Switched Mode
| Product Overview |
|
|
|
|
|
Bulletin 1606 — Power Supplies¬ T
- Quick mounting and connecting, innovative DIN-Rail mount, smallest in class
- UL Listed NEC Class 2; Class 1, Div. 2; Semi F47; ODVA Approved
- Low inrush current limiting
- PFC Active or Passive
- Wide range input; auto select input
- Superior overload design (continuous current, no hiccup)
- NEC Class 2 'Limited Power' options
- Selectable operating mode (single/parallel)
- Superior efficiency and temperature rating
Special Modules
- Brownout buffer, DC to DC converter, N+1 redundancy, DC UPS
Standards Compliance
- World-wide Certifications
- cULus, CE, C-Tick
- NEC Class 2
- SEMI F47 Compatible
- Class 1 Div. 2 (T3A)
- ABS/GL/RINA (Marine)
- cULus, CE, C-Tick
- SEMI F47 Compatible
- ABS/GL/RINA (Marine)
¬ Not all features apply to all power supplies; see individual power supply descriptions for specifics
T A more detailed list of performance specifications can be found at the Allen-Bradley web site
Certifications
|
|
|
|
|
How to Select a Bulletin 1606 Power Supply
The Bulletin 1606 line of Power Supplies is designed with "reserve power" thereby eliminating the need to oversize your power supply to start high inrush loads.
| Steps to size a Power Supply |
| 1. Determine the "Average" continuous current of the load and the typical inrush current. |
| 2. Select a power supply where the rated load is at/or below the current of the device and the Peak Current is less than the short-circuit rating of the power supply. |
| Notes: |
| Example: |
| Application: Single Phase 120V input, 24V output, 5 A continuous current @ 35 °C, with 7.5 A inrush current |
| Solution: 1606-XLS120E |
Output Characteristic for XLS120E (5 A) Power Supply
|
IRATED: 5 A ISHORT CIRCUIT: >9 A IPOWER BOOST: 7.5 A |
| Cat. No. | IRATED [A] | ISHORT CIRCUIT (25 °C) [A] | IPOWER BOOST or IRESERVEPOWER [A] |
| 1606-XLS80E | 3.3 | 5.2 | 5.4§ |
| 1606-XLS120E | 5 | 9 | 7.5§ |
| 1606-XLS240E | 10 | 21 | 15§ |
| 1606-XLS480E | 20 | 30 | 30§ |
| 1606-XLS480E-3 | 20 | 29 | 30§ |
| 1606-XLSDNET4 | 3.8 | 4 | — |
| 1606-XLSDNET8 | 8 | 7 | — |
| 1606-XLE80E | 3.3 | 5.5 | 3.6 |
| 1606-XLE120E | 5 | 11 | 6 |
| 1606-XLE240E | 10 | 16 | 12 |
| 1606-XLE240EP | 10 | 16 | 12 |
| 1606-XLE240F | 5 | 8.5 | 6 |
| 1606-XLP15E | 0.6 | 0.75 | — |
| 1606-XLP25A | 5 | 5 | — |
| 1606-XLP30B | 3 | 4 | — |
| 1606-XLP30E | 1.3 | 1.9 | — |
| 1606-XLP36C | 2.8 | 2 | — |
| 1606-XLP50B | 4.2 | 4.3 | — |
| 1606-XLP50E | 2.1 | 3.1 | — |
| 1606-XLP50EZ | 2.1 | 3.1 | — |
| 1606-XLP50F | 1 | 1.7 | — |
| 1606-XLP72E | 3 | 4.5 | — |
| Cat. No. | IRATED [A] | ISHORT CIRCUIT (25 °C) [A] | IPOWER BOOST or IRESERVEPOWER [A] |
| 1606-XLP90B | 7.5 | 8 | — |
| 1606-XLP90E-2 | 3.75 | 7 | — |
| 1606-XLP95E | 3.9 | 7 | — |
| 1606-XLP100E | 4.2 | 7.1 | — |
| 1606-XLP100E-2 | 4.2 | 8 | — |
| 1606-XLP100F | 2.1 | 3.6 | — |
| 1606-XL60D | 2.5 | 4.5§ | — |
| 1606-XL180B | 15 | 21§ | — |
| 1606-XL480EPT | 20 | 22 | 25 |
| 1606-XL480GP | 13.3 | 12 | 16.6 |
| 1606-XL480F | 10 | 24 | 12.5 |
| 1606-XL120E-3 | 5 | 11§ | 6 |
| 1606-XL240E-3 | 10 | 22§ | 12 |
| 1606-XL480E-3W | 20 | 25 | 25 |
| 1606-XL480F-3H | 10 | N/AØ | 12.5 |
| 1606-XL720E-3 | 30 | N/AØ | 33 |
| 1606-XL960E-3 | 40 | 44 | 45 |
| 1606-XL960E-3S | 40 | 44 | 45 |
| 1606-XL60DR | 2.5 | 4.5§ | — |
| 1606-XL120DR | 5 | 10§ | 6 |
| 1606-XL240DR | 10 | 18§ | 12 |
§ Products with ReservePower.
§ Short circuit current values are temperature dependent for the selected product; i.e., the higher the ambient temperature, the lower the short circuit current.
Ø Hiccup Overload design.
Quick Guide
| Build a Catalog Number |
Bulletin 1606-(number from table) z Power Supply Quick Guide
| 15...40 W | 50 W | 60 W | 72...80 W | 90...100 W | 120 W | 180 W | 240 W | 480 W | 720 W | 960 W | |
| 5...5.5V | XLP15A XLP25A |
— | — | — | — | — | — | — | — | — | — |
| 10...12V | XLP30B | — | — | — | — | — | — | — | — | — | — |
| 12...15V | XLP15B | XLP50B | — | — | XLP90B | — | XL180B | — | — | — | — |
| (+/-)12 and 15V | XLP36C | — | — | — | — | — | — | — | — | — | — |
| 24...28V 1-Ph | XLP15E XLP30E |
XLP50E XLP50EZ |
XL60D | XLS80E XLE80E XLP72E |
XLP95E XLP100E |
XLS120E XLE120E XLE120EC |
— | XLS240E XLS240EC XLE240E XLE240EP |
XLS480E XL480E XL480EP XL480EPT |
— | — |
| 24...28V 2-Ph/3-Ph | — | — | — | — | XLP90E-2 XLP100E-2 |
XL120E-3 | — | XL240E-3 XL240E-3C |
XLS480E-3 XLS480E-3C XL480E-3W |
XL720E-3 | XL960E-3 XL960E-3S |
| 36...43V | — | — | — | — | — | — | — | — | XL480GP | — | — |
| 48...56V 1-Ph | — | XLP50F | — | — | XLP100F | — | — | XLE240F XL240FP |
XL480F | — | — |
| 48...56V 3-Ph | — | — | — | — | — | — | — | — | XL480F-3H | — | — |
| 24V Redundant | — | — | XL60DR | — | — | XL120DR | — | XLPRED XL240DR |
XLSRED XLERED XLRED20-30 |
XLRED20-30 | XLRED40 |
| DeviceNet | — | — | — | — | XLSDNET4 | — | — | XLSDNET8 | — | — | — |
| z Example: For a 24...28 Volt, 3-Phase, 120 Watt power supply, the Catalog Number would be 1606-XL120E-3. | |||||||||||
Special Applications
NEC Class 2
- 1606-XLSDNET4
- 1606-XLP50E
- 1606-XLE72E
- 1606-XLP50EZ
- 1606-XLE80E
- 1606-XLP50F
- 1606-XLP15A
- 1606-XLP72E
- 1606-XLP15B
- 1606-XLP90B
- 1606-XLP15E
- 1606-XLP95E
- 1606-XLP25A
- 1606-XLP90E-2
- 1606-XLP30B
- 1606-XL60D
- 1606-XLP30E
- 1606-XLDNET4
- 1606-XLP36C
- 1606-XL60DR
- 1606-XLP50B
-
ABS/GL/RINA (Marine)
- 1606-XLP15A
- 1606-XLP50EZ
- 1606-XLP15B
- 1606-XLP72E
- 1606-XLP15E
- 1606-XLP90B
- 1606-XLP25A
- 1606-XLP100E
- 1606-XLP30E
- 1606-XLP100F
- 1606-XLP36C
- 1606-XLPRED
- 1606-XLP50E
-
Hazardous Location Rating, Class 1 Div. 2
- 1606-XLP15A
- 1606-XLP30B
- 1606-XLP15B
- 1606-XLP30E
- 1606-XLP15E
- 1606-XLP50B
- 1606-XLS80E
- 1606-XLP50E
- 1606-XLS120E
- 1606-XLP50EZ
- 1606-XLS240E
- 1606-XLP72E
- 1606-XLS480E
- 1606-XLP90B
- 1606-XLS480E-3
- 1606-XLP95E
- 1606-XLSDNET4
- 1606-XLP100E
- 1606-XLSDNET8
- 1606-XLPRED
- 1606-XLSRED
- 1606-XL240E
- 1606-XLP25A
- 1606-XL240EP
Semiconductor F47 Sag Immunity Requirements
| Product | Input Mains Voltage | Output Current Range |
| 1606-XLS80E | Full Range | Full Range |
| 1606-XLS120E | Full Range | Full Range |
| 1606-XLS240E | Full Range | Full Range |
| 1606-XLS480E | Full Range | Full Range |
| 1606-XLS480E-3 | Full Range | Full Range |
| 1606-XLSDNET4 | Full Range | Full Range |
| 1606-XLSDNET8 | Full Range | Full Range |
| 1606-XLP30E | AC 200V or higher | Full Range up to 1.3 A |
| 1606-XLP50E | AC 200V or higher | Full Range up to 2.1 A |
| 1606-XLP100E | AC 200V or higher | Full Range up to 4.2 A |
| 1606-XL60D | AC 120V or higher | Full Range up to 2.5 A |
| 1606-XL120D | AC 120V or higher | Full Range up to 5 A |
| 1606-XLDNET4 | AC 120V or higher | Up to 3 A |
| 1606-XL480E | AC 200V or higher | Full Range up to 20 A |
ODVA Requirements
- 1606-XLSDNET4
- 1606-XLSDNET8
Conformal Coating
- 1606-XLE120EC
- 1606-XL240E-3C
- 1606-XLS240EC
- 1606-XLS480E-3C
Cat. No. Explanation
Important: The following cat. no. breakdown is for explanation purposes only. It is not a product configurator. Not all combinations of fields are valid product cat. nos. First, select the desired power supply using the Product Selection tables. Then, use this breakdown for verification and explanation only.
| 1606 | | XLS | 480 | E | | 3 | ||||
| a | b | c | d | e |
| a | |
| Power Supply Type | |
| Code | Description |
| XLP | Compact family |
| XL | Standard family |
| XLS | Performance family |
| XLE | Essential family |
| b | |
| Rated Output Watts | |
| Code | Description |
| 15 | 15 W |
| 25 | 25 W |
| 30 | 30 W |
| 36 | 36 W |
| 40 | 40 W |
| 50 | 50 W |
| 60 | 60 W |
| 72 | 72 W |
| 80 | 80 W |
| 90 | 90 W |
| 95 | 95 W |
| 100 | 100 W |
| 120 | 120 W |
| 180 | 180 W |
| 240 | 240 W |
| 480 | 480 W |
| 720 | 720 W |
| 960 | 960 W |
| c | |
| Output Voltage | |
| Code | Description |
| A | 5V DC |
| B | 10...12V DC or 12...15 V DC |
| C | Dual +/- 12 and 15V DC |
| D | 24V DC |
| E | 24...28V DC |
| F | 48...56V DC |
| G | 36...43V DC |
| d | |
| Special Functions | |
| Code | Description |
| Can be left blank | |
| C | Conformal coating |
| R | Redundancy module |
| P | Power factor correction |
| L | Load sharing |
| T | Remote shutdown |
| Z | Removeable Terminations |
| X | Semi-Regulated |
| E | Regional voltage; 230V AC input only |
| N | Regional voltage; 120V AC input only |
| e | |
| Multi-Phase Variations | |
| Code | Description |
| Can be left blank | |
| -2 | Two phase |
| -3 | Three phase |
| -3C | Three phase, conformal coating |
| -3H | Three phase, input voltage 400V AC and 450...700V DC |
| -3W | Three phase, wide input range |
| -3S¬ | Three phase, special output signals |
¬ Special output signals are only available with the 960 W power supply.
Product Selection
| Build a Catalog Number |
1606-XLS Performance — Single- and Three-Phase
Single-Phase
| Input Voltage | Input Voltage Selector | Output Power [W] | Output Voltage | Output Current [A] | Input Circuit Protection§ | Inrush Current | Parallel Operation | Meets EN 61000-3-2 PFC Harmonics | DC OK Relay | Cat. No. |
| 100…240V AC, 110…300V DC | Auto | 80 | 24…28 | 3.3 | 6 A SLOW BLOW FUSE OR 1492-SPU1C060/20 A | <7.0 A | Yes | — | — | 1606-XLS80E |
| 100…240V AC, 110…300V DC | Auto | 120 | 24…28 | 5 | 6 A SLOW BLOW FUSE OR 1492-SPU1C060/20 A | <4.9 A | Yes | — | ü | 1606-XLS120E |
| 100…240V AC, 110…300V DC | Auto | 240 | 24…28 | 10 | 6 A SLOW BLOW FUSE OR 1492-SPU1C060/20 A | <5.0 A | Yes | — | ü | 1606-XLS240E |
| 100…240V AC, 110…300V DC | Auto | 480 | 24…28 | 20 | 6 A SLOW BLOW FUSE OR 1489-A1C060/20 A | <9.0 A | Yes | — | ü | 1606-XLS480E |
| 100…240V AC, 110…300V DC | Auto | 91 | 24 | 3.8 | 6 A SLOW BLOW FUSE OR 1489-A1C060/20 A | <4.9 A | No | Yes | ü | 1606-XLSDNET4 |
| 100…240V AC, 110…300V DC | Auto | 192 | 24 | 8 | 6 A SLOW BLOW FUSE OR 1489-A1C060/20 A | <7.6 A | Yes | No | ü | 1606-XLSDNET8 |
Three-Phase
| Input Voltage | Input Voltage Selector | Output Power [W] | Output Voltage | Output Current [A] | Input Circuit Protection | Inrush Current | Parallel Operation | Meets EN 61000-3-2 PFC Harmonics | DC OK Relay | Cat. No. |
| 380…480V AC, 600V DC | Auto | 480 | 24…28 | 20 | 6 A (X3) SLOW BLOW FUSE OR 1492-SP3C060 | <4.0 A | Yes | — | ü | 1606-XLS480E-3 |
§ Unit has internal (not accessible/replaceable) input fuse. Additional protection is not required if used on branch circuits £ UL test levels.
Consult local codes and regulations for installation.
1606-XLE Essential — Single-Phase
| Input Voltage | Input Voltage Selector | Output Power [W] | Output Voltage | Output Current [A] | Input Circuit Protection | Inrush Current | Parallel Operationª | Meets EN 61000-3-2 PFC Harmonics | DC OK Relay | Cat. No. |
| 100…120/200…240V AC | Auto | 80 | 24…28 | 3.3 | 10 A SLOW BLOW FUSE OR 1489-A1C100/20 A§ | <3 A | No | Yes | — | 1606-XLE80E |
| 100…120/200…240V AC | 120 | 24…28 | 5 | 10 A SLOW BLOW FUSE OR 1489-A1C100/20 A§ | <3 A | No | — | — | 1606-XLE120E | |
| 90…132V AC | 24…28 | 5 | 10 A SLOW BLOW FUSE OR 1489-A1C100/20 A§ | <3 A | Yes | — | — | 1606-XLE120EN | ||
| 180…264V AC | 24…28 | 5 | 10 A SLOW BLOW FUSE OR 1489-A1C100/20 A§ | <3 A | No | — | — | 1606-XLE120EE | ||
| 100…120/200…240V AC | 240 | 24…28 | 10 | 10 A SLOW BLOW FUSE OR 1489-A1C100/20 A§ | <3 A | No | — | — | 1606-XLE240E | |
| 90…132V AC | 24…28 | 10 | 10 A SLOW BLOW FUSE OR 1489-A1C100/20 A§ | <3 A | Yes | — | — | 1606-XLE240EN | ||
| 180…264V AC | 24…28 | 10 | 10 A SLOW BLOW FUSE OR 1489-A1C100/20 A§ | <3 A | No | — | — | 1606-XLE240EE | ||
| 100…120/200…240V AC | 24…28 | 10 | 10 A SLOW BLOW FUSE OR 1489-A1C100/20 A§ | <3 A | No | — | — | 1606-XLE240EP | ||
| 100…120/200…240V AC | 48…52 | 5 | 10 A SLOW BLOW FUSE OR 1489-A1C100/20 A§ | <3 A | No | — | — | 1606-XLE240F | ||
1606-XLP Compact — Single- and Two-Phase
Single-Phase
| Input Voltage | Input Voltage Selector | Output Power [W] | Output Voltage | Output Current [A] | Input Circuit Protection | Inrush Current | Parallel Operation | Meets EN 61000-3-2 PFC Harmonics | DC OK Relay | Cat. No. |
| 100…240V AC, 85…375V DC | Auto | 15 | 5…5.5 | 3 | 10 A SLOW BLOW FUSE OR 1489-A1C100/15 A§ | <11 A | Yes | NA | — | 1606-XLP15A |
| 12…15 | 1.3 | — | 1606-XLP15B | |||||||
| 24…28 | 0.6 | — | 1606-XLP15E | |||||||
| 100…240V AC, 85…375V DC | Auto | 25 | 5…5.5 | 5 | 10 A SLOW BLOW FUSE OR 1489-A1C100/15 A§ | <18 A | Yes | NA | — | 1606-XLP25A |
| 100…240V AC, 85…375V DC | Auto | 30 | 10…12 | 3 | 10 A SLOW BLOW FUSE OR 1489-A1C100/15 A§ | <18 A | Yes | NA | — | 1606-XLP30B |
| 24…28 | 1.3 | 1606-XLP30E | ||||||||
| 100…240V AC, 85…375V DC | Auto | 36 | +/- 12/15V | 2.8 | 10 A SLOW BLOW FUSE OR 1489-A1C100/15 A§ | <18 A | No | NA | — | 1606-XLP36C |
| 100…240V AC, 85…375V DC | Auto | 50 | 12…15 | 4.2 | 10 A SLOW BLOW FUSE OR 1489-A1C100/15 A§ | <18 A | Yes | NA | — | 1606-XLP50B |
| 24…28 | 2.1 | ü | 1606-XLP50E | |||||||
| 24…28 | 2.1 | ü | 1606-XLP50EZ | |||||||
| 48…56 | 1 | — | 1606-XLP50F | |||||||
| 100…120/220…240V AC, 220…375V DC | Man. | 72 | 24…28 | 3 | 10 A SLOW BLOW FUSE OR 1489-A1C100/15 A§ | <30 A | Yes | NA | — | 1606-XLP72E |
| 100…120/220…240V AC, 220…375V DC | Auto | 90 | 12…15 | 7.5 | 10 A SLOW BLOW FUSE OR 1489-A1C100/15 A§ | <30 A | Yes | Yes | — | 1606-XLP90B |
| 100…200/200…240V AC, 220…375V DC | Auto | 95 | 24…28 | 3.9 | 10 A SLOW BLOW FUSE OR 1489-A1C100/15 A§ | <30 A | No | Yes | — | 1606-XLP95E |
| 100…200/200…240V AC, 220…375V DC | Auto | 100 | 24…28 | 4.2 | 10 A SLOW BLOW FUSE OR 1489-A1C100/15 A§ | <30 A | Yes | Yes | — | 1606-XLP100E |
| 100…200/200…240V AC, 220…375V DC | Auto | 48…56 | 2.1 | 10 A SLOW BLOW FUSE OR 1489-A1C100/15 A§ | <30 A | Yes | Yes | — | 1606-XLP100F | |
Two-Phase
| Input Voltage | Input Voltage Selector | Output Power [W] | Output Voltage | Output Current [A] | Input Circuit Protection | Inrush Current | Parallel Operation | Meets EN 61000-3-2 PFC Harmonics | DC OK Relay | Cat. No. |
| 380…480V AC | — | 90 | 24…28 | 3.75 | 10 A (X2) SLOW BLOW FUSE OR 1489-A2C100/20 A§ | <35 A | No | — | — | 1606-XLP90E-2 |
| 380…480V AC | — | 100 | 24…28 | 4.2 | 10 A (X2) SLOW BLOW FUSE OR 1489-A2C100/20 A§ | <35 A | Yes | — | — | 1606-XLP100E-2 |
§ Unit has internal (not accessible/replaceable) input fuse. Additional protection is not required if used on branch circuits £ UL test levels.
ª Parallel use for 1 + 1 redundancy only.
Single/parallel operation (inclined characteristic) selectable (jumper).
Consult local codes and regulations for installation.
1606-XL Standard — Single- and Three-Phase
Single-Phase
| Input Voltage | Input Voltage Selector | Output Power [W] | Output Voltage | Output Current [A] | Input Circuit Protection | Inrush Current | Parallel Operation | Meets EN 61000-3-2 PFC Harmonics | DC OK Relay | Cat. No. |
| 100…120/200…240V AC, 160…375V DC | Man. | 60 | 24 | 2.5 | 10 A SLOW BLOW FUSE OR 1489-A1C100/16 A§ | <18 A | Yes | — | — | 1606-XL60D |
| 100…200/200…240V AC, 240…375V DC | Man. | 180 | 12…15 | 15 | 10 A SLOW BLOW FUSE OR 1489-A1C100/10 A§ | <21 A | Yes | — | — | 1606-XL180B |
| 200…240V AC, 270…370V DC | — | 480 | 24…28 | 20 | 10 A SLOW BLOW FUSE OR 1489-A1C100/16 A | <23 A | Yes | — | — | 1606-XL480E |
| 100…120/200…240V AC | Auto | 24…28 | 20 | 10 A SLOW BLOW FUSE OR 1489-A1C100 | <18 A @ 25°C | Yes | — | — | 1606-XL480EP | |
| 100…120/200…240V AC | Auto | 24…28 | 20 | 10 A SLOW BLOW FUSE OR 1489-A1C100 | <18 A @ 25°C | Yes | — | — | 1606-XL480EPT | |
| 100…120/200…240V AC | Auto | 36…43 | 13.3 | 10 A SLOW BLOW FUSE OR 1489-A1C100 | <18 A @ 25°C | Yes | — | — | 1606-XL480GP | |
| 100…120/200…240V AC | Auto | 48…56 | 10 | 10 A SLOW BLOW FUSE OR 1489-A1C100 | <18 A @ 25°C | Yes | — | — | 1606-XL480F | |
Three-Phase
| Input Voltage | Output Power [W] | Output Voltage | Output Current [A] | Input Circuit Protection | Inrush Current | Parallel Operation | Meets EN 61000-3-2 PFC Harmonics | DC OK Relay | Cat. No. |
| 400…500V AC, 450…820V DC | 120 | 24…28 | 5 | 10 A (X3) SLOW BLOW FUSE OR 1492-SP3C100 | <25 A | Yes | — | — | 1606-XL120E-3 |
| 400…500V AC, 450…820V DC | 240 | 24…28 | 10 | 6 A (X3) SLOW BLOW FUSE OR 1492-SP3C060/15 A§ | <17 A | Yes | — | — | 1606-XL240E-3 |
| 400…500V AC, 450…820V DC | 480 | 24…28 | 20 | 6 A (X3) SLOW BLOW FUSE OR 1492-SP3C060/16 A§ | <7 A | Yes | — | — | 1606-XL480E-3W |
| 400V AC, 450…700V DC | 48…56 | 10 | 10 A (X3) SLOW BLOW FUSE OR 1492-SP3C100 | <15 A | 1606-XL480F-3H | ||||
| 400…500V AC, 450…820V DC | 720 | 24…28 | 30 | 10 A (X3) SLOW BLOW FUSE OR 1492-SP3C100 | <17 A | Yes | — | — | 1606-XL720E-3 |
| 400…500V AC | 960 | 24…28 | 40 | 10 A (X3) SLOW BLOW FUSE OR 1492-SP3C100 | <30 A | Yes | — | — | 1606-XL960E-3 |
| Active current sharing | z | 1606-XL960E-3S | |||||||
Single/parallel operation (inclined characteristic) selectable (jumper).
§ Unit has internal (not accessible/replaceable) input fuse. Additional protection is not required if used on branch circuits £ UL test levels.
z DC OK output is provided through a 24V DC signal.
Consult local codes and regulations for installation.
1606 Special Modules
| Input Voltage | Input Voltage Selector | Output Power [W] | Output Voltage | Output Current [A] | Input Circuit Protection | Inrush Current | Parallel Operation | Meets EN 61000-3-2 PFC Harmonics | DC OK Relay | Cat. No. |
| 18…36V DC | — | 40 | 5.1 | 8 | N/A | <5 A | Yes | NA | — | 1606-XLDC40A |
| 100…240V AC, 110…300V DC | Auto | 91 | 24 | 3.8 | 6 A SLOW BLOW FUSE OR 1489-A1C060/20 A§ | <4.9 A | No | Yes | ü | 1606-XLSDNET4 |
| 100…240V AC, 110…300V DC | Auto | 192 | 24 | 8 | 6 A SLOW BLOW FUSE OR 1489-A1C060/20 A§ | <7.6 A | Yes | No | ü | 1606-XLSDNET8 |
| 100…120/200…240V AC, 160…375V DC | Man. | 60 | 24 | 2.5 | 10 A SLOW BLOW FUSE OR 1489-A1C100/16 A§ | <18 A | Yes | NA | ü | 1606-XL60DR |
| 100…120/200…240V AC, 210…375V DC | Man. | 120 | 5 | 10 A SLOW BLOW FUSE OR 1489-A1C100/16 A§ | <11 A | Yes | Yes | ü | 1606-XL120DR | |
| 100…120/200…240V AC, 240…375V DC | Man. | 240 | 10 | 10 A SLOW BLOW FUSE OR 1489-A1C100/10 A§ | <21 A | Yes | No | ü | 1606-XL240DR | |
| 24V DC | — | 720 | Vin -.5V typ | 30 | N/A | N/AT | — | NA | — | 1606-XLRED20-30 |
| 24V DC | — | 960 | Vin -.6V typ | 40 | N/A | N/A§ | — | NA | — | 1606-XLRED40 |
| 10…60V DC | — | 384 | Vin 1 -.9V typ | 16Ø | N/A | N/A | — | NA | — | 1606-XLPRED |
| 10…60V DC | — | 480 | Vin 1 -.9V typ | 20Ø | N/A | N/A | — | — | — | 1606-XLSRED |
| 24…60V DC | — | 480 | Vin 1 -.9V typ | 20Ø | N/A | N/A | — | — | — | 1606-XLERED |
| 100…120/200…240V AC | Auto | 120 | 24…28 | 5 | 10 A SLOW BLOW FUSE OR 1489-A1C100/20 A§ | <3 A | Yes | — | — | 1606-XLE120EC |
| 100…240V AC, 110…300V DC | Auto | 240 | 24…28 | 10 | 6 A SLOW BLOW FUSE OR 1489-A1C060/20 A§ | <4 A | Yes | — | ü | 1606-XLS240EC |
| 400…500V AC, 450…820V DC | — | 240 | 24…28 | 10 | 6 A (X3) SLOW BLOW FUSE OR 1492-SP3C060/15 A§ | <3 A | Yes | — | — | 1606-XL240E-3C |
| 380…480V AC, 600V DC | Auto | 480 | 24…28 | 20 | 6 A (X3) SLOW BLOW FUSE OR 1492-SP3C060 | <15 A | Yes | — | ü | 1606-XLS480E-3C |
1606 Special Modules with UPS
| Input Voltage | Input Voltage Selector | Output Power [W] | Output Voltage | Output Current [A] | Input Circuit Protection | Inrush Current | Parallel Operation | Meets EN 61000-3-2 PFC Harmonics | DC OK Relay | Cat. No. | |
| 22.5…30V DC | — | 240 | 22.5 | 10 | N/A | — | — | — | — | z | 1606-XLS240-UPS |
| 24…28.8V DC | — | 480 | 23…27.8 | 20 | N/A | — | — | NA | — | 1606-XLBUFFER | |
T To be used alongside 20, 30, and 40 A power supplies.
Single/parallel operation (inclined characteristic) selectable (jumper).
§ To be used alongside 40 A power supplies (or smaller).
§ Unit has internal (not accessible/replaceable) input fuse. Additional protection is not required if used on branch circuits £ UL test levels.
Ø See product specifications for proper use.
z The 1606-XLS240-UPS is a charging module, used along side a power supply and a battery assembly, which must be ordered separately. (See Accessories below.)
Consult local codes and regulations for installation.
1606 Accessories
| Description | Cat. No. |
| Back-of-panel bracket for XL | 1606-XLA |
| Back-of-panel bracket for XLS or XLE | 1606-XLB |
| 7 Ah/12V battery assembly with bracket, for use with DC UPS | 1606-XLSBATASSY1 |
| 7 Ah/12V battery | 1606-XLSBAT1 |
| Battery bracket for 7 Ah/12V battery | 1606-XLSBATBR1 |
| 26 Ah/12V battery assembly with bracket, for use with DC UPS | 1606-XLSBATASSY2 |
| 26 Ah/12V battery | 1606-XLSBAT2 |
| Battery bracket for 26 Ah/12V battery | 1606-XLSBATBR2 |
Circuit Protection Suggestions
If you intend to protect the primary side of the power supply with a fuse or a circuit breaker, this section can provide guidance on the proper Allen-Bradley product to use. In order to meet local requirements, please consult local codes and regulations for proper installation.
| Power Supply Type¬ | Recommended Fuse | Supplementary Protector |
| XL480E-3W | 6 A (x3) Slow acting fuse (HBC) | 1492-SP3C060 |
| XL120E-3, XL240E-3, XL480F-3H, XL480E-3, XL720E-3, XL960E-3, XL960E-3S | 10 A (x3) Slow acting fuse (HBC) | 1492-SP3C100 |
| XL60D, XL60DR, XL120D, XL120DR, XL240E, XL240EP, XL240DR, XL480E, XLDNET8, XLDNET4 | 10 A Slow acting fuse (HBC) | 1492-SPU1C100 |
| XL480EPT, XL480F, XL480GP, XL480EP | 15 A Slow acting fuse (HBC) | 1492-SPU1C150T |
| ¬ Products not listed have an internal input fuse. No additional product protection is required. | ||
| T For European applications, 1492-SP1C160 is recommended. | ||
Specifications
1606-XLS Performance Specifications
¬ 1) = CE, 2) = UL 508 (cULus LISTED), 3) = UL 1950 (cURus), 5) Safety standards = IEC/EN 60950, EN 50178, 6) EMC standards = EN 55011 (Class B), EN 55022 (Class B), EN 61000-6-2, 7) EMC standards = EN 61000-3-2 (A14), EN 50081-1
§ MTBF determined by Siemens norm SN 29500 at full load current and 40 °C
z Because these catalog numbers end with "C", it indicates these devices have conformal coating.
1606-XLE
| 1606-XLE80E | 1606-XLE120Ev and 1606-XLE120ECz |
1606-XLE240Ev | 1606-XLE240EP | 1606-XLE240F | |
| Output Volts/Watts | 24V...28V/80 W | 24V...28V/120 W | 24V...28V/240 W | 24V...28V/240 W | 48V...52V/240 W |
| Input Voltage (47...63 Hz) | 100...120V AC/200...240V AC | ||||
| Operational Range | 90...132V AC/180...264V AC | ||||
| Hold-up Time | >60 ms (120V) >244 ms (240V) |
>80 ms (120V) >78 ms (240V) |
>46 ms (120V) >42 ms (240V) |
||
| Rated Input Current | 20 A (100V AC) 45 A (240V AC) |
2.6 A (100V AC) 1.3 A (240V AC) |
5 A (100V AC) 2.5 A (240V AC) |
||
| Efficiency | typ. 90% | typ. 90% | typ. 91% | typ. 91% | typ. 92% |
| Output Voltage | 24...28V | 48...52V | |||
| Rated Output Current | 3.3 A @ 24V 2.9 A @ 28V |
5 A @ 24V 4.3 A @ 28V |
10 A @ 24V 8.6 A @ 28V |
5 A @ 48V 4.6 A @ 52V |
|
| Ripple/Noise | <50 mVPP | ||||
| Operating Temperature Range (Tamb) |
-25...+70 °C, >60 °C with derating | ||||
| Non-Operating Temperature Range | -40...+85 °C | ||||
| MTBF§ | >700 000 hours | ||||
| Dimensions (W x H x D) | 32 x 124 x 102 mm | 32 x 124 x 117 mm | 60 x 124 x 117 mm | ||
| Weight | 430 g | 500 g | 700 g | 800 g | 700 g |
| Certifications/Standards¬ | 1, 2, 3, 4, 5, 6, 7 | ||||
| Special Features | NEC Class 2 | — | |||
¬ 1) = CE, 2) = UL 508 (cULus LISTED), 3) = UL 1950 (cURus), 4) = CSA C22.2, No. 107-1, 5) Safety standards = IEC/EN 60950, EN 50178, 6) EMC standards = EN 55011 (Class B), EN 55022 (Class B), EN 61000-6-2, 7) EMC standards = EN 61000-3-2 (A14), EN 50081-1
§ MTBF determined by Siemens norm SN 29500 at full load current and 40 °C
z Because this catalog number ends with C, it indicates the device has conformal coating.
v Available in regional voltages: add N to the end of the cat. no. for 90...132V, or add E to the end of the cat. no. for 180...264V.
1606-XLP Compact Specifications
¬ 1) = CE, 2) = UL 508 (cULus LISTED), 3) = UL 1950 (cURus), 4) = CSA C22.2, No. 60950, 5) Safety standards = IEC/EN 60950, EN 50178, 6) EMC standards = EN 55011 (Class B), EN 55022 (Class B), EN 61000-6-2, 7) EMC standards = EN 61000-3-2 (A14), EN 50081-1
§ MTBF determined by Siemens norm SN 29500 at full load current and 40 °C
¬ 1) = CE, 2) = UL 508 (cULus LISTED), 3) = UL 1950 (cURus), 4) = CSA C22.2, No. 60950, 5) Safety standards = IEC/EN 60950, EN 50178, 6) EMC standards = EN 55011 (Class B), EN 55022 (Class B), EN 61000-6-2, 7) EMC standards = EN 61000-3-2 (A14), EN 50081-1
§ MTBF determined by Siemens norm SN 29500 at full load current and 40 °C
1606-XL Single Phase Specifications
¬ 1) = CE, 2) = UL 508 (cULus LISTED), 3) = UL 1950 (cURus), 4) = CSA C22.2, No. 60950, 5) Safety standards = IEC/EN 60950, EN 50178, 6) EMC standards = EN 55011 (Class B), EN 55022 (Class B), EN 61000-6-2, 7) EMC standards = EN 61000-3-2 (A14), EN 50081-1
Low inrush current
§ MTBF determined by Siemens norm SN 29500 at full load current and 40 °C
1606-XL Three Phase Specifications
¬ 1) = CE, 2) = UL 508 (cULus LISTED), 3) = UL 1950 (cURus), 4) = CSA C22.2, No. 60950, 5) Safety standards = IEC/EN 60950, EN 50178, 6) EMC standards = EN 55011 (Class B), EN 55022 (Class B), EN 61000-6-2, 7) EMC standards = EN 61000-3-2 (A14), EN 50081-1
Low inrush current
§ MTBF determined by Siemens norm SN 29500 at full load current and 40 °C
z Because this catalog number ends with "C", it indicates the device has conformal coating.
"Shut Down" Input
Function: Turning the unit on or off using logic signal (remote monitoring).
Unit switches off when Input is connected to "Signal GND" terminal (DU £ 1V) or the input has a voltage of +20...28V with respect to the "Signal GND" terminal, (max. 20 mA).
"DC Ok" Output
Function: Indicating whether the unit is operating properly. Output can directly energize a relay or a control light.
Signaling: Output signal is at a "high" level (24V, current source) in normal operation (no overload, overheating, short circuit). When the output signal switches to "low" level (no power at output), Vout remains for 5 ms (nominal) at nominal load.
Connection (signal common): Connection is made with respect to the "Signal GND" terminal (signal output).
Important: Do not connect to the power output (terminals + and -).
Permissible load: resistance - min. 300 W, e.g. 24V relay, control lights (LEDs need no series resistance), Evaluation logic.
For 5V signal: In order to receive a 5V signal: switch a 5V Zener diode (0.5 W) and 1 kW resistance in parallel between this output and the "Signal GND" terminal.
"Thermal Alarm" Output
Function: Output gives warning shortly before and while overtemperature state occurs. Output can directly control a relay or a control light.
Signaling: Output signal is at a "high" level (24V, current source) in normal operation (no overtemperature). At overtemperature, the output switches to "low". Only when the temperature in the unit increases further will the unit reduce its output current (power output).
Connection and permissible load: same as for "DC ok" output.
"Current Monitor" Output
Function: Measuring the output current (power output). Output signal is proportional to the output current of the unit.
Connection: Made with respect to the "Signal GND" terminal (signal output).
Important: Do not connect to the power output (terminals + and -).
Signaling:
Voltage measuring: Voltage at signal output is 1V per 10 A output current (Ri(voltmeter) > 100 k ohm )
Current measurement: Current at signal output is 1 mA per 10 A output current (Ri(ammeter) < 100 W)
"Current Balance" In-/Output
Function: Using these terminals, parallel operating units ensure an equal load sharing (active balancing). Balancing also works reliably with decoupling diodes at the power output (redundancy).
Connection: Connect together "Current Balance" outputs of all units involved.
Important: Signal common here is the - terminal of the power output, not the "Signal GND". Do not connect the "Signal GND" terminals to each other!
"Signal GND" Terminal
Function: Grounding terminal for all signal terminals (not for "Current Balance").
Connection instructions: Do not connect this terminal with terminals + or - of the unit (not even over a load: risk of overload). Do not connect this terminal with terminals of other units (not even with the "Signal GND" terminal of another unit).
Permissible load: Maximum current load: 0.3 A. Terminal is fused internally with a self-healing fuse (polyswitch).
|
|
Special Modules
1606-XL Special Modules
¬ 1) = CE, 2) = UL 508 (cULus LISTED), 3) = UL 1950 (cURus), 5) Safety standards = IEC/EN 60950, EN 50178, 6 EMC standards = EN 55011 (Class B), EN 55022 (Class B), EN 61000-6-2, 7) = EMC standards = EN 61000-3-2 (A14), EN 50081-1
Low inrush current
§ MTBF determined by Siemens norm SN 29500 at full load current and 40 °C
¬ 1) = CE, 2) = UL 508 (cULus LISTED), 3) = UL 1950 (cURus), 5) Safety standards = IEC/EN 60950, EN 50178, 6 EMC standards = EN 55011 (Class B), EN 55022 (Class B), EN 61000-6-2, 7) = EMC standards = EN 61000-3-2 (A14), EN 50081-1
§ MTBF determined by Siemens norm SN 29500 at full load current and 40 °C
Approximate Dimensions and Wire Size
Approximate dimensions are shown in inches (mm) unless otherwise indicated. Dimensions are not to be used for manufacturing purposes.
Bulletin 1606 Dimensions Table
|
| Catalog Number | W [in. (mm)] | H [in. (mm)] | D [in. (mm)]¬ | Wire SizeT (Input and Output unless otherwise noted) |
| 1606-XLS80E | 1.26 (32) | 4.88 (124) | 4.02 (102) | InputT Stranded 20...10 AWG (0.5...4 mm2) Solid 20...10 AWG (0.5...6 mm2) OutputT Stranded 28...12 AWG (0.3...2.5 mm2) Solid 28...12 AWG (0.3...4 mm2) |
| 1606-XLS120E | 1.57 (40) | 4.88 (124) | 4.61 (117) | |
| 1606-XLSDNET4 | ||||
| 1606-XLS240E | 2.36 (60) | 4.88 (124) | 4.61 (117) | Input/OutputT Stranded 20...10 AWG (0.5...4 mm2) Solid 20...10 AWG (0.5...6 mm2) |
| 1606-XLS240EC | ||||
| 1606-XLS480E | 3.31 (84) | 4.88 (124) | 4.61 (117) | |
| 1606-XLS480E-3 | 2.56 (65) | 4.88 (124) | 5.00 (127) | |
| 1606-XLS480E-3C | ||||
| 1606-XLSDNET8 | 2.36 (60) | 4.88 (124) | 4.61 (117) | |
| 1606-XLSRED | 1.26 (32) | 4.88 (124) | 4.02 (102) | |
| 1606-XLE80E | 1.26 (32) | 4.88 (124) | 4.02 (102) | |
| 1606-XLE120E | 1.26 (32) | 4.88 (124) | 4.61 (117) | Input/OutputT Stranded 20...10 AWG (0.5...4 mm2) Solid 20...10 AWG (0.5...6 mm2) |
| 1606-XLE120EC | ||||
| 1606-XLE120EE | ||||
| 1606-XLE120EN | ||||
| 1606-XLE240E | 2.36 (60) | 4.88 (124) | 4.61 (117) | |
| 1606-XLE240EE | ||||
| 1606-XLE240EN | ||||
| 1606-XLE240EP | ||||
| 1606-XLE240F | ||||
| 1606-XLERED | 1.26 (32) | 4.88 (124) | 4.61 (117) | |
| 1606-XLP15A | 0.89 (22.5) | 2.95 (75) | 3.58 (91) | Input/OutputT Stranded 20...10 AWG (0.5...4 mm2) Solid 20...10 AWG (0.5...6 mm2) |
| 1606-XLP15B | ||||
| 1606-XLP15E | ||||
| 1606-XLP25A | 1.77 (45) | 2.95 (75) | 3.58 (91) | Input/OutputT Stranded 28...12 AWG (0.3...2.5 mm2) Solid 28...12 AWG (0.3...4 mm2) |
| 1606-XLP30B | ||||
| 1606-XLP30E | ||||
| 1606-XLP36C | ||||
| 1606-XLP50B | ||||
| 1606-XLP50E | ||||
| 1606-XLP50EZ | ||||
| 1606-XLP50F | ||||
| 1606-XLP72E | ||||
| 1606-XLPRED | ||||
| 1606-XLP90B | 2.87 (73) | 2.95 (75) | 4.06 (103) | |
| 1606-XLP90E-2 | ||||
| 1606-XLP95E | ||||
| 1606-XLP100E | ||||
| 1606-XLP100E-2 | ||||
| 1606-XLP100F | ||||
¬ Depth measurement does not include DIN Rail.
T The wire sizes indicated refer only to the connection capability of the terminal.
For proper operation, the correct wire size must be used (based on accurate determination of the electrical characteristics and loading of the system).
| Catalog Number | W [in. (mm)] | H [in. (mm)] | D [in. (mm)]¬ | Wire SizeT (Input and Output unless otherwise noted) |
| 1606-XL60D | 1.93 (49) | 4.88 (124) | 4.02 (102) | Input/OutputT Stranded 20...10 AWG (0.5...4 mm2) Solid 20...10 AWG (0.5...6 mm2) |
| 1606-XL180B | 4.72 (120) | 4.88 (124) | 4.02 (102) | |
| 1606-XL480E | 8.6 (220) | 4.88 (124) | 4.02 (102) | |
| 1606-XL480EP | ||||
| 1606-XL480EPT | ||||
| 1606-XL480GP | ||||
| 1606-XL480F | ||||
| 1606-XL120E-3 | 2.87 (73) | 4.88 (124) | 4.61 (117) | Input/OutputT Stranded 20...10 AWG (0.5...4 mm2) Solid 20...10 AWG (0.5...6 mm2) |
| 1606-XL240E-3 | 3.50 (89) | 4.88 (124) | 4.61 (117) | |
| 1606-XL240E-3C | 3.50 (89) | 4.88 (124) | 4.61 (117) | |
| 1606-XL480E-3 | 8.66 (220) | 4.88 (124) | 4.02 (102) | |
| 1606-XL480E-3W | 5.91 (150) | 4.88 (124) | 4.76 (121) | |
| 1606-XL480F-3H | 8.66 (220) | 4.88 (124) | 4.02 (102) | |
| 1606-XL720E-3 | 9.45 (240) | 4.88 (124) | 4.41 (112) | |
| 1606-XL960E-3 | 10.83 (275) | 4.88 (124) | 4.61 (117) | InputT Stranded 20...10 AWG (0.5...4 mm2) Solid 20...10 AWG (0.5...6 mm2) |
| 1606-XL960E-3S | OutputT Stranded 22...8 AWG (0.5...10 mm2) Solid 22...8 AWG (0.5...16 mm2) |
|||
| 1606-XLS240-UPS | 1.93 (49) | 4.88 (124) | 4.61 (117) | InputT Stranded 22...10 AWG (0.2...4 mm2) Solid 22...10 AWG (0.2...6 mm2) OutputT Stranded 22...14 AWG (0.2...2 mm2) Solid 22...14 AWG (0.2...2.5 mm2) |
| 1606-XLBUFFER | 2.56 (65) | 4.88 (124) | 4.02 (102) | Input/OutputT Stranded 20...10 AWG (0.5...4 mm2) Solid 20...10 AWG (0.5...6 mm2) |
| 1606-XLDC40A | 1.93 (49) | 4.88 (124) | 4.02 (102) | |
| 1606-XLDNET4 | 2.56 (65) | 4.88 (124) | 4.02 (102) | |
| 1606-XLDNET8 | 4.72 (120) | 4.88 (124) | 4.02 (102) | Input/OutputT Stranded 22...10 AWG (0.2...2.5 mm2) Solid 22...10 AWG (0.2...2.5 mm2) |
| 1606-XL60DR | 1.93 (49) | 4.88 (124) | 4.02 (102) | Input/OutputT Stranded 22...12 AWG (0.2...2.5 mm2) Solid 22...12 AWG (0.2...2.5 mm2) |
| 1606-XL120DR | 2.56 (64) | 4.88 (124) | 4.02 (102) | |
| 1606-XL240DR | 4.72 (120) | 4.88 (124) | 4.02 (102) | |
| 1606-XLRED20-30 | 1.89 (48) | 4.88 (124) | 4.02 (102) | Input/OutputT Stranded 20...10 AWG (0.5...4 mm2) Solid 20...10 AWG (0.5...6 mm2) |
| 1606-XLRED40 | 1.89 (48) | 4.88 (124) | 4.61 (117) | |
¬ Depth measurement does not include DIN Rail.
T The wire sizes indicated refer only to the connection capability of the terminal.
For proper operation, the correct wire size must be used (based on accurate determination of the electrical characteristics and loading of the system).
Accessories
1606-XLA Back of Panel Mounting Bracket for XL Power Supplies
Instead of snapping the power supply onto a DIN-rail, you also can mount it to the back of the panel. This set consists of two aluminum profiles which replace the existing profiles at the back of the unit.
Notes:
- You need one set per unit.
- In addition, two screws are required per set (e.g. M5 x 12 or corresponding sheet-metal screws; they are not included in the set.)
Approximate Dimensions — mm (in.)
|
|
1606-XLB Back of Panel Mounting Bracket for XLS and XLE Power Supplies
Instead of snapping the power supply onto a DIN Rail, you can mount it to the back of the panel. This set consists of two steel brackets which replace the existing DIN Rail aluminum brackets at the back of the unit.
Note:
- You need one set per unit.
Approximate Dimensions — mm
|
|
1606-XL, 1606-XLBuffer, 1606-XLS DC UPS
1606-XL Redundancy Capabilities
The 1606-XL family has two cost effective methods for providing redundancy to applications that are critical and can not risk failure.
1606-XL60DR, XL120DR and XL240DR Redundant Power Supplies
|
|
The 1606-XL60DR, XL120DR and XL240DR are enhanced versions of the standard power supplies.
- Each device has internal diodes which provide isolation against DC bus problems corrupting working supplies.
- Provides "DC OK" output relay to allow remote monitoring of DC power status.
- Utilizes pluggable terminals for easy installation.
1606-XLRED20-30 and 1606-XLRED40 Redundancy Modules
|
|
The 1606-XLRED20-30 and 1606-XLRED40 allow redundant wiring of 20…40 A power supplies.
- Devices provide isolation of power supplies via diodes.
- Provide remote monitoring of DC power status of each power supply.
- A single XLRED20-30 can be used per pair of identical 20 or 30 A power supplies.
- One XLRED40 is required for every 40 A power supply.
1606-XLPRED
- When used in 1 + 1 redundant systems (such as XLRED20-30) limited to 8 A (short circuit) per power supply
- When used in 1 + 1 redundant system (such as XLRED40) limited to 13 A (short circuit)
- See product technical data sheets for more application information.
1606-XLSRED/1606-XLERED
- When used in 1 + 1 redundant systems (such as XLRED20-30) limited to 10 A (short circuit) per power supply
- When used in 1 + 1 redundant system (such as XLRED40) limited to 20 A (short circuit)
- See product instruction manual for more application information.
1606-XLBuffer
Features
- Buffering for 24V loads
- Guaranteed hold-up time: 0.2 s/20 A…3.6 s/1 A
- Fit for industrial use: Energy storage in electrolytic caps., no accumulators
- Clear status indication by Status LED and signalling terminals
- No batteries requiring replacement
Short Description
The buffer unit is a supplementary device for regulated 24V DC power supplies. It buffers load currents during typical mains faults and switching events or load peaks.
Working principle
|
In times when the power supply provides sufficient voltage, the buffer unit stores energy in integrated electrolytic capacitors. In case of a mains voltage fault, this energy is released again in a regulated process.
Bridges mains faults without interruption
|
Statistics show that 80% of all mains faults last less than 0.2 s. These mains faults are completely bridged by the buffer unit and will have no influence on the DC power. This increases the reliability of the system as a whole.
|
Extended hold-up time
Once the main power fails or is switched off, the buffer unit will continue to provide the load current for a defined period of time. Process data can be saved and processes can be terminated before the DC power switches off. Controlled restarts are subsequently possible.
Easy to handle, expandable, and maintenance-free
|
The buffer unit does not require any control wiring. It can be added in parallel to the load circuit at any given point. Any given number of buffer units can be installed in parallel to increase the output capacity or the hold-up time. The dual terminals allow for easy wiring.
Operating Modes
|
Activation Threshold
| 22.5V fixed | Buffering starts if terminal voltage <22.5V, voltage is kept at 22.5V. |
| Vin -1V | Buffering starts if terminal voltage decreases by more than 1V, faster than typ. 0.54V/s. Voltage is kept at that level. Buffering ends when voltage increases once more by 1V. |
| Noise (spikes) | >200mVPP (20MHz bandw., 50 Wmeasurement, buffer operation only) |
| Over voltage protection | limited to max. ±35V |
Hold-up Time
|
Operating Indicators and Elements
|
A - Signaling terminals:
- 7 Active: unit is buffering
- 8 Ready: unit is on stand-by
B - Jumper back-up threshold:
- Position 1-2: variable:
Vin -1V. Buffering if voltage decreases faster than typical 0.54V/s and greater than 1V
- Position 2-3: DC 22.5V fixed. Voltage buffering starts at Vin less than 22.5V
C - Status LED
Indicates charge status of buffer capacitor array
D - Power In/Out terminals:
dual terminals
- + (positive)
- - (negative)
1606-XLS DC UPS
Features
- Requires only one 12V battery
- Electronically protected against output overloads
- Flexible battery options, modular system
- Extensive battery management including battery quality and installation tests
- Regulated output voltage in buffer mode
- Soft charger for optimum battery life
- 50% power reserves
- Extensive diagnostic and monitoring functions
Short Description
The DC UPS is a supplementary device to a 24V power supply. It provides back-up power to bridge dips, sags, or brief losses of power using a 12V battery. Based on the battery you select, you can achieve hold-up times anywhere from a few minutes to several hours.
Working principle
In times when the power supply provides sufficient voltage, the DC UPS charges the 12V battery. When input power fails, the battery voltage will be boosted to a 24V level through a boost converter and the energy will be released in a regulated process to the load.
Integrated in the DC UPS is a sophisticated battery management system. This battery management system incorporates a battery charger, deep discharge protection, and overload protection which together increase the service life of the battery.
In addition, there are extensive protective features that self-protect the unit from damage along with diagnostic and monitoring functions that aid in troubleshooting.
|
Extended Hold-Up Time
The modular design of the DC UPS allows for flexible battery options. The design will accept valve regulated, lead-acid batteries between 3.9Ah 27Ah. The modularity of the system enables you to match the battery with your application requirements.
|
Extensive Diagnostic & Monitoring Functions
Protective Features:
- Wrong battery voltage (24V instead of 12V)
- Deep discharge (battery) protection
- Wrong battery polarity
- Wrong polarity on input terminals
- Too high ambient temperature
- Over-voltage protection
(malfunctioning of the internal regulation loops)
- Output overload or output short-circuit
|
A - Status LED (green):
- Ready: Battery is charged > 85%, no wiring failure is recognized, input voltage is sufficient and inhibit signal is not active.
- Charging: Battery is charging and battery capacity is below 85%.
- Buffering: Unit is in buffer mode.
B - Diagnosis LED (yellow):
- Overload: Output has switched off, due to long overload in buffer mode or due to high temperatures.
- Replace battery: Indicates a battery which failed the battery quality test (SCH test). Battery should be replaced soon.
- Buffer time expired: Output has switched off due to settings of buffer time. The signal will be stored and displayed for 15 minutes.
- Inhibit active: Indicates that buffering is disabled due to an active inhibit signal.
| C - Check wiring LED (red): |
| Check wiring between DC UPS and battery, as well as the battery itself. Also indicates when input voltage is not in range. |
D - Adjustor:
- Buffer time limiter: User accessible switch which limits the maximum buffer time in a buffer event, to save battery capacity.
- End-of-charge voltage: User accessible potentiometer which sets the end-of-charge voltage. Adjust the potentiometer according to the expected battery temperature.
E - Signal contacts:
| Ready (contact 1-2): |
| Contact is closed when battery is charged more than 85%, no wiring failure is recognized, input voltage is sufficient, and inhibit signal is not active. |
| Buffering (contact 3-4): |
| Contact is closed when unit is buffering. |
| Replace battery (contact 5-6): |
| Contact is closed when input voltage is sufficient and battery quality test (SCH test) indicates a negative result, three times in a row. |
| Inhibit input (contact 7&8): |
| The inhibit input disables buffering. In normal mode, a static signal is required. In buffer mode, a pulse with a minimum length of 250 ms is required to stop buffering. The inhibit is stored and can be reset by cycling the input voltage. |