Catalogs > Automation Systems Catalog > Programmable Controllers > FlexLogix System > Networks
Networks
| Introduction | Available Networks | EtherNet/IP Network | ControlNet Network | DeviceNet Network | Serial Communication | DH-485 Network |
|
ControlNet Network
The ControlNet network is an open, control network for real-time, high-throughput applications. The ControlNet network uses the Common Industrial Protocol (CIP) to combine the functionality of an I/O network and a peer-to-peer network providing high-speed performance for both functions. The ControlNet network gives you deterministic, repeatable transfers of all mission-critical control data in addition to supporting transfers of non-time-critical data. I/O updates and controller-to-controller interlocking always take precedence over program uploads and downloads and messaging.
ControlNet Communication Modules
Specifications [PDF]
| Cat. No. | Description | Communication Rate | Logix Connections | Number of Nodes |
| 1756-CN2 | ControlNet communication bridge module, standard media | 5 Mbps | 100 | 99 |
| 1756-CN2R | ControlNet communication bridge module, redundant media | 5 Mbps | 100 | 99 |
| 1756-CNB | ControlNet communication bridge module, standard media | 5 Mbps | 40...48 | 99 |
| 1756-CNBR | ControlNet communication bridge module, redundant media | 5 Mbps | 40...48 | 99 |
| 1756-CN2RXT | ControlLogix-XT, ControlNet communication bridge module, redundant media | 5 Mbps | 100 | 99 |
Example Configuration—ControlNet Network
|
Example Configuration—Redundant ControlNet Media
Redundant ControlNet media requires these components:
- 1756-CN2R or 1756-CNBR ControlNet module
- Two identical ControlNet links
|
Accessories—ControlNet Network
| Cat. No. | Description |
| Taps | |
| 1786-TPR | T-tap right angle |
| 1786-TPS | T-tap straight |
| 1786-TPYR | Y-tap right angle |
| 1786-TPYS | Y-tap straight |
| Cables | |
| 1786-CP | Programming cable to ControlNet RJ45 port |
| 1786-RG6 | ControlNet network, shield high flex cable |
| 1756-RG6F | ControlNet network, quad shield high flex coax cable |
| Other | |
| 1786-XT | ControlNet termination resistor |
| Repeaters | |
| 1786-RPA | ControlNet modular repeater adapter |
| 1786-RPCD | ControlNet coaxial hub repeater |
| 1786-RPFRL | ControlNet fiber ring repeater, long |
| 1786-RPFRXL | ControlNet fiber ring repeater, extra long |
| 1786-RPFS | ControlNet fiber ring repeater, short |
| 1786-RPFM | ControlNet fiber ring repeater, medium |
ControlNet Interface Specifications
|
|
| Cat. No. | Communication Rate | Connections | Cable | Power Dissipation, Max. | Backplane Current @ 5.1V |
| 1788-CNC | 5 Mbps | 32 connections (depending on the RPI, as many as 22 connections can be scheduled) The remaining connections (or all 32, if you have no scheduled connections) can be used for unscheduled connections. |
RG-6 coaxial cable 1786-RG6 (quad shield cable) 1786-RG6F (quad shield high flex coax cable) |
2.25 W | 450 mA |
| 1788-CNCR (redundant media) |
2.38 W | 475 mA | |||
| 1788-CNF | 200/300 micron HCS (hard-clad silica) fiber optic cable Versalink V-system Fiber media requires 1786-RPA and 1786-RPFS to convert fiber media back to coax. |
2.20 W | 440 mA | ||
| 1788-CNFR (redundant media) |
2.25 W | 450 mA | |||
| Certifications: UL, CSA (Class I, Division 2, Group A, B, C, D), UR, CE, C-Tick. | |||||
Typical ControlNet Configuration
|