Switched Mode

Product Overview


Click to enlarge - 1606-XLS120E_gray Click to enlarge - 1606-XLE_L
Click to enlarge - 03002010_1606_XLP30B_smlgray

Bulletin 1606 — Power Supplies★ 


Special Modules


Standards Compliance



★ Not all features apply to all power supplies; see individual power supply descriptions for specifics


Certifications

Click to enlarge - CE Symbol Click to enlarge - C UL US Listed_2008 Click to enlarge - cRUus_2008 Click to enlarge - 1606-4-3a

How to Select a Bulletin 1606 Power Supply

The Bulletin 1606 line of Power Supplies is designed with "reserve power" thereby eliminating the need to oversize your power supply to start high inrush loads.

Steps to size a Power Supply
1. Determine the "Average" continuous current of the load and the typical inrush current.
2. Select a power supply where the rated load is at/or below the current of the device and the Peak Current is less than the short-circuit rating of the power supply.

Notes:
  • ReservePower will deliver up to 25% additional current continuously.
  • PowerBoost will deliver 150% of rated current for up to 5 s.

  • Example:
    Application: Single Phase 120V input, 24V output, 5 A continuous current with 7.5 A inrush current
    Solution: 1606-XLS120E

    Output Characteristic for XLS120E (5 A) Power Supply


    Click to enlarge - 1606_output_graph IRATED: 5 A
    ISHORT CIRCUIT: >9 A
    IPOWER BOOST: 7.5 A

    Cat. No. IRATED [A] ISHORT CIRCUIT (25 °C) [A] IPOWER BOOST or
    IRESERVEPOWER [A]
    1606-XLS80E 3.3 5.2 5.4♣ 
    1606-XLS120E 5 9 7.5♣ 
    1606-XLS240E 10 21 15♣ 
    1606-XLS480E 20 30 30♣ 
    1606-XLS480E-3 20 29 30♣ 
    1606-XLSDNET4 3.8 4
    1606-XLSDNET8 8 7
    1606-XLE80E 3.3 5.5 3.6
    1606-XLE120E 5 11 6
    1606-XLE240E 10 16 12
     

    ♣  Products with ReservePower.
    ∆  Short circuit current values are temperature dependent for the selected product; i.e., the higher the ambient temperature, the lower the short circuit current.
    ◆  Hiccup Overload design.


    Quick Guide

    Bulletin 1606-(number from table) ♠  Power Supply Quick Guide

      15...40 W 50 W 60 W 72...80 W 90...100 W 120 W 180 W 240 W 480 W 720 W 960 W
    5...5.5V XLP15A
    XLP25A
    10...12V XLP30B
    12...15V 1-Ph XLP15B XLP50B XLP60BQ
    XLP60BQT
    XLP90B XL180B
    12...15 V 3-Ph XLE96B
    (+/-)12 and 15V XLP36C
    24...28V 1-Ph XLP15E
    XLP30E
    XLP30EQ
    XLP50E
    XLP50EZ
    XL60D
    XLP60EQ
    XLP60EQT
    XLS80E
    XLE80E
    XLP72E
    XLP95E
    XLP100E
    XLS120E
    XLS120EA
    XLE120E
    XLE120EC
    XLE120EE
    XLE120EN
    XLS240E
    XLS240EC
    XLE240E
    XLE240EP
    XLE240EE
    XLE240EN
    XLS480E
    XLS480EA
    XLS480EC
    XLS480EE
    XLS960EE
    24...28V 2-Ph/3-Ph XLP90E-2
    XLP100E-2
    XLE120E-2 XL240E-3C
    XLE240E-3
    XLS480E-3
    XLS480E-3C
    XL720E-3 XLE960DX-3N
    XLS960E-3
    36...43V XLS480G-3
    48...56V 1-Ph XLP50F XLP100F XLE240F
    XLS480F XLS960FE
    48...56V 3-Ph XLE240F-3 XLS480F-3 XLE960MX-3N
    XLS960F-3
    24V Redundant XL60DR XL120DR XL240DR
    DeviceNet XLEDNET3 XLSDNET4 XLSDNET8
      
    ♠ Example: For a 24...28 Volt, 3-Phase, 120 Watt power supply, the Cat. No. would be 1606-XL120E-3.

    Special Applications

    Bulletin Number NEC Class 2 ABS/GL Marine Hazardeous Location Rating, Class 1 Div 2 ODVA Requirements Conformal Coating ATEX
    1606-XLE XLE80E All XLE Power Supplies All XLE Power Supplies XLEDNET3 XLE120EC
    1606-XLP XLP15A
    XLP15B
    XLP15E
    XLP25A
    XLP30B
    XLP30E
    XLP36C
    XLP50B
    XLP50E
    XLP50EZ
    XLP50F
    XLP72E
    XLP90B
    XLP90E-2
    XLP95E
    XLP15A
    XLP15B
    XLP15E
    XLP25A
    XLP30E
    XLP36C
    XLP50E
    XLP50EZ
    XLP72E
    XLP90B
    XLP100E
    XLP100F
    XLPRED
    XLP15A
    XLP15B
    XLP15E
    XLP25A
    XLP30B
    XLP30E
    XLP50B
    XLP50E
    XLP50EZ
    XLP72E
    XLP90B
    XLP95E
    XLP100E
    XLPRED
    1606-XLS
    XLSDNET4 ALL XLS Power Supplies All XLS Power Supplies★  XLSDNET4
    XLSDNET8
    XLS240EC
    XLS480E-C
    XLS480E-3C
    XLS120EA
    XLS240EA
    XLS480EA
      
    ★  Cat. No. 1606-XLS240K does not have Hazardeous Location Rating.

    Catalog Number Explanation

    Important: The following cat. no. breakdown is for explanation purposes only. It is not a product configurator. Not all combinations of fields are valid product cat. nos. First, select the desired power supply using the Product Selection tables. Then, use this breakdown for verification and explanation only.

    1606 XLS    480    E      3
          a    b    c    d    e

    a
    Power Supply Type
    Code Description
    XLP Compact family
    XLS Performance family
    XLE Essential family

    b
    Rated Output Watts
    Code Description
    15 15 W
    25 25 W
    30 30 W
    36 36 W
    40 40 W
    50 50 W
    60 60 W
    72 72 W
    80 80 W
    90 90 W
    95 95 W
    100 100 W
    120 120 W
    180 180 W
    240 240 W
    480 480 W
    720 720 W
    960 960 W

    c
    Output Voltage
    Code Description
    A 5V DC
    B 10...12V DC or 12...15 V DC
    C Dual +/- 12 and 15V DC
    D 24V DC
    E 24...28V DC
    F 48...56V DC
    G 36...43V DC
    M 48V DC

    d
    Special Functions
    Code Description
      Can be left blank
    C Conformal coating
    R Redundancy module
    P Power factor correction
    Z Removeable Terminations
    X Semi-Regulated
    E Regional voltage;
    230V AC input only
    N Regional voltage;
    120V AC input only
    A ATEX

    e
    Multi-Phase Variations
    Code Description
      Can be left blank
    -2 Two phase
    -3 Three phase
    -3C Three phase, conformal coating
    -3H Three phase, input voltage 400V AC and 450...700V DC
    -3N Three phase, input voltage 480V AC
    -D 360...900V - DC Only

    Note: Special output signals are only available with the 960 W power supply.


    Product Selection

    Build a Catalog Number


    1606-XLS Performance — Single- and Three-Phase

    Single-Phase

    Input Voltage Output Power [W] Output Voltage Output Current [A] Input Circuit Protection∆  Steady State Input Current 120/230 [V AC] Parallel Operation DC OK Relay Cat. No.
    100...240V AC,
    110...300V DC
    80 24…28 3.3 6 A Slow Blow Fuse or
    Cat. No. 1489-A1C060
    1.41/0.82 Yes 1606-XLS80E
    120 24…28 5 1.10/0.62 Yes ü 1606-XLS120E
    120 24…28 5 1.10/0.62 Yes ü ★  1606-XLS120EA
    180 12…15 15 1.65/0.93 Yes ü 1606-XLS180B
    240 24…28 10 6 A Slow Blow Fuse or
    Cat. No. 1489-A1C060
    2.22/1.22 Yes ü 1606-XLS240E
    240 24…28 10 2.22/1.22 Yes ü ★  1606-XLS240EA
    240 24…28 10 2.22/1.22 Yes ü ◆  1606-XLS240EC
    240 48…56 5 2.22/1.22 Yes ü 1606-XLS240F
    240 28…32 8 2.22/1.22 Yes ü 1606-XLS240K
    480 24…28 20 10 A Slow Blow Fuse or
    Cat. No. 1489-A1C100
    4.56/2.48 Yes ü 1606-XLS480E
    480 24…28 20 4.56/2.48 Yes ü ◆  1606-XLS480EC
    480 24...48 20 4.56/2.48 Yes ü ★  1606-XLS480EA
    200...240V AC 480 48…56 10 4.56/2.48 Yes ü 1606-XLS480F
    100...240V AC,
    110...300V DC
    480 36…42 13.3 4.56/2.48 Yes ü 1606-XLS480G
    200...240V AC,
    220...300V DC
    960 24…28 40 —/4.6 Yes ü 1606-XLS960EE
      

    Three-Phase

    Input Voltage Output Power [W] Output Voltage Output Current [A] Input Circuit Protection Steady State Input Current
    400...480 [V AC]
    Parallel Operation DC OK Relay Cat. No.
    380…480V AC, 600V DC 480 24…28 20 6 A Slow Blow Fuse or
    Cat. No. 1489-A3C060
    3 x 0.65 Yes ü 1606-XLS480E-3
    380…480V AC, 600V DC 480 24…28 20 Yes ü ◆  1606-XLS480E-3C
    360…900V DC 480 24…28 20 3 x 0.85 Yes ü 1606-XLS480E-D
    380…480V AC, 600V DC 480 48…56 10 3 x 0.65 Yes ü 1606-XLS480F-3
    380…480V AC, 600V DC 480 36…42 13.3 Yes ü 1606-XLS480G-3
    380…480V AC, 600V DC 960 24…28 40 3 x 1.35 Yes ü 1606-XLS960E-3
    380…480V AC, 600V DC 960 48...54 20 Yes ü 1606-XLS960F-3
      

    ∆ Unit has internal (not accessible/replaceable) input fuse. Additional protection is not required if used on branch circuits £ UL test levels.
    Consult local codes and regulations for installation.
    ◆  The C suffix in the Cat. No. indicates that the product has conformal coating.
    ★  The A suffix in the Cat. No. indicates that the product carries the ATEX rating.


    1606-XLE Essential — Single-Phase

    Input Voltage Output Power [W] Output Voltage Output Current [A] Input Circuit Protection Steady State Input Current
    120/230 [V AC]
    Parallel Operation∇  DC OK Relay Cat. No.
    100…120/200…240V AC 80 24…28 3.3 10 A Slow Blow Fuse or
    Cat. No.
    1489-A1C100/20∆ 
    1.5/0.68 No 1606-XLE80E
    100…120/200…240V AC 120 24…28 5 2.34/1.23 No 1606-XLE120E
    100…120/200…240V AC 24…28 5 2.34/1.23 No ◆  1606-XLE120EC
    90…132V AC 24…28 5 1.23/— No 1606-XLE120EN
    180…264V AC 24…28 5 —/1.17 No 1606-XLE120EE
    100…120/200…240V AC 240 24…28 10 4.34/2.23 No 1606-XLE240E
    90…132V AC 24…28 10 3.73/— Yes 1606-XLE240EN
    180…264V AC 24…28 10 —/2.20 No 1606-XLE240EE
    100…120/200…240V AC 24…28 10 4.34/2.00 No 1606-XLE240EP
    100…120/200…240V AC 48…52 5 4.34/2.23 No 1606-XLE240F
      

    1606-XLE Essential — Three-Phase

    Input Voltage Output Power [W] Output Voltage Output Current [A] Input Circuit Protection Steady State Input Current
    400...480 [V AC]
    Parallel Operation∇  DC OK Relay Cat. No.
    380…480V AC, 600V DC 96 12...15 8 6 A Slow Blow Fuse or
    Cat. No. 1489-A3C060
    2 x 0.56 No 1606-XLE96B-2
    380…480V AC, 600V DC 120 24…28 5 3 x 0.60 1606-XLE120E-2
    380…480V AC, 600V DC 240 24…28 10 0.68 1606-XLE240E-3
    380…480V AC, 600V DC 240 48...56 5 3 x 0.60 1606-XLE240F-3
    480V AC 960 24 40 3 x 1.40 1606-XLE960DX-3N
    480V AC 960 48 20 3 x 1.40 1606-XLE960MX-3N
      

    1606-XLP Compact — Single- and Two-Phase

    Single-Phase

    Input Voltage Output Power [W] Output Voltage Output Current [A] Input Circuit Protection Steady State Input Current
    120/230 [V AC]
    Parallel Operation DC OK Relay Cat. No.
    100…240V AC, 85…375V DC 15 5…5.5 3 10 A Slow Blow Fuse or
    Cat. No. 1489-A1C100/ 15 A∆ 
    0.28/.017 Yes 1606-XLP15A
    12…15 1.3 0.28/.017 1606-XLP15B
    24…28 0.6 0.28/.017 1606-XLP15E
    25 5…5.5 5 0.60/0.30 Yes 1606-XLP25A
    30 10…12 3 0.60/0.25 Yes 1606-XLP30B
    24…28 1.3 0.60/0.35 1606-XLP30E
    0.54/0.30 1606-XLP30EQ
    36 +/- 12/15V 2.8 0.65/0.40 No 1606-XLP36C
    50 12…15 4.2 1.00/0.60 Yes 1606-XLP50B
    24…28 2.1 0.77/0.44 Yes 1606-XLP50E
    24…28 2.1 1.00/0.60 Yes 1606-XLP50EZ
    48…56 1 1.00/0.60 Yes 1606-XLP50F
    54 12...15 4.5 0.91/0.54 Yes 1606-XLP60BQ
    54 12...15 4.5 0.97/0.61 Yes 1606-XLP60BQT
    60 24...48 2.1 0.98/0.58 Yes 1606-XLP60EQ
    60 24...48 2.1 1.05/0.66 Yes 1606-XLP60EQT
    100…120/220…240V AC, 220…375V DC 72 24…28 3 1.60/0.80 Yes 1606-XLP72E
    90 12…15 7.5 1.90/0.90 Yes§  1606-XLP90B
    100…200/200…240V AC, 220…375V DC 95 24…28 3.9 2.00/0.95 No 1606-XLP95E
    100 24…28 4.2 2.10/1.00 Yes§  1606-XLP100E
    48…56 2.1 2.10/1.00 Yes§  1606-XLP100F
      

    Two-Phase

    Input Voltage Output Power [W] Output Voltage Output Current [A] Input Circuit Protection Steady State Input Current
    400...480 [V AC]
    Parallel Operation DC OK Relay Cat. No.
    380…480V AC 90 24…28 3.75 10 A Slow Blow Fuse or
    Cat. No. 1489-A1C100
    / 20 A∆ 
    2 x 0.36 No§  1606-XLP90E-2
    380…480V AC 100 24…28 4.2 2 x 0.40 Yes§  1606-XLP100E-2
      

    ∆ Unit has internal (not accessible/replaceable) input fuse. Additional protection is not required if used on branch circuits £ UL test levels.
    § Single/parallel operation (inclined characteristic) selectable (jumper). Consult local codes and regulations for installation.


    Bulletin 1606 Back-of-Panel Brackets

    Instead of snapping the power supply onto a DIN Rail, you can mount it to the back of the panel. This set consists of two steel brackets which replace the existing DIN Rail aluminum brackets at the back of the unit.

    Note: You need one set per unit.

    Description Cat. No.
    Back-of-panel bracket for XLS and XLE power supplies, below 20 A 1606-XLB
    Back-of-panel bracket for XLS and XLE power supplies, 20 A and above 1606-XLC
      

    1606 Special Modules

    Input Voltage Output Power [W] Output Voltage Output Current [A] Input Circuit Protection Steady State Input Current
    120/230 [V AC]
    Parallel Operation DC OK Relay Cat. No.
    18…36V DC 40 5.1 8 N/A N/A Yes 1606-XLDC40A
    14…32.4V DC 92 24 3.8 N/A N/A 1606-XLDC92D
    100…240V AC, 110…300V DC 91 24 3.8 6 A SLOW BLOW FUSE OR 1489-A1C060/20 A∆  1.02/0.48 Yes ü 1606-XLSDNET4
    100…240V AC, 110…300V DC 192 24 8 6 A SLOW BLOW FUSE OR 1489-A1C060/20 A∆  2.13/1.00 Yes ü 1606-XLSDNET8
    100…120/200…240V AC 80 24…28 3.3 10 A SLOW BLOW FUSE OR 1489-A1C100/20 A∆  1.50/0.68 No 1606-XLEDNET3
    100…120/200…240V AC, 160…375V DC 60 24 2.5 10 A SLOW BLOW FUSE OR 1489-A1C100/16 A∆  1.30/0.70 Yes§  ü 1606-XL60DR
    100…120/200…240V AC, 210…375V DC 120 5 10 A SLOW BLOW FUSE OR 1489-A1C100/16 A∆  2.60/1.40 Yes§  ü 1606-XL120DR
    100…120/200…240V AC, 240…375V DC 240 10 10 A SLOW BLOW FUSE OR 1489-A1C100/10 A∆  6.00/2.60 Yes§  ü 1606-XL240DR
    24V DC 720 Vin -.5V typ 30 N/A N/A‡  1606-XLRED20-30
    24V DC 960 Vin -.6V typ 40 N/A N/A♣  1606-XLRED40
    10…60V DC 384 Vin 1 -.9V typ 16◆  N/A N/A 1606-XLPRED
    10…60V DC 480 Vin 1 -.9V typ 20◆  N/A N/A 1606-XLSRED
    24...28 960 Vin 2.15 typ. 40 N/A N/A 1606-XLSRED40
    24...28 1920 Vin 2.7 typ. 80 N/A N/A 1606-XLSRED80
    24…60V DC 480 Vin 1 -.9V typ 20◆  N/A N/A ü 1606-XLERED
      

    1606 Special Modules with UPS

    Input Voltage Output Power [W] Output Voltage Output Current [A] Cat. No.
    22.5…30V DC 240 22.5 10 ♠  1606-XLS240-UPS
    22.5…30V DC 240 22.5 10 1606-XLS240-UPSC
    22.5...30V DC 240 12/22.5 5/10 1606-XLS240-UPSD
    22.5...30V DC 240 22.5 10 1606-XLS240-UPSE
    24…28.8V DC 480 22.5…27.8 20 1606-XLSBUFFER24
    48…56V DC 960 45…54 10 1606-XLSBUFFER48
      

    ‡  To be used alongside 20, 30, and 40 A power supplies.
    §  Single/parallel operation (inclined characteristic) selectable (jumper).
    ♣  To be used alongside 40 A power supplies (or smaller).
    ∆  Unit has internal (not accessible/replaceable) input fuse. Additional protection is not required if used on branch circuits £ UL test levels.
    ◆  See product specifications for proper use.
    ♠  Cat. No. 1606-XLS240-UPS is a charging module, used along side a power supply and a battery assembly. The battery assembly must be ordered separately. Order Cat. No. 1606-XLSBATASSY1 for 7 Ah/ 12V battery assembly or Cat No. 1606-XLSBATASSY2 for 26 Ah/ 12V battery assembly. Consult local codes and regulations for installation.


    Bulletin 1606 Special Module Accessories

    Description Cat. No.
    7 Ah/12V Battery Assembly with Bracket, for use with DC UPS 1606-XLSBATASSY1
    7 Ah/12V Battery 1606-XLSBAT1
    Battery bracket for 7 Ah/12V battery 1606-XLSBATBR1
    26 Ah/12V Battery Assembly with Bracket, for use with DC UPS 1606-XLSBATASSY2
    26 Ah/12V Battery 1606-XLSBAT2
    Battery bracket for 26 Ah/12V battery 1606-XLSBATBR2
      

    Specifications and Approximate Dimensions

    Bulletin 1606-XLS
      1606-XLS80E 1606-XLS120E
    1606-XLS120EA& 
    1606-XLS180B 1606-XLS240E
    1606-XLS240EA& 
    1606-XLS240EC♠ 
    Output Volts/Watts 24…28V/80 W 24…28V/120 W 12...15V/180 W 24…28V/240 W
    Input Voltage (47...63 Hz) 100…240V AC, 
    110...300V DC
    100…240V AC, 110...300V DC 100…240V AC, 110...300V DC 100…240V AC, 110...300V DC
    Operational Range 85…276V AC, 88…375V DC 85…264V AC, 88…360V DC 85…264V AC, 88…360V DC 85…276V AC, 88…375V DC
    Hold-up Time 27…174 ms 33…59 ms 32 ms 27 ms
    Rated Input Current 1.4 A (100V AC),
    0.82 A (240V AC)
    1.4 A (100V AC),
    0.65 A (240V AC)
    1.65 A (120V AC),
    0.93 A (230V AC)
    2.8 A (100V AC),
    1.2 A (240V AC)
    Efficiency typ. 90.0% typ. 92.7% typ. 91.5% typ. 91.8%
    Output Voltage 24…28V 24…28V 12...15V 24…28V
    Rated Output Current 3.4 A (@ 24V)
    3.0 A (@ 28V)
    5 A (@ 24V)
    4.5 A (@ 28V)
    15 A 10 A (@ 24V)
    9 A (@ 28V)
    ReservePower (typ. 4 s) 5.4 A (@ 24V)
    5.0 A (@ 28V)
    7.5 A (@ 24V)
    6.7 A (@ 28V)
    22.5 (@12V) 15 A (@ 24V)
    13.5 A (@ 28V)
    Ripple/Noise <100 mVPP <50 mVPP <50 mVPP <50 mVPP
    Operating Temperature
    Range (Tamb)
    -25...+70 °C >60 °C with derating
    Non-Operating Temperature Range -40...+85 °C
    MTBF∆  >650 000 hours >831 000 hours >577 000 hours >581 000 hours
    Dimensions (W x H x D) 32 x 124 x 102 mm 40 x 124 x 117 mm 60 x 124 x 117 mm 60 x 124 x 117 mm
    Weight 420 g 620 g 900 g 900 g
    Certifications/Standards★  1, 2, 3, 5, 6, 7, 9 1, 2, 3, 5, 6, 7, 8, 9
    Special Features Active PFC; Class 1 Div. 2; Semi F47, 9) ABS/GL/RINA (Marine)
      
    ★ 1) = CE, 2) = UL 508 (cULus LISTED), 3) = UL 1950 (cURus), 4) = CSA C22.2, No. 60950, 5) Safety standards = IEC/EN 60950, EN 50178, 6) EMC standards = EN 55011 (Class B), EN 55022 (Class B), EN 61000-6-2, 7) EMC standards = EN 61000-3-2 (A14), EN 50081-1, 8) ATEX, 9) GL/ABS
    ∆ MTBF determined by Siemens norm SN 29500 at full load current and 40 °C, 8) ATEX
    &  Indicates ATEX rating
    ♠  Indicates conformal coating

    Bulletin 1606-XLS
      1606-XLS480E
    1606-XLS480EA& 
    1606-XLS480EC♠ 
    1606-XLS480E-3
    1606-XLS480E-3C♠ 
    1606-XLS480F 1606-XLS480F-3 1606-XLS480G 1606-XLS480G-3
    Output Volts/Watts 24…28V/480 W 24…28V/480 W 48...56V/480 W 48...56V/480 W 36...42V/480 W 36...42V/480 W
    Input Voltage (47...63 Hz)
    100…240V AC /110...300V DC 380…480V AC, 600V DC 100…240V AC, 110...300V DC 380...480V AC 100…240V AC, 110...300V DC 380…480V AC, 600V DC
    Operational Range 85…276V AC, 88…375V DC 323…552V AC, 450…780V DC 85…276V AC, 88…375V DC 323...552 V AC 85…276V AC, 88…375V DC 323…552V AC, 450…780V DC
    Hold-up Time 32…51 ms 19 ms 32...51 ms 22 ms 32...51 ms 22 ms
    Rated Input Current 4.6 A (100V AC),
    2.5 A (240V AC)
    0.9 A (380V AC),
    0.65 A (480V AC)
    4.6 A (100V AC),
    2.5 A (240V AC)
    0.79 A (380V AC),
    0.65 A (480V AC)
    4.6 A (100V AC),
    2.5 A (240V AC)
    0.79 A (380V AC),
    0.65 A (480V AC)
    Efficiency typ. 92.4% typ. 94.8% typ. 92.4% typ. 95.4 % typ. 92.4% typ. 94.8%
    Output Voltage 24…28V 24…28V 24…28V 48...55V 36...42V 36...42V
    Rated Output Current 20 A (@ 24V)
    17 A (@ 28V)
    20 A (@ 24V)
    17.5 A (@ 28V)
    20 A (@ 24V)
    17 A (@ 28V)
    10 A (@ 48V) 13 A (@ 36V) 13.3 A (@ 36V)
    ReservePower (typ. 4 s) 30 A (@ 24V)
    26 A (@ 28V)
    30 A (@ 24V)
    26 A (@ 28V)
    30 A (@ 24V) 15 A (@ 48V) 20 A (@ 42V) 20 A (@ 42V)
    Ripple/Noise <100 mVPP <100 mVPP <100 mVPP <100 mVPP <100 mVPP <100 mVPP
    Operating Temperature
    Range (Tamb)
    -25...+70 °C
    >60 °C with derating
    Non-Operating Temperature Range -25...+70 °C
    >60 °C with derating
    MTBF∆  >469 000 hours >690 000 hours >469 000 hours >690 000 hours > 407 000 hours > 690 000 hours
    Dimensions (W x H x D) 84 x 124 x 127 mm 65 x 124 x 127 mm 84 x 124 x 127 mm 65 x 124 x 127 mm 82 x 124 x127 mm 65 x 124 x127 mm
    Weight 1200 g 870 g 1200 g 870 g 1200 g 870 g
    Certifications/Standards★  1, 2, 3, 5, 6, 7, 8, 9 1, 2, 3, 5, 6, 7, 9
    Special Features ABS/GL/RINA (Marine)
      
    ★ 1) = CE, 2) = UL 508 (cULus LISTED), 3) = UL 1950 (cURus), 4) = CSA C22.2, No. 60950, 5) Safety standards = IEC/EN 60950, EN 50178, 6) EMC standards = EN 55011 (Class B), EN 55022 (Class B), EN 61000-6-2, 7) EMC standards = EN 61000-3-2 (A14), EN 50081-1, 8) ATEX, 9) ABS/GL/RINA (Marine)
    ∆ MTBF determined by Siemens norm SN 29500 at full load current and 40 °C
    &  Indicates ATEX rating
    ♠  Indicates conformal coating

    Bulletin 1606-XLS
      1606-XLS960EE 1606-XLS960E-3 1606-XLS960F-3
    Output Volts/Watts 24…28V/960 W 24…28V/960 W 24…28V/960 W
    Input Voltage (47...63 Hz) 200...240V AC, 220...300V DC 380...480 V AC
    200...240V AC, 220...300V DC
    Operational Range 170...264V AC, 176...375V DC 380....480V AC, 600V DC 170...264V AC, 176...375V DC
    Hold-up Time 32 ms 20 ms 20 ms
    Rated Input Current 4.6 A 1.65 A 1.65 A
    Efficiency typ. 94.6% typ. 95.2% typ. 95.4%
    Output Voltage 24...28V 24...28V 48...54V
    Rated Output Current 40 A (@ 24V)
    34 A (@ 28V)
    40 A (@ 24V)
    34.3 A (@ 28V)
    20 A (@ 48V)
    17.8 A (@ 54V)
    ReservePower (typ. 4 s) 60 A (@ 24V)
    51 A (@ 28V)
    60 A (@ 24V)
    51 A (@ 28V)
    30 A (@ 48V)
    26.7 A (@ 54V)
    Ripple/Noise <100 mVPP <100 mVPP <100 mVPP
    Operating Temperature
    Range (Tamb)
    -25 °C...+70 °C
    Non-Operating Temperature Range -40 °C...+85 °C
    Dimensions (W x H x D) 125 x 124 x 127 mm 110 x 124 x 127 mm 125 x 124 x 127 mm
    Weight 1800 g 1500 g 1800 g
    Certifications/Standards★  1, 2, 3, 4, 5, 6, 7, 9
    Special Features Class 1, DIv. 2, ABS/GL/RINA (Marine)
      
    ★ 1) = CE, 2) = UL 508 (cULus LISTED), 3) = UL 1950 (cURus), 4) = CSA C22.2, No. 60950, 5) Safety standards = IEC/EN 60950, EN 50178, 6) EMC standards = EN 55011 (Class B), EN 55022 (Class B), EN 61000-6-2, 7) EMC standards = EN 61000-3-2 (A14), EN 50081-1, 9) ABS/GL/RINA (Marine)
    ∆ MTBF determined by Siemens norm SN 29500 at full load current and 40 °C

    Bulletin 1606-XLE
      1606-XLE80E 1606-XLE120E
    1606-XLE120EC♠ 
    1606-XLE120EE 1606-XLE120EN 1606-XLE240E 1606-XLE240EE 1606-XLE240EN 1606-XLE240EP 1606-XLE240F
    Output Volts/
    Watts
    24V...28V/
    80 W
    24V...28V/
    120 W
    24V...28V/
    120 W
    24V...28V/
    120 W
    24V...28V/
    240 W
    24V...28V/
    240 W
    24V...28V/
    240 W
    24V...28V/
    240 W
    48V...52V/
    240 W
    Input Voltage (47...63 Hz)
    [V AC]
    100...120/
    200...240
    100...120/
    200...240
    200...240 100...120 100...120/
    200...240
    200...240 100...120 100...120/200...240
    Operational Range
    [V AC]
    90...132/
    180...264
    90...132 180...264 90...132 90...132/
    180...264
    180...264 90...132 90...132/180...264
    Hold-up Time >60 ms (120V)
    >244 ms (240V)
    >80 ms (120V)
    >78 ms (240V)
    >80 ms (120V) >78 ms (240V) >46 ms (120V)
    >42 ms (240V)
    >45 ms (240V) >46 ms (120V) >46ms (120V)
    >42ms (240V)
    >46ms (120V)
    >42ms (240V)
    Rated Input Current 1.24 A (100V AC)
    0.68 A (240V AC)
    2.6 A (100V AC)
    1.3 A (240V AC)
    2.6 A 1.4 A 5 A
    (100V AC)
    2.5 A
    (240V AC)
    2.7 A 5 A <5.0 A (115V)/<2.3 A (230V) <1.3 A (115V)/<0.7 A (230V)
    Efficiency typ. 90% typ. 90% typ. 90% typ. 90.2% typ. 91% typ. 91.6 %
    typ. 90.8 % typ. 91% typ. 92%
    Output Voltage 24...28V 48...52V
    Rated Output Current 3.3 A @ 24V
    2.9 A @ 28V
    5 A @ 24V
    4.3 A @ 28V
    5 A @ 24V 5 A @ 24V 10 A @ 24V
    8.6 A @ 28V
    10 A @ 24V 10 A @ 24V 10 A 5 A @ 48V
    4.6 A @ 52V
    Ripple/Noise <50 mVPP
    Operating Temperature
    Range (Tamb)
    -25...+70 °C, >60 °C with derating
    Non-Operating Temperature Range -40...+85 °C
    MTBF∆  >700 000 hours
    Dimensions (W x H x D) 32 x 124 x 102 mm 32 x 124 x 117 mm 60 x 124 x 117 mm
    Weight 430 g 500 g 500 g 500 g 700 g 700 g 700 g 800 g 700 g
    Certifications/Standards★  1, 2, 3, 4, 5, 6, 7, 9  
    Special Features NEC Class 2
      
    ★ 1) = CE, 2) = UL 508 (cULus LISTED), 3) = UL 1950 (cURus), 4) = CSA C22.2, No. 60950, 5) Safety standards = IEC/EN 60950, EN 50178, 6) EMC standards = EN 55011 (Class B), EN 55022 (Class B), EN 61000-6-2, 7) EMC standards = EN 61000-3-2 (A14), EN 50081-1, 9) ABS/GL/RINA (Marine)
    ∆  MTBF determined by Siemens norm SN 29500 at full load current and 40 °C.
    ♠  Indicates conformal coating.

    Bulletin 1606-XLP
      1606-XLP15A 1606-XLP15B 1606-XLP15E 1606-XLP25A
    Output Volts/Watts 5...5.5V/15 W 12...15V/15 W 24...28V/15 W 5...5.5V/25 W
    Input Voltage (47...63 Hz) 100...240V AC wide range; 85...370V DC
    Operational Range 85...264V AC
    Hold-up Time >168 ms (230V AC)
    >45 ms (100V AC)
    >191 ms (230V AC)
    >46 ms (100V AC)
    >196 ms (230V AC)
    >47 ms (100V AC)
    >170 ms (230V AC)
    >19 ms (100V AC)
    Rated Input Current <0.28 A (100V AC)
    <0.17 A (196V AC)
    <0.5 A (100V AC)
    <0.35 A (196V AC)
    Efficiency typ. >77% typ. >83% typ. >88% typ. >80%
    Output Voltage 5...5.5V
    5.1V preset
    12...15V 24...28V 5...5.5V
    5.1V preset
    Rated Output Current 3 A 1.0...1.3 A 0.54...0.63 A 5 A (at 5.1V),
    4.5 A (at 5.5V)
    Ripple/Noise <50 mVpp <75 mVpp <50 mVpp <50 mVpp
    Operating Temperature
    Range (Tamb)
    -10...+70 °C, >60 °C: 0.4 W/K derating -10...+70 °C
    >60 °C: 0.5 W/K derating
    Non-Operating Temperature Range -40...+85 °C
    MTBF∆  2 686 000 hours 3 811 000 hours 4 369 000 hours 600 000 hours
    Dimensions (W x H x D) 22.5 x 75 x 91 mm 45 x 75 x 91 mm
    Weight 130 g 240 g
    Certifications/Standards★  1, 2, 4, 5, 7, 9
    Special Features NEC Class 2 power supply; ABS/GL/RINA (Marine); Class 1 Div. 2
      
    ★ 1) = CE, 2) = UL 508 (cULus LISTED), 3) = UL 1950 (cURus), 4) = CSA C22.2, No. 60950, 5) Safety standards = IEC/EN 60950, EN 50178, 6) EMC standards = EN 55011 (Class B), EN 55022 (Class B), EN 61000-6-2, 7) EMC standards = EN 61000-3-2 (A14), EN 50081-1, 9) ABS/GL/RINA (Marine)
    ∆ MTBF determined by Siemens norm SN 29500 at full load current and 40 °C

    Bulletin 1606-XLP
      1606-XLP30B 1606-XLP30E 1606-XLP30EQ 1606-XLP36C 1606-XLP50B
    Output Volts/Watts 10...12V/30 W 24...28V/30 W 24...28V/30 W ±12V/±15V/36 W 12...15V/50 W
    Input Voltage (47...63 Hz) 100...240V AC wide range; 85...375V DC
    Operational Range 85...264V AC
    Hold-up Time >170 ms (230V AC)
    >18 ms (100V AC)
    >190 ms (230V AC)
    >19 ms (100V AC)
    >141 ms (230V AC)
    >31 ms (100V AC)
    >180 ms (230V AC)
    >18 ms (100V AC)
    >170 ms (230V AC)
    >17 ms (100V AC)
    Rated Input Current <0.6 A (100V AC)
    <0.25 A (240V AC)
    <0.6 A (100V AC)
    <0.35 A (196V AC)
    <0.54 A (100V AC)
    <0.3 A (230V AC)
    <0.65 A (AC 100V AC)
    <0.4 A (AC 196V AC)
    <1.0 A (100V AC)
    <0.6 A (196V AC)
    Efficiency typ. 84% typ. 87.5% typ. 88.5% typ. 86% typ. 90%
    Output Voltage 10...12V
    12V preset (with jumper), 10...12V adjustable (without jumper)
    24...28V
    24.5V preset
    24...28V ±12V (without jumper),
    ±15V (with jumper)
    ±15V preset
    12...15V
    15V preset (with jumper) 12...15V adjustable (without jumper)
    Rated Output Current 3 A (@ 10V),
    2.5 A (@ 12V)
    1.3 A (@ 24.5V),
    1 A (@ 28V)
    1.3 A (@ 24V),
    1 A (@ 28V)
    0...2.8 A (@ +12V),
    0...1.4 A (@ -12V)
    0...2.4 A (@ +15V),
    0...1.4 A @ (-15V)
    4.2 A (@ 12V),
    3.4 A (@ 15V)
    Ripple/Noise <10 mVpp <50 mVpp <50 mVpp <50 mVpp <100mVpp
    Operating Temperature
    Range (Tamb)
    -10...+70 °C
    >60 °C: 0.6 W/K derating
    -10...+70 °C
    >60 °C: 0.5 W/K derating
    -10...+70 °C
    >60 °C: 0.8 W/K derating
    -10...+70 °C
    > 60 °C: 1 W/K derating
    -10...+70 °C
    >60 °C: 1 W/K derating
    Non-Operating Temperature Range -10...+70 °C
    >60 °C: 0.6 W/K derating
    -10...+70 °C
    >60 °C: 0.5 W/K derating
    -10...+70 °C
    >60 °C: 0.5 W/K derating
    -10...+70 °C
    > 60 °C: 1 W/K derating
    -10...+70 °C
    >60 °C: 1 W/K derating
    MTBF∆  appr. 650 000 hours 2 123 000 hours 600 000 hours appr. 600 000 hours
    Dimensions (W x H x D) 45 x 75 x 91 mm 45 x 75 x 91 mm 22.5 x 75 x 91 mm 45 x 75 x 91 mm 45 x 75 x 91 mm
    Weight 250 g 230 g 140 g 240 g 260 g
    Certifications/Standards★  1, 2, 4, 5, 7, 9
    Special Features NEC Class 2 power supply; Class 1 Div. 2, ABS/GL/RINA (Marine) NEC Class 2 power supply; Class 1 Div. 2; Semi F47, ABS/GL/RINA (Marine) NEC Class 2 power supply; Class 1 Div. 2; Semi F47, ABS/GL/RINA (Marine) Output voltage adjustable:
    DC ±12V without jumper or
    DC ±15V with jumper;
    NEC Class 2 power supply;
    Class 1 Div. 2;
    ABS/GL/RINA (Marine)
    Output voltage adjustable:
    DC 12...15V without jumper or
    DC 15V with jumper;
    NEC Class 2 power supply;
    Class 1 Div. 2
    ABS/GL/RINA (Marine)
      
    ★ 1) = CE, 2) = UL 508 (cULus LISTED), 3) = UL 1950 (cURus), 4) = CSA C22.2, No. 60950, 5) Safety standards = IEC/EN 60950, EN 50178, 6) EMC standards = EN 55011 (Class B), EN 55022 (Class B), EN 61000-6-2, 7) EMC standards = EN 61000-3-2 (A14), EN 50081-1, 9) ABS/GL/RINA (Marine)
    ∆ MTBF determined by Siemens norm SN 29500 at full load current and 40 °C

    Bulletin 1606-XLP
      1606-XLP50E 1606-XLP50EZ 1606-XLP50F 1606-XLP60EQ 1606-XLP60EQT
    Output Volts/Watts 24...28V/50 W 48...56V/50 W 24...28V/60 W
    Input Voltage (47...63 Hz) 100...240V AC wide range; 85...375V DC
    Operational Range 85...264V AC
    Hold-up Time >171 ms (230V AC)
    >17 ms (100V AC)
    >170 ms (230V AC)
    >17 ms (100V AC)
    >107 ms (230V AC)
    >24 ms (120V AC)
    Rated Input Current <1.0 A (100V AC)
    <0.6 A (196V AC)
    Efficiency typ. 88.5% typ. 90% typ. 88%
    Output Voltage 24...28V
    24.5V preset
    48...56V
    48V preset
    24...28V
    Rated Output Current 2.1 A (@ 24.5V),
    1.8 A (@ 28V)
    1.05 A (@ 48V),
    0.9 A (@ 56V)
    2.5 A (@ 24V),
    2.1 A (@ 28V)
    Ripple/Noise <50 mVpp <200 mVpp <50 mVpp
    Operating Temperature
    Range (Tamb)
    -10...+70 °C
    >60 °C: 1 W/K derating
    -40...+70 °C
    >60 °C: 1 W/K derating
    Non-Operating Temperature Range -40...+85 °C
    MTBF∆  appr. 600 000 hours > 1 292 000 h
    Dimensions (W x H x D) 45 x 75 x 91 mm
    Weight 240 g 250 g
    Certifications/Standards★  1, 2, 3, 4, 5, 6, 9 1, 2, 3, 4, 5, 6
    Special Features NEC Class 2 power supply;
    ABS/GL/RINA (Marine);
    Class 1 Div. 2;
    Semi F47
    Removeable Terminations;
    NEC Class 2 power supply;
    ABS/GL/RINA (Marine);
    Class 1 Div. 2
    NEC Class 2 power supply;
    ABS/GL/RINA (Marine)
    NEC Class 2 power supply
      
    ★ 1) = CE, 2) = UL 508 (cULus LISTED), 3) = UL 1950 (cURus), 4) = CSA C22.2, No. 60950, 5) Safety standards = IEC/EN 60950, EN 50178, 6) EMC standards = EN 55011 (Class B), EN 55022 (Class B), EN 61000-6-2, 7) EMC standards = EN 61000-3-2 (A14), EN 50081-1, 9)ABS/GL/RINA (Marine)
    ∆ MTBF determined by Siemens norm SN 29500 at full load current and 40 °C

    Bulletin 1606-XLP Specifications, continued
      1606-XLP60BQ 1606-XLP60BQT 1606-XLP72E 1606-XLP90B 1606-XLP90E-2
    Output Volts/Watts 12...15V/54 W 12...15V/54 W 24...28V/72 W 12...15V/90 W 24...28V/90 W
    Input Voltage (47...63 Hz) 100...240V 100...240V 100...120/220...240V AC manual select; 220...375V DC 100...120/220...240V AC; 220...375V DC 2Æ, 380...480V AC
    Operational Range 85...264V AC 85...264V AC 85...132/184...264V AC 323..552V AC
    Hold-up Time >113 ms (230V AC)
    >25 ms (120V AC)
    >113 ms (230V AC)
    >25 ms (120V AC)
    >40 ms (230V AC)
    >25 ms (100V AC)
    >40 ms (230V AC)
    >20 ms (196V AC, 100V AC)
    >52 ms (400V)
    >93 ms (480V)
    Rated Input Current <0.91 A (110V AC)
    <0.54 A (230V AC)
    <0.97 A (110V AC)
    <0.61 A (230V AC)
    <1.6 A (100V AC)
    <0.8 A (220V AC)
    <1.9 A <0.42 A (400V)
    <0.36 A (480V)
    Efficiency typ. 87.2 % typ. 87.6 % typ. 89% typ. 88.5% typ. 89%
    Output Voltage 12...15V 12...15V 24...28V
    24.5V preset (at 2.9 A)
    12...15V
    Preset at 12V
    24...28V
    Preset at 24.5V
    Rated Output Current 4.5 A (@ 12V),
    3.6 A (@ 15V)
    4.5 A (@ 12V),
    3.6 A (@ 15V)
    3 A (@ 24V),
    2.6 A (@ 28V)
    7.5 A (@ 12V),
    6 A (@ 15V)
    3.75 A (@ 24V),
    3.2 A (@ 28V)
    Ripple/Noise <50 mVpp <50 mVpp <50 mVpp <50 mVpp <50 mVpp
    Operating Temperature
    Range (Tamb)
    -10...+70 °C
    60...70 °C: 1.4 W/°C derating
    -40...+70 °C
    60...70 °C: 1.4 W/°C derating
    -10...+70 °C
    >60 °C: 1.5 W/K derating
    -10...+70 °C
    >60 °C: 1 W/K derating
    -10...+70 °C
    >60 °C: 2 W/K derating
    Non-Operating Temperature Range -40...+85 °C
    MTBF∆  appr. 600 000 hours appr. 500 000 hours appr. 500 000 hours
    Dimensions (W x H x D) 45 x 75 x 91 mm 45 x 75 x 91 mm 45 x 75 x 91 mm 73 x 75 x 103 mm 73 x 75 x 103 mm
    Weight 250 g 250 g 260 g 360 g 360 g
    Certifications/Standards★  1, 2, 3, 4, 5, 6 1, 2, 3, 4, 5, 6 1, 2, 3, 4, 5, 6, 9 1, 2, 3, 4, 5, 6, 7, 9 1, 2, 3, 4, 5, 6, 7, 9
    Special Features NEC Class 2 power supply NEC Class 2 power supply
    Operation down to -40 °C
    NEC Class 2 power supply;
    ABS/GL/RINA (Marine);
    Class 1 Div. 2
    NEC Class 2 power supply;
    ABS/GL/RINA (Marine);
    Class 1 Div. 2
    NEC Class 2 power supply;
    ABS/GL/RINA (Marine)
      
    ★ 1) = CE, 2) = UL 508 (cULus LISTED), 3) = UL 1950 (cURus), 4) = CSA C22.2, No. 60950, 5) Safety standards = IEC/EN 60950, EN 50178, 6) EMC standards = EN 55011 (Class B), EN 55022 (Class B), EN 61000-6-2, 7) EMC standards = EN 61000-3-2 (A14), EN 50081-1, 9)ABS/GL/RINA (Marine)
    ∆ MTBF determined by Siemens norm SN 29500 at full load current and 40 °C

    Bulletin 1606-XLP
      1606-XLP95E 1606-XLP100E 1606-XLP100F 1606-XLP100E-2
    Output Volts/Watts 24...28V/95 W 24...28V/100 W 48...56V/100 W 24...28V/100 W
    Input Voltage (47...63 Hz) 100...120/220...240V AC auto select; 220...375V DC 2Æ, 380...480V AC
    Operational Range 85...132/184...264V AC 323..552V AC
    Hold-up Time >40 ms (230V AC)
    >20 ms (100V AC)
    >48 ms (400V)
    >85 ms (480V)
    Rated Input Current <2.0 A (100V AC)
    <0.95 A (220V AC)
    <2.1 A (100V AC)
    <1.0 A (220V AC)
    <0.46 A (400V)
    <0.40 A (480V)
    Efficiency typ. 90% typ. 91% typ. 89%
    Output Voltage 24...28V
    24.5V preset
    48...56V
    48V preset
    24...28V
    Preset at 24.5V
    Rated Output Current 3.9 A (@ 24.5V),
    3.2 A (@ 28V)
    4.2 A (@ 24.5V),
    3.6 A (@ 28V)
    2.1 A (@ 48V),
    1.8 A (@ 56V)
    4.2 A (@ 24V),
    3.6 A (@ 28V)
    Power Boost
    Ripple/Noise <50 mVpp <50 mVpp <50 mVpp <50 mVpp
    Operating Temperature
    Range (Tamb)
    -10...+70 °C
    >60 °C: 2 W/K derating
    Non-Operating Temperature Range -40...+85 °C
    MTBF∆  appr. 500 000 hours
    Dimensions (W x H x D) 73 x 75 x 103 mm
    Weight 360 g
    Certifications/Standards★  1, 2, 3, 4, 5, 6, 7 1, 2, 3, 5, 6, 9 1, 2, 3, 5, 6, 9
    Special Features NEC Class 2 power supply;
    Class 1 Div. 2
    Single/parallel operation (inclined characteristic) select on front panel;
    ABS/GL/RINA (Marine);
    Class 1 Div. 2;
    Semi F47
    Single/parallel operation (inclined characteristic) select on front panel;
    ABS/GL/RINA (Marine)
      
    ★ 1) = CE, 2) = UL 508 (cULus LISTED), 3) = UL 1950 (cURus), 4) = CSA C22.2, No. 60950, 5) Safety standards = IEC/EN 60950, EN 50178, 6) EMC standards = EN 55011 (Class B), EN 55022 (Class B), EN 61000-6-2, 7) EMC standards = EN 61000-3-2 (A14), EN 50081-1, 9)ABS/GL/RINA (Marine)
    ∆ MTBF determined by Siemens norm SN 29500 at full load current and 40 °C

    "DC Ok" Output

    Function: Indicating whether the unit is operating properly. Output can directly energize a relay or a control light.
    Signaling: Output signal is at a "high" level (24V, current source) in normal operation (no overload, overheating, short circuit). When the output signal switches to "low" level (no power at output), Vout remains for 5 ms (nominal) at nominal load.
    Connection (signal common): Connection is made with respect to the "Signal GND" terminal (signal output).
    Important: Do not connect to the power output (terminals + and -).


    Permissible load: resistance - min. 300 W, e.g. 24V relay, control lights (LEDs need no series resistance), Evaluation logic.
    For 5V signal: In order to receive a 5V signal: switch a 5V Zener diode (0.5 W) and 1 kW resistance in parallel between this output and the "Signal GND" terminal.


    "Thermal Alarm" Output

    Function: Output gives warning shortly before and while overtemperature state occurs. Output can directly control a relay or a control light.
    Signaling: Output signal is at a "high" level (24V, current source) in normal operation (no overtemperature). At overtemperature, the output switches to "low". Only when the temperature in the unit increases further will the unit reduce its output current (power output).
    Connection and permissible load: same as for "DC ok" output.


    "Current Monitor" Output

    Function: Measuring the output current (power output). Output signal is proportional to the output current of the unit.
    Connection: Made with respect to the "Signal GND" terminal (signal output).
    Important: Do not connect to the power output (terminals + and -).
    Signaling:
    Voltage measuring: Voltage at signal output is 1V per 10 A output current (Ri(voltmeter) > 100 k ohm )
    Current measurement: Current at signal output is 1 mA per 10 A output current (Ri(ammeter) < 100 W)


    "Current Balance" In-/Output

    Function: Using these terminals, parallel operating units ensure an equal load sharing (active balancing). Balancing also works reliably with decoupling diodes at the power output (redundancy).

    Connection: Connect together "Current Balance" outputs of all units involved.
    Important: Signal common here is the - terminal of the power output, not the "Signal GND". Do not connect the "Signal GND" terminals to each other!


    "Signal GND" Terminal

    Function: Grounding terminal for all signal terminals (not for "Current Balance").
    Connection instructions: Do not connect this terminal with terminals + or - of the unit (not even over a load: risk of overload). Do not connect this terminal with terminals of other units (not even with the "Signal GND" terminal of another unit).
    Permissible load: Maximum current load: 0.3 A. Terminal is fused internally with a self-healing fuse (polyswitch).


    Click to enlarge - 1606-9-5


    Click to enlarge - 1606-9-6


    Bulletin 1606 Special Modules
      1606-XLDC40A 1606-XLDC92D 1606-XLSDNET4 1606-XLSDNET8 1606-XLEDNET3
    Output Volts/Watts 24V/40 W 24V/92 W 24V/91 W 24V/192 W 24V...28V/80 W
    Input Voltage (47...63 Hz) 18...36V DC 24V DC 100…240V AC; 110...300V DC AC 100…240V DC 110...300V 100...120V AC/200...240V AC
    Operational Range 16...40V DC 14...32.4V DC 85…264V AC 88…360V DC 85…276 V AC 88…375 V DC 90...132V AC/180...264V AC
    Hold-up Time 18...36V DC 18...36V DC 43 ms (120V AC)
    77 ms (240V AC)
    38 ms (120V AC)
    41 ms (240V AC)
    >60 ms (120V)
    >244 ms (240V)
    Rated Input Current <2.9 A <5.5 A 1.1 A (100V AC)
    0.5 A (240V AC)
    2.3 A (100V AC)
    1.0 A (240V AC)
    1.24 A (100V AC)
    0.68 A (240V AC)
    Efficiency typ. 82% typ. 90.3% typ. 92.4% typ. 92.7% typ. 90%
    Output Voltage 5.1V 24V 24V 24V 24...28V
    Rated Output Current 8 A 3.8 A 3.8 A 8 A 3.3 A @ 24V
    2.9 A @ 28V
    Ripple/Noise <50 mVPP <50 mVPP < 50 mVpp < 50 mVpp <50 mVPP
    Operating Temperature
    Range (Tamb)
    0...+70 °C
    >60 °C with derating
    -25...+70 °C
    >60 °C with derating
    -25...+70 °C
    >60 °C with derating
    -25...+70 °C
    >60 °C with derating
    -25...+70 °C, >60 °C with derating
    Non-Operating Temperature Range -25...+85 °C -40...+85 °C -40...+85 °C -25...+70 °C
    >60 °C with derating
    -40...+85 °C
    MTBF∆  > 510 000 hours - >581 000 hours >831 000 hours >700 000 hours
    Dimensions (W x H x D) 49 x 124 x 102 mm 32 x 124 x 102 mm 40 x 124 x 117 mm 60 x 124 x 117 mm 32 x 124 x 102 mm
    Weight 470 g 410 g 620 g 900 g 430 g
    Certifications/Standards★  1, 2, 3, 5, 6, 7 1, 2, 3, 5, 6, 7 1, 2, 3, 5, 6, 7 1, 2, 3, 4, 5, 6, 7
    Special Features NEC Class 2 power supply; Active PFC; ODVA Approved; Class 1 Div. 2; Semi F47 Active PFC; ODVA Approved; Class 1 Div. 2; Semi F47 NEC Class 2 power supply; ODVA Approved; Class 1 Div. 2; Semi F47
      
    ★ 1) = CE, 2) = UL 508 (cULus LISTED), 3) = UL 1950 (cURus), 4) = CSA C22.2, No. 60950, 5) Safety standards = IEC/EN 60950, EN 50178, 6) EMC standards = EN 55011 (Class B), EN 55022 (Class B), EN 61000-6-2, 7) EMC standards = EN 61000-3-2 (A14), EN 50081-1
    ∆ MTBF determined by Siemens norm SN 29500 at full load current and 40 °C

    Bulletin 1606 Redundant Power Supplies
      N+1 Redundancy N+1 Redundancy N+1 Redundancy
      1606-XL60DR 1606-XL120DR 1606-XL240DR
    Output Volts/Watts 24V/60 W 24V/120 W 24V/240 W
    Input Voltage (47...63 Hz) 100...120V/200...240V AC manual select;
    160...375V DC
    100...120/200...240V AC manual select;
    210...375V DC
    AC 100...120/200...240V manual select;
    DC 240...375V
    Operational Range 85...132/176...264V AC 85...132/176...264 V AC
    Hold-up Time >20 ms (AC 196V) >37 ms (AC 196V) >25 ms (AC 196V)
    Rated Input Current <1.3 A (115V)/<0.7 A (230V) <2.6 A (115V)/<1.4 A (230V) <6 A (115V)/<2.8 A (230V)
    Efficiency typ. 86.5% typ. 89% typ. 89%
    Output Voltage 24V 24V 24V
    Rated Output Current 2.5 A 5 A 10 A
    Power Boost 6 A 12 A
    Ripple/Noise <30 mVPP <30 mVPP <30 mVPP
    Operating Temperature
    Range (Tamb)
    -10...+70 °C
    >60 °C with derating
    -10...+70 °C
    >60 °C with derating
    0...+70 °C
    >60 °C with derating
    Non-Operating Temperature Range -10 °C...+70 °C
    >60 °C with derating
    -40...+85 °C -40...+85 °C
    MTBF∆  700 000 hours 480.000 hours 390.000 hours
    Dimensions (W x H x D) 49 x 124 x 102 mm 64 x 124 x 102 mm 120 x 124 x 102 mm
    Weight 470 g 620 g 980 g
    Certifications/Standards★  1, 2, 3, 5, 6 1, 2, 3, 5, 6, 7 1, 2, 3, 5, 6
    Special Features RDY relay contact;
    N+1 redundancy;
    plug connectors;
    NEC Class 2 power supply
    RDY relay contact;
    N+1 redundancy;
    plug connectors
    RDY relay contact;
    N+1 redundancy;
    plug connectors
      
    ★ 1) = CE, 2) = UL 508 (cULus LISTED), 3) = UL 1950 (cURus), 4) = CSA C22.2, No. 60950, 5) Safety standards = IEC/EN 60950, EN 50178, 6) EMC standards = EN 55011 (Class B), EN 55022 (Class B), EN 61000-6-2, 7) EMC standards = EN 61000-3-2 (A14), EN 50081-1
    ∆ MTBF determined by Siemens norm SN 29500 at full load current and 40 °C

    Bulletin 1606 Redundancy Module
      N+1 Redundancy N+1 Redundancy N+1 Redundancy N+1 Redundancy N+1 Redundancy N+1 Redundancy
      1606-XLRED20-30 1606-XLRED40 1606-XLPRED 1606-XLSRED 1606-XLERED 1606-XLSRED40 1606-XLSRED80
    Output Volts/Watts 30 A Dual redundancy module 40 A Single redundancy module 8 A Dual redundancy 10 A Dual redundancy 20 A Dual redundancy 40 A Dual redundancy
    Input Voltage (47...63 Hz) DC 24V (max. 35V) DC 10...60V DC 10...60V 24...28 V DC 24...28 V DC
    Operational Range 18...36 V DC 10...60V DC 10...60V DC 24...28 V DC 24...28 V DC
    Rated Input Current 20...30 A (max. 35 A) 0...40 A (max. 50 A) Single input: 8 A max.
    Dual input: 16 A max. total
    Single input: 10 A max.
    Dual input: 20 A max. total
    Single input: 20 A max.
    Dual input: 40 A max. total
    Single input: 40 A max.
    Dual input: 80 A max. total
    Output Voltage Vin -0.5V typ. Vin -0.6V typ. Vin -0.9V typ. Vin -0.9V typ. Vin -2.15V typ. Vin -2.7V typ.
    Rated Output Current 20...30 A (max. 35 A) 0...40 A (max. 50 A) 0...10 A 0...20 A 0...40 A 0...80 A
    Operating Temperature
    Range (Tamb)
    -10 °C...+70 °C -40 °C...+70 °C
    >60 °C with derating
    -25 °C...+70 °C
    >60 °C with derating
    -25 °C...+70 °C
    >60 °C with derating
    -25 °C...+70 °C
    >60 °C with derating
    Dimensions (W x H x D) 48 x 124 x 102 mm 48 x 124 x 117 mm 45 x 75 x 91 mm 32 x 124 x 102 mm 32 x 124 x 117 mm 36 x 124 x 127 mm 46 x 124 x 127 mm
    Weight 625 g 646 g 136 g 290 g 350 g 340 g 440 g
    Certifications/Standards★  1, 2, 3, 6 1, 2, 3, 6 1, 2, 3, 6 1, 2, 3, 6 1, 2, 3, 6
    Special Features Dual redundancy module for 2x35 A; N+1 redundancy Single redundancy module for 2.5-50 A; N+1 redundancy Redundancy for DC 10...60V applications;
    ABS/GL/RINA (Marine);
    Class 1 Div. 2
    Redundancy for DC 10...60V applications;
    Class 1 Div. 2
    Redundancy for DC 10...60V applications;
    Class 1 Div. 2;
    DC OK
    Redundancy for DC 24...28V applications;
    Class 1 Div. 2
    Redundancy for DC 24...28V applications;
    Class 1 Div. 2
      
    ★ 1) = CE, 2) = UL 508 (cULus LISTED), 3) = UL 1950 (cURus), 4) = CSA C22.2, No. 60950, 5) Safety standards = IEC/EN 60950, EN 50178, 6) EMC standards = EN 55011 (Class B), EN 55022 (Class B), EN 61000-6-2, 7) EMC standards = EN 61000-3-2 (A14), EN 50081-1
    ∆ MTBF determined by Siemens norm SN 29500 at full load current and 40 °C

    Bulletin 1606-XLS UPS
      UPS UPS UPS UPS
      1606-XLS240-UPS 1606-XLS240-UPSC 1606-XLS240-UPSD 1606-XLS240-UPSE
    Output Volts/Watts 22.5V...30V/240 W 22.25V/240 W 22.25V and
    12V/240 W
     
    Input Voltage (47...63 Hz) 24V DC (22.5...30V DC) 24V DC (22.5...30V DC) 24V DC (22.5...30V DC)  
    Rated Input Current Voltage
    stand-by mode/charging mode
    typ. 0.12 A/
    max. 1.3 A
    typ. 0.12 A/
    max. 1.3 A
    typ. 0.12 A/
    max. 1.3 A
    Operational Range 22.5...30V DC 22.5...30V DC 22.5...30V DC 22.5...30V DC
    Hold-up Time battery dependent
    Output Voltage 22.4V 22.25V 22.25V 22.25V
    Rated Output Current 10 A 10 A 10 A 10 A
    Power Boost 15 A 15 A 15 A 15 A
    Operating Temperature
    Range (Tamb)
    -25...+60 °C -25...+40 °C
    Non-Operating Temperature Range -40...+85 °C -20...+50 °C
    MTBF∆  886 000 hours 886 000 hours 788 000 hours 886 000 hours
    Dimensions (W x H x D) 49 x 124 x 117 123 x 124 x 119 49 x 124 x 117 49 x 124 x 117
    Weight 530 g 2850 g 650 g 545 g
    Certifications/Standards★  1, 2, 3, 5, 6
    Special Features Inhibit replacement battery buffering
      
    ★ 1) = CE, 2) = UL 508 (cULus LISTED), 3) = UL 1950 (cURus), 4) = CSA C22.2, No. 60950, 5) Safety standards = IEC/EN 60950, EN 50178, 6) EMC standards = EN 55011 (Class B), EN 55022 (Class B), EN 61000-6-2, 7) EMC standards = EN 61000-3-2 (A14), EN 50081-1
    ∆ MTBF determined by Siemens norm SN 29500 at full load current and 40 °C

    Bulletin 1606-XLSBUFFER
      Buffer Module Buffer Module
      1606-XLSBUFFER 24 1606-XLSBUFFER 48
    Output Volts 22.5V DC 45V DC
    Input Current 80 mA typ.
    600 mA max.
    40 mA typ.
    500 mA max.
    Hold-up Time 200 ms @ 20 A 100 ms @ 20 A
    Output Voltage Vin -1V: 22.5V fixed Vin -2V: 45V fixed
    Rated Output Current 20 A 20 A
    Operating Temperature
    Range (Tamb)
    -25...+70 °C
    Non-Operating Temperature Range -40...+85 °C
    Dimensions (W x H x D) 64 x 124 x 102 mm 64 x 124 x 102 mm
    Weight 740 g 740 g
    Certifications/Standards★  1, 2, 3, 5, 6
    Special Features Selectable buffered voltage; § 
      
    ★ 1) = CE, 2) = UL 508 (cULus LISTED), 3) = UL 1950 (cURus), 4) = CSA C22.2, No. 60950, 5) Safety standards = IEC/EN 60950, EN 50178, 6) EMC standards = EN 55011 (Class B), EN 55022 (Class B), EN 61000-6-2, 7) EMC standards = EN 61000-3-2 (A14), EN 50081-1
    §  Low inrush current

    Approximate Dimensions

    Approximate dimensions are shown in millimeters (in.) unless otherwise indicated. Dimensions are not to be used for manufacturing purposes.

    Cat. No. 1606-XLB, Back of Panel Mounting Bracket
    For use with Bulletin 1606-XLE and -XLS Power Supplies below 20 A.


    Click to enlarge - 1606-XLB_dims1


    Click to enlarge - 1606-XLB_dims2


    Cat. No. 1606-XLC, Back of Panel Mounting Bracket
    For use with Bulletin 1606-XLE and -XLS Power Supplies 20 A and above.


    Application Information

    1606-XL Redundancy Capabilities

    The 1606-XL family has two cost effective methods for providing redundancy to applications that are critical and can not risk failure.

    1606-XL60DR, XL120DR and XL240DR Redundant Power Supplies

    Click to enlarge - 1606-13-1 Click to enlarge - 1606-13-3

    The 1606-XL60DR, XL120DR and XL240DR are enhanced versions of the standard power supplies.


    1606-XLRED20-30 and 1606-XLRED40 Redundancy Modules

    Click to enlarge - 1606-13-2 Click to enlarge - 1606-13-4

    Extensive Diagnostic & Monitoring Functions

    Protective Features:


    Click to enlarge - 1606-XLS DC UPS 4


    A - Status LED (green):


    B - Diagnosis LED (yellow):


    C - Check wiring LED (red):


    D - Adjustor:


    E - Signal contacts:

    Ready (contact 1-2):


    Buffering (contact 3-4):


    Replace battery (contact 5-6):


    Inhibit input (contact 7&8):