MicroLogix 1400 System

Catalogs > Automation Systems Catalog > Programmable Controllers > MicroLogix 1400 System > 1762 MicroLogix Expansion I/O

1762 MicroLogix Expansion I/O

Introduction Environmentals and Certifications Digital I/O Modules Analog I/O Modules Specialty I/O Modules
Environmentals and Certifications

Environmental Specifications

  1762 MicroLogix Expansion I/O Modules
Operating Temperature -20…65 °C (-4…149 °F) (on selected modules)
Operating Humidity 5…95% noncondensing
Operating Altitude, Max. 2,000 m (6,561 ft)
Vibration, Operating 10…500 Hz, 5 g, 0.015 in peak-to-peak
Vibration, Relay Operation 2 g
Shock, Operating 30 g panel mounted, 20 g DIN-rail mounted
Shock, Relay Operation 7.5 g panel mounted, 5 g DIN rail mounted
Shock, Nonoperating 40 g panel mounted, 30 g DIN rail mounted
Dimensions (HxWxD), Approx. 90 x 40 x 87mm (3.543 x 1.575 x 3.425 in.)⋆ 
Radiated and Conducted Emissions EN50081-2 Class A
ESD Immunity (IEC 1000-4-2) 4 kV contact, 8 kV air, 4 kV indirect
Radiated RF Immunity (IEC 1000-4-3) 10V/m, 80…1000 MHz, 80% amplitude modulation, +900 MHz keyed carrier
EFT/B Immunity (IEC 1000-4-4) 2 kV, 5 kHz
Surge Transient Immunity (IEC 1000-4-5) 2 kV common mode, 1 kV differential mode
Conducted RF Immunity (IEC 1000-4-6) 10V, 0.15…80 MHz‡ 
⋆ Height including mounting tabs is 110 mm (4.33 in.).
‡ Conducted immunity frequency range may be 150 kHz…30 MHz if the radiated immunity frequency range is 30 MHz…1000 MHz.

Certifications

Certifications: C-UL certified (under CSA C22.2 No. 142), UL 508 Listed, CE compliant for all applicable directives.
Hazardous Environment Class: Class I, Division 2, Hazardous Location, Groups A, B, C, D (UL1604, C-UL under CSA C22.2 No. 213).

When product is marked. See the Product Certification link at www.ab.com for Declarations of Conformity, Certificates, and other certification details.