ControlLogix System

Catalogs > Automation Systems Catalog > Programmable Controllers > ControlLogix System > Redundancy Modules

Redundancy Modules

Redundancy Modules

ControlLogix redundancy modules are required for a redundant system. Standard and extreme environment modules are available.

ControlLogix firmware version 19.50 supports enhanced redundancy features for high-availability applications. Download the enhanced redundancy firmware bundle (V19.52Enh) from the Rockwell Automation Support site.


Redundant Controller System Requirements

Redundant System Requirements
Two 1756 chassis Each chassis must have the same:
– number of slots
– modules in the same slots
– redundancy firmware revisions in each module
Additional ControlNet nodes, if the application uses ControlNet networks Two additional ControlNet nodes outside the redundant chassis pair
Redundancy module in each chassis 1756-RM or 1756-RMXT redundancy module in each chassis, connected by a 1756-RMCx cable
ControlLogix controllers One or two 1756-L6 or 1756-L7 controllers in each chassis
Software for enhanced redundancy systems Required:
– Redundancy Module Configuration Tool 7.2.7
– RSLinx Classic 2.57 (CPR 9, SR3)
– RSLogix 5000 19.01 (CPR 9, SR 3)
Optional
– FactoryTalk Services Platform 2.10.02 (CPR 9, SR3)(1)
– FactoryTalk Alarms and Events 2.20.00 (CPR 9, SR2)
– FactoryTalk Batch 11.00.00(2)
– FactoryTalk View Site Edition 5.10.00 (CPR 9, SR2)
– RSLinx Enterprise 5.21 (CPR 9, SR2)

ControlLogix Redundancy Modules

Specifications [PDF]

Cat. No. Description Controllers Supported ControlNet Communication Modules Supported EtherNet/IP Communication Modules Supported
1756-RM ControlLogix redundancy module One or two 1756-L6 or 1756-L7 controllers in each chassis Up to seven enhanced ControlNet communication modules: 1756-CN2/B, 1756-CN2R/B, 1756-CN2RXT Up to seven enhanced EtherNet/IP communication modules: 1756-EN2T, 1756-EN2TR, 1756-EN2TXT
1756-RMXT ControlLogix redundancy module rated for extreme environment
Enhanced redundancy firmware v19.50 does not support the following:
1757-SRM redundancy module
1756-CNB(R) series D or E ControlNet communication modules
1756-ENBT, 1756-EWEB, and 1756-EN2F EtherNet/IP communication modules

Connector Cables

Cat. No. Description Length
1756-RMC1 Cable, 1756-RM redundancy module 1 m (3.28 ft)
1756-RMC3 3 m (9.84 ft)
1756-RMC10 10 m (32.81 ft)