MicroLogix 1400 System

Catalogs > Automation Systems Catalog > Programmable Controllers > MicroLogix 1400 System > 1762 MicroLogix Expansion I/O

1762 MicroLogix Expansion I/O

Introduction Environmentals and Certifications Digital I/O Modules Analog I/O Modules Specialty I/O Modules
Digital I/O Modules

Digital Output Modules

Cat. No. Outputs Voltage Category Operating Voltage Range Continuous Current per Output, Max. Continuous Current per Module, Max. Off-State Leakage Current, Max. Bus Current Load, Max.
1762-OA8 8 (4 points/group) 100…240V AC 85…265V AC at 47…63 Hz 0.25 A at 55 °C (131°F)
0.5 A at 30 °C (86 °F)
2.0 A (1.0 A per common) at 55 °C (131 °F)
4.0 A (2.0 A per common) at 30 °C (86 °F)
2 mA at 132V AC
2.5 mA at 265V AC
115 mA at 5V DC (0.575 W)
1762-OB8 8 24V DC source 20…26.4V DC 0.5 A at 55 °C (131°F)
1.0 A at 30 °C (86 °F)
4.0 A at 55 °C (131°F)
8.0 A at 30 °C (86 °F)
1.0 mA 115 mA at 5V DC (0.575 W)
1762-OB16 16 24V DC source 20…26.4V DC 0.5 A at 55 °C (131°F)
1.0 A at 30 °C (86 °F)
4.0 A at 55 °C (131°F)
8.0 A at 30 °C (86 °F)
1 mA 175 mA at 5V DC (0.88 W
)
1762-OW8 8 (4 points/group) AC/DC N.O. contact 5…265V AC
5…125V DC
2.5 A⋆  16.0 A (8.0 A per common) 0 mA 80 mA at 5V DC (0.40 W)
90 mA at 24V DC (2.16 W)
1762-OW16 16 (8 points/group) AC/DC N.O. contact 5…265V AC
5…125V DC
2.5 A⋆  16.0 A (8.0 A per common) 0 mA 140 mA at 5V DC (0.7 W)‡ 
180 mA at 24V DC (4.32 W)‡ 
1762-OX6I 6 N.C., N.O. AC/DC Type C Relay 5…265V AC
5…125V DC
7.0 A⋆  30.0 A (7.0 A per common⋆ ) 0 mA 110 mA at 5V DC (0.55 W)
110 mA at 24V DC (2.64 W)
1762-OV32T 32 (16 points/group) 24V DC sink 10.2...26.4V DC 0.5 A at 60 °C (140 °F) 4.0 A (2.0 A per common) at 60 °C (140 °F) 0.1 mA at 26.4V DC 175 mA at 5V DC
1762-OB32T 32 (16 points/group) 24V DC source 10.2...26.4V DC 0.5 A at 60 °C (140 °F) 4.0 A (2.0 A per common) at 60 °C (140 °F) 0.1 mA at 26.4V DC 175 mA at 5V DC
⋆ See MicroLogix Programmable Controllers Family Selection Guide, publication 1761-SG001, for complete information on relay contact ratings.

Digital Input Modules

Cat. No. Inputs Voltage Category Operating Voltage Range On-State Current, Max. Impedance, Nom. Signal Delay, Max. Off-State Voltage and Current, Max. Bus Current Draw, Max.
1762-IA8 8 100/120V AC 79…132V AC at 47…63 Hz 16 mA at 132V AC, 63 Hz 12 kW at 50 Hz
10 KW at 60 Hz
On/Off: 20 ms 20V AC
2.5 mA
50 mA at 5V DC (0.25 W)
1762-IQ8 8 24V DC sink/source 10…26.4V DC at 55 °C (131 °F)
10…30V DC at 30 °C (86 °F)
12 mA at 30V DC 3 kW On/Off: 8 ms 5V DC
1.5 mA
50 mA at 5V DC (0.25 W)
1762-IQ16 16 (8 points/group) 24V DC sink/source 10…26.4V DC
10…30V DC⋆ ‡ 
12 mA at 30V DC 3 kW On/Off: 8 ms 5V DC
1.5 mA
70 mA at 5V DC (0.35 W)‡ 
1762-IQ32T 32 (8 points/group) 24V DC sink/source 10…26.4V DC
10…30V DC§ 
6.5 mA at 30.0V DC 4.7 kW On/Off: 8.0 ms 5V DC
1 mA
170 mA at 5V DC
⋆ See MicroLogix 1762-IQ16 DC Input Module Installation Instructions, publication 1762-IN010, for derating chart.
§ See MicroLogix 1762-IQ32T DC Input Module Installation Instructions, publication 1762-IN019, for derating chart.
‡ Only applicable for series B.

Digital Combination Modules

Cat. No. Inputs/Outputs Voltage Category Operating Voltage Range On-State Current, Max. Continuous Current per Output, Max. Off-State Voltage and Current, Max. Off-State Leakage Current, Max. Impedance, Nom. Signal Delay, Max. Bus Current, Max.
1762-IQ8OW6 8 inputs 24V DC sink/source 10…26.4V DC at 65 °C
10…30V DC at 30 °C
10 mA at 5V DC 5V DC
1.5 mA
3 kW On/Off: 8 ms 110 mA at 5V DC (0.25 W)
80 mA at 24V DC
6 outputs AC/DC N.O. contact 5…265V AC
5…125V DC
2.5 A (8.0 A per module, max.) 0 mA 110 mA at 5V DC (0.40 W)
80 mA at 24V DC (2.16 W)