FlexLogix Controller

1794 FlexLogix Controllers

FlexLogix controllers can monitor and control I/O AC ross the 1794 backplane, as well as over I/O links. FlexLogix controllers can communicate with computers or other processors AC ross RS-232-C (DF1/DH-485 protocol), DeviceNet, ControlNet, and EtherNet/IP networks. To provide communication for a FlexLogix controller, install the appropriate communication interface module into the controller.

The multi-tasking operating system supports eight configurable tasks that can be prioritized. One task can be continuous. The others must be periodic or event tasks. Each task can have as many as 32 programs, each with its own local data and logic, allowing virtual machines to operate independently within the same controller.


As of December 31, 2008, FlexLogix controllers ceased to be offered for general sale; however, we plan to provide repair services and technical support for FlexLogix controllers for an additional seven years, if components remain available. For more information: http://www.ab.com/programmablecontrol/pac/flexlogix/

Click to enlarge - 1794-L34 Flex5434_gray_GS


Specification Description
FlexBus Output Current @ 5V DC 653 mA
Power Supply 1794-PS3 or 1794-PS13
In applications that must be compliant with CSA requirements, use a Separated Extra-Low Voltage (SELV) power supply that is compliant with IEC 610101, Annex H.
Battery 1756-BA1 (94194801) - comes with the controller
Programming Cable 1761-CBLPM02 to 1761-NET-AIC isolator
1761-CBLPA00 to 1761-NET-AIC isolator
1756-CP3 directly to controller
1747-CP3 directly to controller
Extended-Local I/O Cable 1794-CE1 cable (0.3 m, 1 ft)
1794-CE3 cable (0.9 m, 3 ft)
  
Certifications: UL, CSA (Class I, Division 2, Group A, B, C, D), CE.

FlexLogix Controllers

Cat. No.
User Memory¬ 
Power Dissipation, Max. Thermal Dissipation, Max. Backplane Current @ 5.1V
Battery-Backed Static RAM Nonvolatile Memory
1794-L34 512 Kbytes 512 KbytesT  3.5 W 11.6 BTU/hr 1.2 A
  
Certifications: UL, CSA (Class I, Division 2, Group A, B, C, D), CE.
¬ Available user memory is the amount of memory available to the user after RSLogix 5000 Enterprise Series software is connected and a null program is loaded.
T Must have a series B controller with firmware revision 11 or later.

Controller Memory Use

The following equations provide an estimate of the memory needed for a controller.

Controller tasks _____ * 4000 = _____ bytes
(minimum 1 task)
Digital I/O points _____ * 400 = _____ bytes
Analog I/O points _____ * 2600 = _____ bytes
Communication
cards
¬ 
_____ * 5000 = _____ bytes
  
¬ When estimating memory use by communication modules, count all the communication modules in the system, not just those in the local chassis. This includes device connection modules, adapter modules, and ports on PanelView terminals.

Controller Battery

The FlexLogix controller comes with one 1756-BA1 battery.

Cat. No. Description
1756-BA1 Lithium battery (0.59g) installed in each controller.
Order only if you need a replacement.
  

Compatibility

Control Distributed I/O Modules

The FlexLogix controller can control these distributed I/O modules using the I/O Configuration tree in RSLogix 5000 programming software.

I/O Modules EtherNet/IP ControlNet DeviceNet
1732 ArmorBlock Yes No Yes
1734 POINT Yes Yes Yes
1734D POINTBlock No No Yes
1738 ArmorPoint Yes Yes Yes
1746 SLC No No No
1756 ControlLogix Yes Yes No
1769 Compact No No Yes
1771 PLC-5 No YesT  No
1790 CompactBlock LDX No No Yes
1791D CompactBlock No No Yes
1792D ArmorBlock MaXum No No Yes
1794 FLEX Yes Yes Yes
1797 FLEX Ex No Yes No
1798 FLEX Armor No No Yes
1799 Embedded No No Yes
  
¬ Requires RSLogix 5000 programming software version 11 or later. Use the generic FLEX profile.
T Use a 1771-ACN15, 1771-ACNR15 adapter module. Version 10 and later of RSLogix 5000 Enterprise Series software supports 1771 digital, analog, and specialty I/O modules. Previous versions of the software support only 1771 digital I/O modules.

Communicate with Display Devices

The FlexLogix controller can communicate with these display devices.

Display Devices EtherNet/IP ControlNet DeviceNet RS-232 (DF1) DH-485
2711P PanelView Plus terminal Yes Yes Yes Yes No¬ 
6182H VersaView CE computer Yes Yes Yes Yes No¬ 
2711 PanelView terminal Yes Yes Yes YesT  YesT 
2711 e PanelView terminal No Yes No No No
800E, 800T RediSTATION/RediPANEL operator module No No Yes No No
2706 InView message display Yes Yes Yes Yes Yes
2706 DL40 Dataliner message display No No No Yes No
2706 DL, DL50 DataLiner message display No No No Yes No
2707 DTAM Plus operator interface No No Yes YesT  YesT 
  
¬ These devices support DH-485 communication to FlexLogix and CompactLogix controllers.
T Use PLC/SLC mapping.

Communicate with Other Controllers

The FlexlLogix controller can communicate with these controllers.

Controller EtherNet/IP ControlNet DeviceNet RS-232 (DF1) DH-485
1756 ControlLogix
1756 GuardLogix
Yes Yes Yes Yes Yes
1768, 1769 CompactLogix Yes Yes Yes Yes Yes
1789 SoftLogix5800 Yes Yes Yes Yes No
1794 FlexLogix Yes Yes Yes Yes Yes
5720 PowerFlex 700S with DriveLogix Yes Yes Yes Yes Yes
1785 PLC-5 Yes¬ T  Yes Yes‡  Yes NA
1747 SLC Yes§  Yes Yes‡  Yes Yes
1761 MicroLogix Yes No Yes‡  Yes Yes
1762 MicroLogix Yes No Yes‡  Yes Yes
1763 MicroLogix Yes No Yes‡  Yes Yes
1764 MicroLogix Yes No Yes‡  Yes Yes
1772 PLC-2 NA NA NA Yesz  NA
1775 PLC-3 NA NA NA Yesv  NA
5250 PLC-5/250 NA NA No Yes NA
  
¬ The Ethernet PLC-5 controller must be series C, firmware revision N.1 or later; series D, firmware revision E.1 or later; or series E, firmware revision D.1 or later.
T The 1785-ENET Ethernet communication interface module must be series A, firmware revision D or later.
‡ The PLC-5, SLC, and MicroLogix processors appear as I/O points to the Logix controller. Use the appropriate DeviceNet interface for the controller.
§ Use a 1747-L55x controller with OS501 or greater.
Ø The PLC-2 controller requires a 1785-KA module for DH+ communications.
z The PLC-2 controller requires a 1771-KG module for serial (DF1) communications.
ª The PLC-3 controller requires a 1775-S5 module for DH+ communications.
v The PLC-3 controller requires a 1775-KA module for serial (DF1) communications.

Communicate with Other Communication Devices

The FlexLogix controller can communicate with these communication devices.

Communication Device EtherNet/IP ControlNet DeviceNet RS-232 (DF1) DH-485
1770-KFD NA NA Yes NA NA
9355 RSLinx software Yes Yes No Yes No
1784-KTC, 1784-KTCx, 1784-KTCx15, 1784-PCIC(S), 1784-PCC NA Yes NA NA NA
1784-PCIDS, 1784-PCD NA NA Yes NA NA
1784-KTX, 1784-KTXD, 1784-PCMK NA NA NA NA NA
1788-CN2DN NA Yes Yes NA NA
1788-EN2DN Yes NA Yes NA NA
1788-CN2FF NA Yes NA NA NA
1203-CN1 ControlNet module NA Yes¬  NA NA NA
1203-FM1/FB1 SCANport NA YesT  NA NA NA
  
¬ Use the generic module configuration to configure the 1203-CN1 module and a CIP generic MSG instruction to communicate with the module.
T Use a CIP generic MSG instruction to communicate with the 1203-FM1 SCANport module on a DIN rail that is remote to the controller. The remote DIN rail also requires a 1794-ACN(R)15 ControlNet adapter module.