Catalogs > Automation Systems Catalog > Programmable Controllers > MicroLogix 1200 System > MicroLogix 1200 Controllers
MicroLogix 1200 Controllers
SpecificationsGeneral Specifications
| Cat. No. | 1762-L24AWA 1762-L24AWAR |
1762-L24BWA 1762-L24BWAR |
1762-L24BXB 1762-L24BXBR |
1762-L40AWA 1762-L40AWAR |
1762-L40BWA 1762-L40BWAR |
1762-L40BXB 1762-L40BXBR |
| Dimensions (HxWxD), Approx. | 90 x 110 x 87 mm (3.54 x 4.33 x 3.43 in.)⋆ | 90 x 160 x 87 mm (3.54 x 6.30 x 3.43 in.)⋆ | ||||
| Weight | 0.9 kg (2.0 lb) | 1.1 kg (2.4 lb) | ||||
| Input Voltage Range | 85…265V AC at 47…63 Hz | 20.4…26.4V DC | 85…265V AC at 47…63 Hz | 20.4…26.4V DC | ||
| Input Voltage, Nom. | 100/120V AC, 200/240V AC | 24V DC | 100/120V AC, 200/240V AC | 24V DC | ||
| Apparent Input Power, Max. | 68 VA | 70 VA | N/A | 80 VA | 82 VA | N/A |
| Real Input Power, Max. | 29 W | 31 W | 27 W | 37 W | 38 W | 37 W |
| Power Supply Maximum Inrush | 25 A for 8 ms at 120V AC 40 A for 4 ms at 240V AC |
15 A for 20 ms at 24V DC | 25 A for 8 ms at 120V AC 40 A for 4 ms at 240V AC |
15 A for 20 ms at 24V DC | ||
| Power Supply Output | 400 mA at 5V DC 350 mA at 24V DC |
400 mA at 5V DC 350 mA at 24V DC |
400 mA at 5V DC 350 mA at 24V DC |
600 mA at 5V DC 500 mA at 24V DC |
600 mA at 5V DC 500 mA at 24V DC§ |
600 mA at 5V DC 500 mA at 24V DC |
| User Output Power | — | 24V DC at 250 mA, 400 mF max. | — | — | 24V DC at 400 mA, 400 mF max.§ | — |
| Operating Temperature | 0…55 °C (32…131 °F) | |||||
| Nonoperating Temperature | -40…85 °C (-40…185 °F) | |||||
| Operating Humidity | 5…95% noncondensing | |||||
| Vibration | ||||||
| 10…500 Hz, 5 g, 0.030 in max. peak-to-peak | ||||||
| 1.5 g | ||||||
| Shock | ||||||
| 30 g | ||||||
| 7 g | ||||||
| 50 g panel mounted, 40 g DIN rail mounted | ||||||
| Agency Certification | UL 508 C-UL under CSA C22.2 no. 142 Class I, Div. 2, Groups A, B, D, B (UL 1604, C-UL under CSA C22.2 no. 213) CE/C-Tick compliant for all applicable directives/acts. |
|||||
| Electrical/EMC | The controller has passed testing at the following levels: IEC1000-4-2: 4 kV contact, 8 kV air, 4 kV indirect IEC1000-4-3: 10V/m IEC1000-4-4: 2 kV, 5 kHz; communication cable: 1 kV, 5 kHz IEC1000-4-5: communication cable 1 kV DM (differential mode) I/O: 2 kV CM (common mode), 2 kV DM (differential mode) Power Supply: 4 kV CM (common mode), 2 kV DM (differential mode) IEC1000-4-6: 10V, communication cable 3V♣ |
|||||
| ⋆ Height = 104 mm (4.09 in) with DIN latch open. Total load of the 5V, 24V, and user power output shall not exceed 12 W. § Total load of the 5V, 24V, and user power output shall not exceed 16 W. ♣ Conducted immunity frequency range may be 150 kHz to 30 MHz if the radiated immunity frequency range is 30 MHz to 1000 MHz. |
||||||
MicroLogix 1200 Controllers
The MicroLogix 1200 controller is available with 24 or 40 built-in I/O. Controllers with 24V DC inputs that also have AC -input power supplies include a built-in power supply for user output power.
| Cat. No. | Number of I/O | Input Type | Input Signal Delay | Output Type | Continuous Output Current, Max. | User Output Power |
| 1762-L24BWA 1762-L24BWAR |
14 inputs 10 outputs |
24V DC sink/source | Selectable: 0.025, 0.075, 0.1, 0.25, 0.5, 1, 2, 4, 8, or 16 ms |
Relay Contact | (See relay contact output specs.) 8 A/common 30 A total at 150V AC 20 A total at 240V AC |
24V DC at 250 mA, 400 mF max. |
| 1762-L40BWA 1762-L40BWAR |
24 inputs 16 outputs |
24V DC at 400 mA, 400 mF max. | ||||
| 1762-L24BXB 1762-L24BXBR |
14 inputs 10 outputs |
5 Relay 5 FET (24V DC) |
(See FET and relay contact output specs.) 7.5 A/common 30 A total at 150V AC 20 A total at 240V AC |
— | ||
| 1762-L40BXB 1762-L40BXBR |
24 inputs 16 outputs |
8 Relay 8 FET (24V DC) |
(See FET and relay contact output specs.) 8 A/common 30 A total at 150V AC 20 A total at 240V AC |
|||
| 1762-L24AWA 1762-L24AWAR |
14 inputs 10 outputs |
120V AC | On: 2…20 ms | Relay Contact | ||
| 1762-L40AWA 1762-L40AWAR |
24 inputs 16 outputs |
|||||
Input Specifications
| Cat. No. | 1762-L24AWA, 1762-L40AWA 1762-L24AWAR, 1762-L40AWAR |
1762-L24BWA, 1762-L24BXB, 1762-L40BWA, 1762-L40BXB 1762-L24BWAR, 1762-L24BXBR, 1762-L40BWAR, 1762-L40BXBR |
|
| Inputs 0 to 3 | Inputs 4 and up | ||
| On-State Voltage Range | 79…132V AC | 14…26.4V DC @ 55 °C (131 °F) 14…30.0V DC @ 30 °C (86 °F) |
10…26V DC @ 55 °C (131 °F) 10…30.0V DC @ 30 °C (86 °F) |
| Off-State Voltage Range | 0…20V AC | 0…5V DC | |
| Operating Frequency | 47…63 Hz | 0…20 kHz | 0…1 kHz (depends on scan time) |
| On-State Current | |||
| 5.0 mA @ 79V AC | 2.5 mA @ 14V DC | 2.0 mA @ 10V DC | |
| 12 mA @ 120V AC | 7.3 mA @ 24V DC | 8.9 mA @ 24V DC | |
| 16.0 mA @ 132V AC | 12.0 mA @ 30V DC | 12.0 mA @ 30V DC | |
| Off-State Leakage Current, Max. | 2.5 mA | 1.5 mA | |
| Impedance, Nom. | 12 kW @ 50 Hz 10 kW @ 60 Hz |
3.3 kW | 2.7 kW |
| Inrush Current | 250 mA | — | — |
Relay Contact Output Specifications
| Maximum Voltage | Current | Apparent Power | |||
| Make | Break | Continuous | Make | Break | |
| 240V AC | 7.5A | 0.75A | 2.5A | 1800 VA | 180 VA |
| 120V AC | 15A | 1.5A | 2.5A | ||
| 125V DC | 0.22A | 1.0A | 28 VA | ||
| 24V DC | 1.2A | 2.0A | |||
FET Output Specifications
| Cat. No. | 1762-L24BXB, 1762-L24BXBR, 1762-L40BXB, 1762-L40BXBR | |
| General Operation | High-Speed Operation⋆ (Output 2 Only) | |
| On-State Voltage Drop | ||
| 1V DC | — | |
| 2.5V DC | ||
| Current Rating per Output | ||
| 1.5A @ 30 °C (86 °F), 1.0A @ 55 °C (131 °F) | 100 mA | |
| 1.0 mA | 10 mA | |
| 1.0 mA | 1.0 mA | |
| Turn-On Time, Max. | 0.1 ms | 6 ms |
| Turn-Off Time, Max. | 1.0 ms | 18 ms |
| Repeatability, Max. | — | 2 ms |
| Drift, Max. | — | 1s per 5 °C (9 °F) |
| ⋆ Output 2 has increased functionality over the other FET outputs. Output 2 can be used as the other FET outputs. But, in addition, within a limited current range, it may be operated at a higher speed. Output 2 also provides a pulse train output (PTO) or pulse width modulation output (PWM) function. | ||