ControlLogix Controllers

1756 ControlLogix Controllers

Click to enlarge - 1756-L1M2 Logix5550 Open_GS


The ControlLogix controller provides a scalable controller solution that is capable of addressing a large amount of I/O points.

The ControlLogix controller can be placed into any slot of a ControlLogix I/O chassis and multiple controllers can be installed in the same chassis. Multiple controllers in the same chassis communicate with each other over the backplane (just as controllers can communicate over networks) but operate independently.

ControlLogix controllers can monitor and control I/O across the ControlLogix backplane, as well as over I/O links. ControlLogix controllers can communicate with computers or other processors across RS-232-C (DF1/DH-485 protocol), DeviceNet, DH+, ControlNet, and EtherNet/IP networks. To provide communication for a ControlLogix controller, install the appropriate communication interface module into the chassis.

The multitasking operating system supports 32 configurable tasks that can be prioritized. One task can be continuous. The others must be periodic or event tasks. Each task can have as many as 100 programs, each with its own local data and logic, allowing virtual machines to operate independently within the same controller.


Specification Description
Battery 1756-BA1 for series A controllers
1756-BA2 for 1756-L6x, series B controllers
1756-BATM (contains a 1756-BATA battery assembly) for series A controllers
Programming cable 1756-CP3 or 1747-CP3 serial cable
  
Certifications: UL, CSA (Class I, Division 2, Group A, B, C, D), CE, FM (1756-L6x controllers only), C-Tick, EEx ATEX

Available 1756 Controllers

Cat. No. Memory Power Dissipation, Max. Thermal Dissipation, Max. Backplane Current (mA) at 5V Backplane Current (mA) at 24V
Available User Memory (Kbytes)¬  I/O Memory Nonvolatile Memory
1756-L55M12 750 K bytes 208 K bytesT  NA 5.6 W 19.1 BTU/hr 1230 mA 14 mA
1756-L55M13 1536 K bytes 208 K bytesT  NA 5.6 W 19.1 BTU/hr 1230 mA 14 mA
1756-L55M14 3584 K bytes 208 K bytesT  NA 5.7 W 19.4 BTU/hr 1250 mA 14 mA
1756-L55M16 7680 K bytes
‡ 
208 K bytesT  NA 6.3 W 21.5 BTU/hr 1480 mA 14 mA
1756-L55M22 750 K bytes 208 K bytesT  750 Kbytes 5.6 W 19.1 BTU/hr 1230 mA 14 mA
1756-L55M23 1536 K bytes 208 K bytesT  1.5 Mbytes 5.6 W 19.1 BTU/hr 1230 mA 14 mA
1756-L55M24 3584 K bytes 208 K bytesT  3.5 Mbytes 5.7 W 19.4 BTU/hr 1250 mA 14 mA
1756-L61 2048 K bytes 478 K bytesT  64 Mbytes CompactFlash§  3.5 W 11.9 BTU/hr 1200 mA 14 mA
1756-L61S 2048 KB Standard
1024 KB Safety
478 KB 64 MB CompactFlash 3.5 W 11.9 BTU/hr 1200 mA 14 mA
1756-L62 4096 K bytes 478 K bytesT  64 Mbytes CompactFlash§  3.5 W 11.9 BTU/hr 1200 mA 14 mA
1756-L62S 4096 KB Standard
1024 KB Safety
478 KB 64 MB CompactFlash 3.5 W 11.9 BTU/hr 1200 mA 14 mA
1756-L63 8196 K bytes 478 K bytesT  64 Mbytes CompactFlash§  3.5 W 11.9 BTU/hr 1200 mA 14 mA
1756-L64 16,384 K bytes 478 K bytesT  64 Mbytes CompactFlash§  3.5 W 11.9 BTU/hr 1200 mA 14 mA
1756-L60M03SEv    478 K bytesT  64 Mbytes CompactFlash§  8.5 W 11.9 BTU/hr 1960 mA 6 mA
1756-LSP NA - Safety Partner NA NA 3.5 W 11.9 BTU/hr 1200 mA 14 mA
  
¬ Data and Logic memory stores: tags other than I/O, produced, or consumed tags; logic routines; and communication with OPC/DDE tags that use RSLinx software.
T I/O memory stores: I/O tags, produced tags, consumed tags, communication via Message (MSG) instructions, communication with workstations, and communication with OPC/DDE tags that use RSLinx software.
‡ No more than 3500 Kbytes of data.
§ Requires a 1784-CF64 Industrial CompactFlash card.
v The 1756-L60M03SE is a 1756-L60 ControlLogix controller with an embedded 1756-M03SE SERCOS interface. This is a 2-slot module.

The 1756-L6x controller executes ladder scans almost twice as fast as the 1756-L55 controllers and executes function block, REAL data type math, and motion instructions four to five times faster than the 1756-L55 controllers.

The 1756-L60M03SE controller combines a 1756-L6x controller and a SERCOS motion module in a two-slot module. This controller is ideal for small motion systems and can control three SERCOS axes with the included interface. This controller can control as many as six axes if you add an additional motion module.


Select a Controller for a Redundant Controller System

If you are designing a redundant controller system, consider:


Select a Controller for a Safety System

If you are designing a safety controller system, consider:


Controller Memory Use

The following equations provide an estimate of the memory needed for a controller.

Controller Tasks _____ * 4000 = _____ bytes
(minimum 1 task)
Digital I/O points _____ * 400 = _____ bytes
Analog I/O points _____ * 2600 = _____ bytes
Communication modules¬  _____ * 2000 = _____ bytes
Motion axes _____ * 8000 = _____ bytes
  
¬ When estimating memory use by communication modules, count all the communication modules in the system, not just those in the local chassis. This includes device connection modules, adapter modules, and ports on PanelView terminals.

Additional 1756-L55 Memory

The 1756-L55 controllers do not operate standalone. Choose one of these memory boards to come already assembled with the controller. You can also order additional memory boards either for spare parts or to upgrade existing 1756-L55 controllers.

The 1756-L6x controllers have a fixed RAM size and do not use a memory board. Use a CompactFlash card for nonvolatile storage.


Catalog Number Supported Controller Battery-backed Static RAM Nonvolatile RAM
1756-M12¬  1756-L55 750 KB None
1756-M13 1756-L55 1.5 MB None
1756-M14 1756-L55 3.5 MB None
1756-M16 1756-L55 7.5 MB
3.5 MB for tag data
None
1756-M22¬  1756-L55 750 KB 750 KB
1756-M23T  1756-L55 1.5 MB 1.5 MB
1756-M24T  1756-L55 3.5 MB 3.5 MB
1784-CF64 1756-L6x‡  None
RAM contents are written to internal Flash during power down
Same as the memory limit for the controller
  
¬ The 1756-L55 controller must have firmware revision 10 or later.
T The 1756-L55 controller must have firmware revision 8 or later.
‡ You can use CompactFlash with the 1756-L61, 1756-L62, 1756-L63, and 1756-L60M03SE controllers. The 1756-L61, 1756-L62 controllers require firmware revision 12 or later. The 1756-L63 controller requires firmware revision 11 or later. The 1756-L60M03SE controller requires firmware revision 13 or later.

CompactFlash Memory

The CompactFlash card offers nonvolatile memory (flash) to permanently store a user program and tag data on a controller.


The 1756-L55M2x controllers have fixed internal nonvolatile memory.

The 1756-L6x controllers support a removable CompactFlash card for nonvolatile memory. You install the 1784-CF64 card in a socket on the controller. The CompactFlash card stores the user program, tag data, and controller firmware. This lets you upgrade firmware on a 1756-L6x controllers without using RSLogix 5000 software or ControlFlash software.


Battery Requirements

Each controller ships with a battery.

Cat. No. Description Estimated Worst Case Battery Life
1756-BA1 Lithium battery (0.59 g) installed in each ControlLogix controller.
Order only if you need a replacement.
Estimate @ 25 °C (77 °F)
• 1756-L55M12: 63 days
• 1756-L55M13: 63 days
• 1756-L55M14: 30 days
• 1756-L55M16: 13 days
• 1756-L55M22: 63 days
• 1756-L55M23: 63 days
• 1756-L55M44: 30 days
• Series A 1756-L6x: 21 days
• 1756-L60M03SE: 21 days
1756-BATM Externally mounted battery assembly.
Provides longer battery life than the 1756-BA1.

Contains:
• One 1756-BATA assembly
• 1 m (3.28 ft) cable to connect housing to controller
Estimate @ 25 °C (77 °F)
• 1756-L55M12: 299 days
• 1756-L55M13: 299 days
• 1756-L55M14: 213 days
• 1756-L55M16: 133 days
• 1756-L55M22: 299 days
• 1756-L55M23: 299 days
• 1756-L55M24: 213 days
• Series A 1756-L6x: 146 days
1756-BATA Lithium battery assembly (maximum of 5 g lithium per each D cell; assembly contains 2 D cells) included with the 1756-BATM.
Order only if you need a replacement.
1756-BA2 Lithium battery (0.59 g) installed in each 1756-L6x series B controller.
Order only if you need a replacement.
Estimate @ 60 °C (140 °F)
• Series B 1756-L6x: 8 months
  

The 1756-BATM battery module is recommended for use with all 1756-L55 and series A 1756-L6x controllers.

Controller 1756-BATM 1756-BATA 1756-BA1 1756-BA2
1756-L55M12 Recommended For a replacement For a replacement Not supported
1756-L55M13 Recommended For a replacement For a replacement Not supported
1756-L55M14 Highly recommended For a replacement For a replacement Not supported
1756-L55M16 Highly recommended For a replacement Not recommended for long-term use Not supported
1756-L55M22¬  Recommended For a replacement For a replacement Not supported
1756-L55M23¬  Recommended For a replacement For a replacement Not supported
1756-L55M24¬  Highly recommended For a replacement Not recommended for long-term use Not supported
1756-L60M03SE Highly recommended For a replacement For a replacement Not supported
1756-L61T  Highly recommended
Series A only
For a replacement
Series A only
Series A only Series B only
1756-L61S Not supported Not supported Not supported Only battery supported
1756-L62T  Highly recommended
Series A only
For a replacement
Series A only
Series A only Series B only
1756-L62S Not supported Not supported Not supported Only battery supported
1756-L63T  Highly recommended
Series A only
For a replacement
Series A only
Series A only Series B only
1756-L64 Not supported Not supported Not supported Only battery supported
1756-LSP Safety partner Not supported Not supported Not supported Only battery supported
  
¬ These controllers have nonvolatile memory and can be used without a battery.
T The 1756-L6x controllers have nonvolatile memory if you install a 1784-CF64 CompactFlash card. With nonvolatile memory, the controller can be used without a battery. If you do not use a battery, current tag data will be at the state they were when the nonvolatile memory was saved.

Compatibility

Control Distributed I/O Modules

The ControlLogix controller can control these distributed I/O modules using the I/O Configuration tree in RSLogix 5000 programming software.

I/O Modules EtherNet/IP ControlNet DeviceNet Remote I/O
1732 ArmorBlock I/O Yes No Yes No
1734 POINT I/O Yes Yes Yes No
1734D POINTBlock I/O No No Yes No
1738 ArmorPoint I/O Yes Yes Yes No
1746 SLC I/O No No No Yes
1756 ControlLogix I/O Yes Yes No No
1769 Compact I/O No No Yes No
1771 Universal I/O No YesT  No Yes
1790 CompactBlock LDX I/O No No Yes No
1791D CompactBlock I/O No No Yes No
1792D ArmorBlock MaXum I/O No No Yes No
1794 FLEX I/O Yes Yes Yes Yes
1797 FLEX Ex I/O No Yes No No
1798 FLEX Armor I/O No No Yes No
1799 Embedded I/O No No Yes No
  
¬ Requires RSLogix 5000 programming software version 11 or later. Use the generic FLEX profile.
T Use a 1771-ACN15, 1771-ACNR15 adapter module. Version 10 and later of RSLogix 5000 Enterprise Series software supports 1771 digital, analog, and specialty I/O modules. Previous versions of the software support only 1771 digital I/O modules.

Communicate with Display Devices

The ControlLogix controller can communicate with these display devices.

Display Devices EtherNet/IP ControlNet DeviceNet DH+ Remote I/O RS-232 (DF1) DH-485
2711P PanelView Plus terminal Yes Yes Yes Yes Yes Yes No¬ 
6182H VersaView CE computer Yes Yes Yes Yes Yes Yes No¬ 
2711 PanelView terminal Yes Yes Yes YesT  Yes YesT  YesT 
2711 e PanelView terminal No Yes No YesT  Yes No No
800E, 800T RediSTATION/RediPANEL operator module No No Yes No Yes No No
2706 InView message display Yes Yes Yes Yes Yes Yes Yes
2706 DL40 Dataliner message display No No No No Yes Yes No
2706 DL, DL50 DataLiner message display No No No No No Yes No
2707 DTAM Plus operator interface No No Yes No Yes YesT  YesT 
  
¬ These devices support DH-485 communication to FlexLogix and CompactLogix controllers.
T Use PLC/SLC mapping.

Communicate with Other Controllers

The ControlLogix controller can communicate with these controllers.

Controller EtherNet/IP ControlNet DeviceNet DH+ RS-232 (DF1) DH-485§ 
1756 ControlLogix
1756 GuardLogix
Yes Yes Yes Yes Yes Yes
1768, 1769 CompactLogix Yes Yes Yes No Yes Yes
1789 SoftLogix5800 Yes Yes Yes No Yes No
1794 FlexLogix Yes Yes Yes No Yes Yes
5720 PowerFlex 700S with DriveLogix Yes Yes Yes No Yes Yes
1785 PLC-5 Yes¬ T  Yes Yes‡  Yes Yes N/A
1747 SLC Yes§  Yes Yes‡  Yes§  Yes Yes
1761 MicroLogix Yes No Yes‡  No Yes Yes
1762 MicroLogix Yes No Yes‡  No Yes Yes
1763 MicroLogix Yes No Yes‡  No Yes Yes
1764 MicroLogix Yes No Yes‡  No Yes Yes
1772 PLC-2 N/A N/A N/A YesØ  Yesz  N/A
1775 PLC-3 N/A N/A N/A Yesª  Yesv  N/A
5250 PLC-5/250 N/A N/A No Yes Yes N/A
  
¬ The Ethernet PLC-5 controller must be series C, firmware revision N.1 or later; series D, firmware revision E.1 or later; or series E, firmware revision D.1 or later.
T The 1785-ENET Ethernet communication interface module must be series A, firmware revision D or later.
‡ The PLC-5, SLC, and MicroLogix processors appear as I/O points to the Logix controller. Use the appropriate DeviceNet interface for the controller.
§ Use a 1747-L55x controller with OS501 or greater.
Ø The PLC-2 controller requires a 1785-KA module for DH+ communications.
z The PLC-2 controller requires a 1771-KG module for serial (DF1) communications.
ª The PLC-3 controller requires a 1775-S5 module for DH+ communications.
v The PLC-3 controller requires a 1775-KA module for serial (DF1) communications.
§ The 1756-DH485 module supports full DH-485 functionality.

Communicate with Other Communication Devices

The ControlLogix controller can communicate with these communication devices.

Communication Device EtherNet/IP ControlNet DeviceNet DH+ RS-232 (DF1) DH-485
1770-KFD N/A N/A Yes N/A N/A N/A
9355 RSLinx software Yes Yes No Yes Yes No
1784-KTC, 1784-KTCx, 1784-KTCx15, 1784-PCIC(S), 1784-PCC N/A Yes N/A N/A N/A N/A
1784-PCIDS, 1784-PCD N/A N/A Yes N/A N/A N/A
1784-KTX, 1784-KTXD, 1784-PCMK N/A N/A N/A Yes N/A N/A
1788-CN2DN N/A Yes Yes N/A N/A N/A
1788-EN2DN Yes N/A Yes N/A N/A N/A
1788-CN2FF N/A Yes N/A N/A N/A N/A
1203-CN1 ControlNet module N/A Yes¬  N/A N/A N/A N/A
1203-FM1/FB1 SCANport N/A YesT  N/A N/A N/A N/A
  
¬ Use the generic module configuration to configure the 1203-CN1 module and a CIP generic MSG instruction to communicate with the module.
T Use a CIP generic MSG instruction to communicate with the 1203-FM1 SCANport module on a DIN rail that is remote to the controller. The remote DIN rail also requires a 1794-ACN(R)15 ControlNet adapter module.