Catalogs > Automation Systems Catalog > Programmable Controllers > GuardPLC Safety Control System > GuardPLC Safety Control Systems Overview
GuardPLC Safety Control Systems Overview
GuardPLC™ Safety Control Systems
|
System Overview
The GuardPLC system is a state-of-the-art safety system offering fast safety PLCs, optimum controller throughput, and a reliable safety network.
The GuardPLC system meets the worldwide standard for programmable controls, complying with many of the latest global safety standards and the worldwide standard for functional safety in programmable electronic systems. The GuardPLC system can be used without restriction in applications up to Safety Integrity Level 3 (SIL 3) according to IEC 61508 and Category 4, PLe according to ISO 13849-1:2006.
The GuardPLC system consists of four main components:
- Packaged or modular controller and associated integrated I/O
- Safety Communication via GuardPLC Ethernet networks
- Distributed I/O modules for GuardPLC Ethernet networks
- Programming and configuration software
Benefits
Benefits resulting from the use of safety PLCs and safety networks include:
- Greater integration and flexibility of machine controls.
- Capability for better and easier diagnostics when intelligence is provided to the standard control level
- Faster and easier maintenance
- Reduction in the cost of installation, commissioning, and reconfiguring
- Reduction in design and hardware costs, compared to using safety relays alone for logic
- Potential for throughput performance improvement in more complex systems
GuardPLC Safety Control Systems
|
|
|
|
|
|
| GuardPLC 1200 Controller | GuardPLC 1600 Controller | GuardPLC 1800 Controller | GuardPLC 2000 Controller | Distributed Safety I/O for GuardPLC Ethernet | |
| Description | Designed for smaller applications requiring functional safety and serviceable by a fixed number of I/O points. | A cost-effective safety PLC offering a built-in 4-port Ethernet switch, digital I/O, and flexible communication options for connecting devices. | Analog inputs and high-speed counters allow the GuardPLC 1800 to sense temperature, pressure, speed, and motion. | A high-performance safety system easily expanded and simple to program—the ultimate in scaleable safety control. | Distributed safety I/O blocks provide exceptional flexibility in configuring the right mix of I/O in the right place. |
| Memory | 500kB user program 500kB application data |
250kB user program 250kB application data |
250kB user program 250kB application data |
500kB user program 500kB application data |
— |
| Digital I/O | 20 inputs 8 outputs |
20 inputs 8 outputs |
24 inputs 8 outputs |
24 inputs¬ 16 outputs¬ |
16 inputs only 16 outputs only 8 inputs and 8 outputs 16 inputs and 8 outputs 20 inputs and 8 outputs |
| Other I/O | 2 high-speed counters | — | 8 analog inputs 2 high-speed counters |
8 analog inputs¬ 8 analog outputs¬ 2 high-speed counters¬ |
8 analog inputs 8 relay outputs |
| Embedded Ethernet | single port | 4-port switch | 4-port switch | single port | 2-port switch |
| Other Communications | ASCII (RS-232) | EtherNet/IP GuardPLC Ethernet Modbus RTU Slave or PROFIBUS DP Slave ASCII (RS-485) |
EtherNet/IP GuardPLC Ethernet Modbus RTU Slave or PROFIBUS DP Slave ASCII (RS-485) |
ASCII (RS-232) | GuardPLC Ethernet |
| Programming Software | All GuardPLC controllers are programmed with RSLogix Guard PLUS! Programming Software. | ||||
| ¬ I/O combinations vary by catalog number. | |||||