ControlLogix System

Catalogs > Automation Systems Catalog > Programmable Controllers > ControlLogix System > ControlLogix Controllers

ControlLogix Controllers

Introduction Available 1756 Controllers Controller Memory Use Battery Requirements Compatibility
Available 1756 Controllers

Cat. No. Memory Power Dissipation, Max. Thermal Dissipation, Max. Backplane Current (mA) at 5V Backplane Current (mA) at 24V
Available User Memory (Kbytes)¬  I/O Memory Nonvolatile Memory
1756-L55M12 750 K bytes 208 K bytesT  NA 5.6 W 19.1 BTU/hr 1230 mA 14 mA
1756-L55M13 1536 K bytes 208 K bytesT  NA 5.6 W 19.1 BTU/hr 1230 mA 14 mA
1756-L55M14 3584 K bytes 208 K bytesT  NA 5.7 W 19.4 BTU/hr 1250 mA 14 mA
1756-L55M16 7680 K bytes
‡ 
208 K bytesT  NA 6.3 W 21.5 BTU/hr 1480 mA 14 mA
1756-L55M22 750 K bytes 208 K bytesT  750 Kbytes 5.6 W 19.1 BTU/hr 1230 mA 14 mA
1756-L55M23 1536 K bytes 208 K bytesT  1.5 Mbytes 5.6 W 19.1 BTU/hr 1230 mA 14 mA
1756-L55M24 3584 K bytes 208 K bytesT  3.5 Mbytes 5.7 W 19.4 BTU/hr 1250 mA 14 mA
1756-L61 2048 K bytes 478 K bytesT  64 Mbytes CompactFlash§  3.5 W 11.9 BTU/hr 1200 mA 14 mA
1756-L61S 2048 KB Standard
1024 KB Safety
478 KB 64 MB CompactFlash 3.5 W 11.9 BTU/hr 1200 mA 14 mA
1756-L62 4096 K bytes 478 K bytesT  64 Mbytes CompactFlash§  3.5 W 11.9 BTU/hr 1200 mA 14 mA
1756-L62S 4096 KB Standard
1024 KB Safety
478 KB 64 MB CompactFlash 3.5 W 11.9 BTU/hr 1200 mA 14 mA
1756-L63 8196 K bytes 478 K bytesT  64 Mbytes CompactFlash§  3.5 W 11.9 BTU/hr 1200 mA 14 mA
1756-L64 16,384 K bytes 478 K bytesT  64 Mbytes CompactFlash§  3.5 W 11.9 BTU/hr 1200 mA 14 mA
1756-L60M03SEv    478 K bytesT  64 Mbytes CompactFlash§  8.5 W 11.9 BTU/hr 1960 mA 6 mA
1756-LSP NA - Safety Partner NA NA 3.5 W 11.9 BTU/hr 1200 mA 14 mA
  
¬ Data and Logic memory stores: tags other than I/O, produced, or consumed tags; logic routines; and communication with OPC/DDE tags that use RSLinx software.
T I/O memory stores: I/O tags, produced tags, consumed tags, communication via Message (MSG) instructions, communication with workstations, and communication with OPC/DDE tags that use RSLinx software.
‡ No more than 3500 Kbytes of data.
§ Requires a 1784-CF64 Industrial CompactFlash card.
v The 1756-L60M03SE is a 1756-L60 ControlLogix controller with an embedded 1756-M03SE SERCOS interface. This is a 2-slot module.

The 1756-L6x controller executes ladder scans almost twice as fast as the 1756-L55 controllers and executes function block, REAL data type math, and motion instructions four to five times faster than the 1756-L55 controllers.

The 1756-L60M03SE controller combines a 1756-L6x controller and a SERCOS motion module in a two-slot module. This controller is ideal for small motion systems and can control three SERCOS axes with the included interface. This controller can control as many as six axes if you add an additional motion module.


Select a Controller for a Redundant Controller System

If you are designing a redundant controller system, consider:


Select a Controller for a Safety System

If you are designing a safety controller system, consider: