ms @ 57.6 kbit/s
•7 ms @ 115.2 kbit/s
•3 ms @ 230.4 kbit/s
ControlNet PLC-5 Processors with Protected Memories
1785-L46C15 PLC-5/46C 48KT  •Battery-backed static RAM
•EEPROM program backup option using 1785-ME32, -ME64, and -M100
•Protected
Forcible
•2048 (any mix) or
•2048 in + 2048 out (complementary)
Non-forcibleØ 
•48000
Forcible
•2048
Non-
forcibleØ 
•48000
ControlNet I/O
•0.5 ms (average)z 
Universal Remote I/O
•10 ms @ 57.6 kbit/s
•7 ms @ 115.2 kbit/s
•3 ms @ 230.4 kbit/s
  
¬ Max. number of data table words and max. number of timers and counters are user-configured.
T Limit of 32K words per data table file.
‡ Limit of 32K words per data table file and a total data table size of 64K words. Limit of 56K words per program file.
§ In a single non-local chassis.
Ø Non forcible I/O is only available as ControlNet I/O.
z With several I/O chassis connected to the processor across a ControlNet link, the average I/O scan time per I/O rack in a single chassis is 0.5 ms. However the min. time for a complete ControlNet I/O scan (network update time) is 2 ms. Therefore, with a single I/O chassis connected to the processor across a ControlNet link, the min. I/O scan time for that single I/O chassis is 2 ms. Even with several I/O chassis connected to the processor across a ControlNet link, the min. time for an individual I/O chassis to be updated is 2 ms.

Ethernet and ControlNet PLC-5 Processors (continued)

Cat. No. Processor ControlNet / Ethernet / Remote / Extended Local-I/O / DH+ Ports (Mode) Number of I/O Chassis, Max. RS-232-C / 422-A / 423-A Ports§  Backplane Current Load @ 5V
Total¬  Extended Local Universal RemoteT 
Ethernet PLC-5 Processors
1785-L20E PLC-5/20E •1 Ethernet
•1 DH+
•1 DH+/Remote I/O (Adap or Scan)
13 0 12 1 3.6 A
1785-L40E PLC-5/40E •1 Ethernet
•2 DH+/Remote I/O (Adap or Scan)
61 0 60 1 3.6 A
1785-L80E PLC-5/80E •1 Ethernet
•2 DH+/Remote I/O (Adap or Scan)
65 0 64 1 3.6 A
ControlNet PLC-5 Processors
1785-L20C15 PLC-5/20C •1 ControlNet (dual media)
•1 DH+
•1 DH+/Remote I/O (Adap or Scan)
77 0 12 1 2.7 A (typ)
3.0 A (max)
1785-L40C15 PLC-5/40C •1 ControlNet (dual media)
•2 DH+/Remote I/O (Adap or Scan)
125 0 60 1 3.0 A
1785-L80C15 PLC-5/80C •1 ControlNet (dual media)
•2 DH+/Remote I/O (Adap or Scan)
125 0 60 1 3.0 A
ControlNet PLC-5 Processor with Protected Memory
1785-L46C15 PLC-5/46C •1 ControlNet (dual media)
•2 DH+/Remote I/O (Adap or Scan)
125 0 60 1 3.0 A
  
¬ Limited by data-table size and how much data table you use for each chassis.
T Universal Remote I/O Chassis — any device with a remote I/O adapter port compatible with the Allen-Bradley Universal Remote I/O link. This includes 1771 I/O chassis, 1791 I/O blocks, PanelView displays, RediPANEL displays, Dataliner displays, 1336 drives.
‡ The ControlNet I/O map table can contain up to 128 entries. Each map-table entry corresponds to one scheduled transfer of data.
§ RS-422-A and RS-423-A both have a cable length limitation of 61m (200 ft).

Memory Devices

Cat. No. Description For this Product Function Memory Size
1785-ME16 EEPROM Standard PLC-5 processors Program backup 16K words
1785-ME32 EEPROM Standard PLC-5 processors Program backup 32K words
1785-ME64 EEPROM Standard PLC-5 processors Program backup 64K words
1785-M100 EEPROM Standard PLC-5 processors Program backup 100K words