MicroLogix 1200 System

Catalogs > Automation Systems Catalog > Programmable Controllers > MicroLogix 1200 System > MicroLogix 1200 Controllers

MicroLogix 1200 Controllers

Introduction Product Design Communication Typical Configurations Specifications
Specifications

General Specifications

Cat. No. 1762-L24AWA
1762-L24AWAR
1762-L24BWA
1762-L24BWAR
1762-L24BXB
1762-L24BXBR
1762-L40AWA
1762-L40AWAR
1762-L40BWA
1762-L40BWAR
1762-L40BXB
1762-L40BXBR
Dimensions (HxWxD), Approx. 90 x 110 x 87 mm (3.54 x 4.33 x 3.43 in.)⋆  90 x 160 x 87 mm (3.54 x 6.30 x 3.43 in.)⋆ 
Weight 0.9 kg (2.0 lb) 1.1 kg (2.4 lb)
Input Voltage Range 85…265V AC at 47…63 Hz 20.4…26.4V DC 85…265V AC at 47…63 Hz 20.4…26.4V DC
Input Voltage, Nom. 100/120V AC, 200/240V AC 24V DC 100/120V AC, 200/240V AC 24V DC
Apparent Input Power, Max. 68 VA 70 VA N/A 80 VA 82 VA N/A
Real Input Power, Max. 29 W 31 W 27 W 37 W 38 W 37 W
Power Supply Maximum Inrush 25 A for 8 ms at 120V AC
40 A for 4 ms at 240V AC
15 A for 20 ms at 24V DC 25 A for 8 ms at 120V AC
40 A for 4 ms at 240V AC
15 A for 20 ms at 24V DC
Power Supply Output 400 mA at 5V DC
350 mA at 24V DC
400 mA at 5V DC
350 mA at 24V DC‡ 
400 mA at 5V DC
350 mA at 24V DC
600 mA at 5V DC
500 mA at 24V DC
600 mA at 5V DC
500 mA at 24V DC§ 
600 mA at 5V DC
500 mA at 24V DC
User Output Power 24V DC at 250 mA, 400 mF max.‡  24V DC at 400 mA, 400 mF max.§ 
Operating Temperature 0…55 °C (32…131 °F)
Nonoperating Temperature -40…85 °C (-40…185 °F)
Operating Humidity 5…95% noncondensing
Vibration
Operating
10…500 Hz, 5 g, 0.030 in max. peak-to-peak
Relay Operation
1.5 g
Shock
Operating Shock
30 g
Shock, Relay Operation
7 g
Nonoperating Shock
50 g panel mounted, 40 g DIN rail mounted
Agency Certification • UL 508
• C-UL under CSA C22.2 no. 142
• Class I, Div. 2, Groups A, B, D, B (UL 1604, C-UL under CSA C22.2 no. 213)
• CE/C-Tick compliant for all applicable directives/acts.
Electrical/EMC The controller has passed testing at the following levels:
• IEC1000-4-2: 4 kV contact, 8 kV air, 4 kV indirect
• IEC1000-4-3: 10V/m
• IEC1000-4-4: 2 kV, 5 kHz; communication cable: 1 kV, 5 kHz
• IEC1000-4-5: communication cable 1 kV DM (differential mode)
• I/O: 2 kV CM (common mode), 2 kV DM (differential mode)
• Power Supply: 4 kV CM (common mode), 2 kV DM (differential mode)
• IEC1000-4-6: 10V, communication cable 3V♣ 
  
⋆ Height = 104 mm (4.09 in) with DIN latch open.
‡ Total load of the 5V, 24V, and user power output shall not exceed 12 W.
§ Total load of the 5V, 24V, and user power output shall not exceed 16 W.
♣ Conducted immunity frequency range may be 150 kHz to 30 MHz if the radiated immunity frequency range is 30 MHz to 1000 MHz.

MicroLogix 1200 Controllers

The MicroLogix 1200 controller is available with 24 or 40 built-in I/O. Controllers with 24V DC inputs that also have AC -input power supplies include a built-in power supply for user output power.

Cat. No. Number of I/O Input Type Input Signal Delay Output Type Continuous Output Current, Max. User Output Power
1762-L24BWA
1762-L24BWAR
14 inputs
10 outputs
24V DC sink/source Selectable: 0.025, 0.075, 0.1,
0.25, 0.5, 1, 2, 4, 8, or 16 ms
Relay Contact (See relay contact output specs.)
• 8 A/common
• 30 A total at 150V AC
• 20 A total at 240V AC
24V DC at 250 mA, 400 mF max.
1762-L40BWA
1762-L40BWAR
24 inputs
16 outputs
24V DC at 400 mA, 400 mF max.
1762-L24BXB
1762-L24BXBR
14 inputs
10 outputs
5 Relay
5 FET (24V DC)
(See FET and relay contact output specs.)
• 7.5 A/common
• 30 A total at 150V AC
• 20 A total at 240V AC
1762-L40BXB
1762-L40BXBR
24 inputs
16 outputs
8 Relay
8 FET (24V DC)
(See FET and relay contact output specs.)
• 8 A/common
• 30 A total at 150V AC
• 20 A total at 240V AC
1762-L24AWA
1762-L24AWAR
14 inputs
10 outputs
120V AC On: 2…20 ms Relay Contact
1762-L40AWA
1762-L40AWAR
24 inputs
16 outputs
  

Input Specifications

Cat. No. 1762-L24AWA, 1762-L40AWA
1762-L24AWAR, 1762-L40AWAR
1762-L24BWA, 1762-L24BXB, 1762-L40BWA, 1762-L40BXB
1762-L24BWAR, 1762-L24BXBR, 1762-L40BWAR, 1762-L40BXBR
Inputs 0 to 3 Inputs 4 and up
On-State Voltage Range 79…132V AC 14…26.4V DC @ 55 °C (131 °F)
14…30.0V DC @ 30 °C (86 °F)
10…26V DC @ 55 °C (131 °F)
10…30.0V DC @ 30 °C (86 °F)
Off-State Voltage Range 0…20V AC 0…5V DC
Operating Frequency 47…63 Hz 0…20 kHz 0…1 kHz (depends on scan time)
On-State Current
Minimum
5.0 mA @ 79V AC 2.5 mA @ 14V DC 2.0 mA @ 10V DC
Nominal
12 mA @ 120V AC 7.3 mA @ 24V DC 8.9 mA @ 24V DC
Maximum
16.0 mA @ 132V AC 12.0 mA @ 30V DC 12.0 mA @ 30V DC
Off-State Leakage Current, Max. 2.5 mA 1.5 mA
Impedance, Nom. 12 kW @ 50 Hz
10 kW @ 60 Hz
3.3 kW 2.7 kW
Inrush Current 250 mA
  

Relay Contact Output Specifications

Maximum Voltage Current Apparent Power
Make Break Continuous Make Break
240V AC 7.5A 0.75A 2.5A 1800 VA 180 VA
120V AC 15A 1.5A 2.5A
125V DC 0.22A 1.0A 28 VA
24V DC 1.2A 2.0A
  

FET Output Specifications

Cat. No. 1762-L24BXB, 1762-L24BXBR, 1762-L40BXB, 1762-L40BXBR
General Operation High-Speed Operation⋆  (Output 2 Only)
On-State Voltage Drop
at maximum load current
1V DC
at maximum surge current
2.5V DC
Current Rating per Output
maximum load
1.5A @ 30 °C (86 °F), 1.0A @ 55 °C (131 °F) 100 mA
minimum load
1.0 mA 10 mA
maximum leakage
1.0 mA 1.0 mA
Turn-On Time, Max. 0.1 ms 6 ms
Turn-Off Time, Max. 1.0 ms 18 ms
Repeatability, Max. 2 ms
Drift, Max. 1s per 5 °C (9 °F)
  
⋆ Output 2 has increased functionality over the other FET outputs. Output 2 can be used as the other FET outputs. But, in addition, within a limited current range, it may be operated at a higher speed. Output 2 also provides a pulse train output (PTO) or pulse width modulation output (PWM) function.