Power Supplies

Catalogs > Industrial Controls Catalog > Power Supplies > Switched Mode

Switched Mode

Introduction Certifications How to Select a Bulletin 1606 Power Supply Quick Guide Cat. No. Explanation
Product Selection 1606 Accessories Specifications Approximate Dimensions and Wire Size 1606-XL, 1606-XLBuffer, 1606-XLS DC UPS
How to Select a Bulletin 1606 Power Supply

The Bulletin 1606 line of Power Supplies is designed with "reserve power" thereby eliminating the need to oversize your power supply to start high inrush loads.

Steps to size a Power Supply
1. Determine the "Average" continuous current of the load and the typical inrush current.
2. Select a power supply where the rated load is at/or below the current of the device and the Peak Current is less than the short-circuit rating of the power supply.

Notes:
  • PowerBoost will deliver up to 25% additional current continuously at 40 °C or less.
  • ReservePower will deliver 150% of rated current for up to 5 s.

  • Example:
    Application: Single Phase 120V input, 24V output, 5 A continuous current @ 35 °C, with 7.5 A inrush current
    Solution: 1606-XLS120E

    Output Characteristic for XLS120E (5 A) Power Supply


    Click to enlarge - 1606_output_graph IRATED: 5 A
    ISHORT CIRCUIT: >9 A
    IPOWER BOOST: 7.5 A

    Cat. No. IRATED [A] ISHORT CIRCUIT (25 °C) [A] IPOWER BOOST or
    IRESERVEPOWER [A]
    1606-XLS80E 3.3 5.2 5.4§ 
    1606-XLS120E 5 9 7.5§ 
    1606-XLS240E 10 21 15§ 
    1606-XLS480E 20 30 30§ 
    1606-XLS480E-3 20 29 30§ 
    1606-XLSDNET4 3.8 4
    1606-XLSDNET8 8 7
    1606-XLE80E 3.3 5.5 3.6
    1606-XLE120E 5 11 6
    1606-XLE240E 10 16 12
    1606-XLE240EP 10 16 12
    1606-XLE240F 5 8.5 6
    1606-XLP15E 0.6 0.75
    1606-XLP25A 5 5
    1606-XLP30B 3 4
    1606-XLP30E 1.3 1.9
    1606-XLP36C 2.8 2
    1606-XLP50B 4.2 4.3
    1606-XLP50E 2.1 3.1
    1606-XLP50EZ 2.1 3.1
    1606-XLP50F 1 1.7
    1606-XLP72E 3 4.5
     

    Cat. No. IRATED [A] ISHORT CIRCUIT (25 °C) [A] IPOWER BOOST or
    IRESERVEPOWER [A]
    1606-XLP90B 7.5 8
    1606-XLP90E-2 3.75 7
    1606-XLP95E 3.9 7
    1606-XLP100E 4.2 7.1
    1606-XLP100E-2 4.2 8
    1606-XLP100F 2.1 3.6
    1606-XL60D 2.5 4.5§ 
    1606-XL180B 15 21§ 
    1606-XL480EPT 20 22 25
    1606-XL480GP 13.3 12 16.6
    1606-XL480F 10 24 12.5
    1606-XL120E-3 5 11§  6
    1606-XL240E-3 10 22§  12
    1606-XL480E-3W 20 25 25
    1606-XL480F-3H 10 N/AØ  12.5
    1606-XL720E-3 30 N/AØ  33
    1606-XL960E-3 40 44 45
    1606-XL960E-3S 40 44 45
    1606-XL60DR 2.5 4.5§ 
    1606-XL120DR 5 10§  6
    1606-XL240DR 10 18§  12
     

    §  Products with ReservePower.
    §  Short circuit current values are temperature dependent for the selected product; i.e., the higher the ambient temperature, the lower the short circuit current.
    Ø  Hiccup Overload design.