ControlLogix System

Catalogs > Automation Systems Catalog > Programmable Controllers > ControlLogix System > ControlLogix Controllers

ControlLogix Controllers

Introduction Available 1756 Controllers Controller Memory Use Battery Requirements Compatibility
Battery Requirements

Each controller ships with a battery.

Cat. No. Description Estimated Worst Case Battery Life
1756-BA1 Lithium battery (0.59 g) installed in each ControlLogix controller.
Order only if you need a replacement.
Estimate @ 25 °C (77 °F)
• 1756-L55M12: 63 days
• 1756-L55M13: 63 days
• 1756-L55M14: 30 days
• 1756-L55M16: 13 days
• 1756-L55M22: 63 days
• 1756-L55M23: 63 days
• 1756-L55M44: 30 days
• Series A 1756-L6x: 21 days
• 1756-L60M03SE: 21 days
1756-BATM Externally mounted battery assembly.
Provides longer battery life than the 1756-BA1.

Contains:
• One 1756-BATA assembly
• 1 m (3.28 ft) cable to connect housing to controller
Estimate @ 25 °C (77 °F)
• 1756-L55M12: 299 days
• 1756-L55M13: 299 days
• 1756-L55M14: 213 days
• 1756-L55M16: 133 days
• 1756-L55M22: 299 days
• 1756-L55M23: 299 days
• 1756-L55M24: 213 days
• Series A 1756-L6x: 146 days
1756-BATA Lithium battery assembly (maximum of 5 g lithium per each D cell; assembly contains 2 D cells) included with the 1756-BATM.
Order only if you need a replacement.
1756-BA2 Lithium battery (0.59 g) installed in each 1756-L6x series B controller.
Order only if you need a replacement.
Estimate @ 60 °C (140 °F)
• Series B 1756-L6x: 8 months
  

The 1756-BATM battery module is recommended for use with all 1756-L55 and series A 1756-L6x controllers.

Controller 1756-BATM 1756-BATA 1756-BA1 1756-BA2
1756-L55M12 Recommended For a replacement For a replacement Not supported
1756-L55M13 Recommended For a replacement For a replacement Not supported
1756-L55M14 Highly recommended For a replacement For a replacement Not supported
1756-L55M16 Highly recommended For a replacement Not recommended for long-term use Not supported
1756-L55M22¬  Recommended For a replacement For a replacement Not supported
1756-L55M23¬  Recommended For a replacement For a replacement Not supported
1756-L55M24¬  Highly recommended For a replacement Not recommended for long-term use Not supported
1756-L60M03SE Highly recommended For a replacement For a replacement Not supported
1756-L61T  Highly recommended
Series A only
For a replacement
Series A only
Series A only Series B only
1756-L61S Not supported Not supported Not supported Only battery supported
1756-L62T  Highly recommended
Series A only
For a replacement
Series A only
Series A only Series B only
1756-L62S Not supported Not supported Not supported Only battery supported
1756-L63T  Highly recommended
Series A only
For a replacement
Series A only
Series A only Series B only
1756-L64 Not supported Not supported Not supported Only battery supported
1756-LSP Safety partner Not supported Not supported Not supported Only battery supported
  
¬ These controllers have nonvolatile memory and can be used without a battery.
T The 1756-L6x controllers have nonvolatile memory if you install a 1784-CF64 CompactFlash card. With nonvolatile memory, the controller can be used without a battery. If you do not use a battery, current tag data will be at the state they were when the nonvolatile memory was saved.