Catalogs > Automation Systems Catalog > Programmable Controllers > ControlLogix System > Redundancy Modules
Redundancy Modules
Redundancy ModulesControlLogix redundancy modules are required for a redundant system. Standard and extreme environment modules are available.
ControlLogix firmware version 19.50 supports enhanced redundancy features for high-availability applications. Download the enhanced redundancy firmware bundle (V19.52Enh) from the Rockwell Automation Support site.
Redundant Controller System Requirements
| Redundant System Requirements | |
| Two 1756 chassis | Each chassis must have the same: number of slots modules in the same slots redundancy firmware revisions in each module |
| Additional ControlNet nodes, if the application uses ControlNet networks | Two additional ControlNet nodes outside the redundant chassis pair |
| Redundancy module in each chassis | 1756-RM or 1756-RMXT redundancy module in each chassis, connected by a 1756-RMCx cable |
| ControlLogix controllers | One or two 1756-L6 or 1756-L7 controllers in each chassis |
| Software for enhanced redundancy systems | Required: Redundancy Module Configuration Tool 7.2.7 RSLinx Classic 2.57 (CPR 9, SR3) RSLogix 5000 19.01 (CPR 9, SR 3) Optional FactoryTalk Services Platform 2.10.02 (CPR 9, SR3)(1) FactoryTalk Alarms and Events 2.20.00 (CPR 9, SR2) FactoryTalk Batch 11.00.00(2) FactoryTalk View Site Edition 5.10.00 (CPR 9, SR2) RSLinx Enterprise 5.21 (CPR 9, SR2) |
ControlLogix Redundancy Modules
Specifications [PDF]
| Cat. No. | Description | Controllers Supported | ControlNet Communication Modules Supported | EtherNet/IP Communication Modules Supported |
| 1756-RM | ControlLogix redundancy module | One or two 1756-L6 or 1756-L7 controllers in each chassis | Up to seven enhanced ControlNet communication modules: 1756-CN2/B, 1756-CN2R/B, 1756-CN2RXT | Up to seven enhanced EtherNet/IP communication modules: 1756-EN2T, 1756-EN2TR, 1756-EN2TXT |
| 1756-RMXT | ControlLogix redundancy module rated for extreme environment | |||
| Enhanced redundancy firmware v19.50 does not support the following: 1757-SRM redundancy module 1756-CNB(R) series D or E ControlNet communication modules 1756-ENBT, 1756-EWEB, and 1756-EN2F EtherNet/IP communication modules |
||||
Connector Cables
| Cat. No. | Description | Length |
| 1756-RMC1 | Cable, 1756-RM redundancy module | 1 m (3.28 ft) |
| 1756-RMC3 | 3 m (9.84 ft) | |
| 1756-RMC10 | 10 m (32.81 ft) |