Catalogs > Industrial Controls Catalog > Power Supplies > Switched Mode
Switched Mode
| Introduction | Certifications | How to Select a Bulletin 1606 Power Supply | Quick Guide | Cat. No. Explanation |
| Product Selection | 1606 Accessories | Specifications | Approximate Dimensions and Wire Size | 1606-XL, 1606-XLBuffer, 1606-XLS DC UPS |
The Bulletin 1606 line of Power Supplies is designed with "reserve power" thereby eliminating the need to oversize your power supply to start high inrush loads.
| Steps to size a Power Supply |
| 1. Determine the "Average" continuous current of the load and the typical inrush current. |
| 2. Select a power supply where the rated load is at/or below the current of the device and the Peak Current is less than the short-circuit rating of the power supply. |
| Notes: |
| Example: |
| Application: Single Phase 120V input, 24V output, 5 A continuous current @ 35 °C, with 7.5 A inrush current |
| Solution: 1606-XLS120E |
Output Characteristic for XLS120E (5 A) Power Supply
|
IRATED: 5 A ISHORT CIRCUIT: >9 A IPOWER BOOST: 7.5 A |
| Cat. No. | IRATED [A] | ISHORT CIRCUIT (25 °C) [A] | IPOWER BOOST or IRESERVEPOWER [A] |
| 1606-XLS80E | 3.3 | 5.2 | 5.4§ |
| 1606-XLS120E | 5 | 9 | 7.5§ |
| 1606-XLS240E | 10 | 21 | 15§ |
| 1606-XLS480E | 20 | 30 | 30§ |
| 1606-XLS480E-3 | 20 | 29 | 30§ |
| 1606-XLSDNET4 | 3.8 | 4 | — |
| 1606-XLSDNET8 | 8 | 7 | — |
| 1606-XLE80E | 3.3 | 5.5 | 3.6 |
| 1606-XLE120E | 5 | 11 | 6 |
| 1606-XLE240E | 10 | 16 | 12 |
| 1606-XLE240EP | 10 | 16 | 12 |
| 1606-XLE240F | 5 | 8.5 | 6 |
| 1606-XLP15E | 0.6 | 0.75 | — |
| 1606-XLP25A | 5 | 5 | — |
| 1606-XLP30B | 3 | 4 | — |
| 1606-XLP30E | 1.3 | 1.9 | — |
| 1606-XLP36C | 2.8 | 2 | — |
| 1606-XLP50B | 4.2 | 4.3 | — |
| 1606-XLP50E | 2.1 | 3.1 | — |
| 1606-XLP50EZ | 2.1 | 3.1 | — |
| 1606-XLP50F | 1 | 1.7 | — |
| 1606-XLP72E | 3 | 4.5 | — |
| Cat. No. | IRATED [A] | ISHORT CIRCUIT (25 °C) [A] | IPOWER BOOST or IRESERVEPOWER [A] |
| 1606-XLP90B | 7.5 | 8 | — |
| 1606-XLP90E-2 | 3.75 | 7 | — |
| 1606-XLP95E | 3.9 | 7 | — |
| 1606-XLP100E | 4.2 | 7.1 | — |
| 1606-XLP100E-2 | 4.2 | 8 | — |
| 1606-XLP100F | 2.1 | 3.6 | — |
| 1606-XL60D | 2.5 | 4.5§ | — |
| 1606-XL180B | 15 | 21§ | — |
| 1606-XL480EPT | 20 | 22 | 25 |
| 1606-XL480GP | 13.3 | 12 | 16.6 |
| 1606-XL480F | 10 | 24 | 12.5 |
| 1606-XL120E-3 | 5 | 11§ | 6 |
| 1606-XL240E-3 | 10 | 22§ | 12 |
| 1606-XL480E-3W | 20 | 25 | 25 |
| 1606-XL480F-3H | 10 | N/AØ | 12.5 |
| 1606-XL720E-3 | 30 | N/AØ | 33 |
| 1606-XL960E-3 | 40 | 44 | 45 |
| 1606-XL960E-3S | 40 | 44 | 45 |
| 1606-XL60DR | 2.5 | 4.5§ | — |
| 1606-XL120DR | 5 | 10§ | 6 |
| 1606-XL240DR | 10 | 18§ | 12 |
§ Products with ReservePower.
§ Short circuit current values are temperature dependent for the selected product; i.e., the higher the ambient temperature, the lower the short circuit current.
Ø Hiccup Overload design.