Catalogs > Automation Systems Catalog > Programmable Controllers > ControlLogix System > Controllers
Controllers
| Introduction | Environmentals and Certifications | Standard ControlLogix Controllers | ControlLogix-XT Controllers | GuardLogix Controllers | Redundant Controllers | Accessories—Controllers |
The ControlLogix controller supports controller redundancy. In a redundant controller system, you need:
- Two 1756 chassis each with the same:
- number of slots
- modules in the same slots
- number of slots
- Redundancy firmware revisions in each module
- Two additional ControlNet nodes outside the redundant chassis pair
- And one of the following:
- one 1756-RM module per chassis and one 1756-RMCx cable, or
- one 1757-SRM module per chassis and one 1757-SRCx cable
- one 1756-RM module per chassis and one 1756-RMCx cable, or
ControlLogix Redundancy Modules
Specifications [PDF]
| Cat. No. | Description | Controllers Supported | Communication Modules Supported |
| 1756-RM | ControlLogix redundancy module | two 1756-L61, 1756-L62, 1761-L63 controllers or one 1756-L64 controller |
seven, max (1756-CN2 series B, 1756-CN2R series B, or 1756-EN2T modules) |
| 1757-SRM | one 1756-L61, 1756-L62, 1756-L63, 1756-L64 controller | seven, max (1756-CNB series D or E, 1756-CNBR series D or E, 1756-ENBT, or 1756-EWEB modules) | |
Connector Cables
| Cat. No. | Description | Length |
| 1756-RMC1 | Cable, 1756-RM redundancy module | 1 m (3.28 ft) |
| 1756-RMC3 | 3 m (9.84 ft) | |
| 1756-RMC10 | 10 m (32.81 ft) | |
| 1757-SRC1 | Cable, 1757-SRM redundancy module | 1 m (3.28 ft |
| 1757-SRC3 | 3 m (9.84 ft) | |
| 1757-SRC10 | 10 m (32.81 ft) | |
| 1757-SRC50 | 50 m (164.04 ft) | |
| 1757-SRC100 | 100 m (328.08 ft) | |