FlexLogix System

Catalogs > Automation Systems Catalog > Programmable Controllers > FlexLogix System > Networks

Networks

Introduction Available Networks EtherNet/IP Network ControlNet Network DeviceNet Network Serial Communication DH-485 Network
Click to enlarge - 1756-CNB Module_GS


ControlNet Network

The ControlNet network is an open, control network for real-time, high-throughput applications. The ControlNet network uses the Common Industrial Protocol (CIP) to combine the functionality of an I/O network and a peer-to-peer network providing high-speed performance for both functions. The ControlNet network gives you deterministic, repeatable transfers of all mission-critical control data in addition to supporting transfers of non-time-critical data. I/O updates and controller-to-controller interlocking always take precedence over program uploads and downloads and messaging.

ControlNet Communication Modules

Specifications [PDF]

Cat. No. Description Communication Rate Logix Connections Number of Nodes
1756-CN2 ControlNet communication bridge module, standard media 5 Mbps 100 99
1756-CN2R ControlNet communication bridge module, redundant media 5 Mbps 100 99
1756-CNB ControlNet communication bridge module, standard media 5 Mbps 40...48 99
1756-CNBR ControlNet communication bridge module, redundant media 5 Mbps 40...48 99
1756-CN2RXT ControlLogix-XT, ControlNet communication bridge module, redundant media 5 Mbps 100 99
  

Example Configuration—ControlNet Network

Click to enlarge - 1756-CNB Config_BW


Example Configuration—Redundant ControlNet Media

Redundant ControlNet media requires these components:


Click to enlarge - 1756 Redundant Media_BW


Accessories—ControlNet Network

Cat. No. Description
Taps
1786-TPR T-tap right angle
1786-TPS T-tap straight
1786-TPYR Y-tap right angle
1786-TPYS Y-tap straight
Cables
1786-CP Programming cable to ControlNet RJ45 port
1786-RG6 ControlNet network, shield high flex cable
1756-RG6F ControlNet network, quad shield high flex coax cable
Other
1786-XT ControlNet termination resistor
Repeaters
1786-RPA ControlNet modular repeater adapter
1786-RPCD ControlNet coaxial hub repeater
1786-RPFRL ControlNet fiber ring repeater, long
1786-RPFRXL ControlNet fiber ring repeater, extra long
1786-RPFS ControlNet fiber ring repeater, short
1786-RPFM ControlNet fiber ring repeater, medium

ControlNet Interface Specifications

Click to enlarge - 1788CNCCommCard_GS Click to enlarge - 1788CNF_CommCard_GS

Cat. No. Communication Rate Connections Cable Power Dissipation, Max. Backplane Current @ 5.1V
1788-CNC 5 Mbps 32 connections (depending on the RPI, as many as 22 connections can be scheduled)
The remaining connections (or all 32, if you have no scheduled connections) can be used for unscheduled connections.
RG-6 coaxial cable
1786-RG6 (quad shield cable)
1786-RG6F (quad shield high flex coax cable)
2.25 W 450 mA
1788-CNCR
(redundant media)
2.38 W 475 mA
1788-CNF 200/300 micron HCS (hard-clad silica) fiber optic cable
Versalink V-system

Fiber media requires 1786-RPA and 1786-RPFS to convert fiber media back to coax.
2.20 W 440 mA
1788-CNFR
(redundant media)
2.25 W 450 mA
  
Certifications: UL, CSA (Class I, Division 2, Group A, B, C, D), UR, CE, C-Tick.

Typical ControlNet Configuration

Click to enlarge - 1794Cnet1788-CNx_BW