Catalogs > Automation Systems Catalog > Programmable Controllers > MicroLogix 1200 System > 1762 MicroLogix Expansion I/O
1762 MicroLogix Expansion I/O
| Introduction | Environmentals and Certifications | Digital I/O Modules | Analog I/O Modules | Specialty I/O Modules |
Environmental Specifications
| 1762 MicroLogix Expansion I/O Modules | |
| Operating Temperature | -20…65 °C (-4…149 °F) (on selected modules) |
| Operating Humidity | 5…95% noncondensing |
| Operating Altitude, Max. | 2,000 m (6,561 ft) |
| Vibration, Operating | 10…500 Hz, 5 g, 0.015 in peak-to-peak |
| Vibration, Relay Operation | 2 g |
| Shock, Operating | 30 g panel mounted, 20 g DIN-rail mounted |
| Shock, Relay Operation | 7.5 g panel mounted, 5 g DIN rail mounted |
| Shock, Nonoperating | 40 g panel mounted, 30 g DIN rail mounted |
| Dimensions (HxWxD), Approx. | 90 x 40 x 87mm (3.543 x 1.575 x 3.425 in.)⋆ |
| Radiated and Conducted Emissions | EN50081-2 Class A |
| ESD Immunity (IEC 1000-4-2) | 4 kV contact, 8 kV air, 4 kV indirect |
| Radiated RF Immunity (IEC 1000-4-3) | 10V/m, 80…1000 MHz, 80% amplitude modulation, +900 MHz keyed carrier |
| EFT/B Immunity (IEC 1000-4-4) | 2 kV, 5 kHz |
| Surge Transient Immunity (IEC 1000-4-5) | 2 kV common mode, 1 kV differential mode |
| Conducted RF Immunity (IEC 1000-4-6) | 10V, 0.15…80 MHz |
| ⋆ Height including mounting tabs is 110 mm (4.33 in.). Conducted immunity frequency range may be 150 kHz…30 MHz if the radiated immunity frequency range is 30 MHz…1000 MHz. |
|
Certifications
Certifications: C-UL certified (under CSA C22.2 No. 142), UL 508 Listed, CE compliant for all applicable directives.
Hazardous Environment Class: Class I, Division 2, Hazardous Location, Groups A, B, C, D (UL1604, C-UL under CSA C22.2 No. 213).
When product is marked. See the Product Certification link at www.ab.com for Declarations of Conformity, Certificates, and other certification details.