Catalogs > Industrial Controls Catalog > Power Supplies > Switched Mode
Switched Mode
| Introduction | Certifications | How to Select a Bulletin 1606 Power Supply | Quick Guide | Cat. No. Explanation |
| Product Selection | 1606 Accessories | Specifications | Approximate Dimensions and Wire Size | 1606-XL, 1606-XLBuffer, 1606-XLS DC UPS |
| Build a Catalog Number |
1606-XLS Performance — Single- and Three-Phase
Single-Phase
| Input Voltage | Input Voltage Selector | Output Power [W] | Output Voltage | Output Current [A] | Input Circuit Protection§ | Inrush Current | Parallel Operation | Meets EN 61000-3-2 PFC Harmonics | DC OK Relay | Cat. No. |
| 100…240V AC, 110…300V DC | Auto | 80 | 24…28 | 3.3 | 6 A SLOW BLOW FUSE OR 1492-SPU1C060/20 A | <7.0 A | Yes | — | — | 1606-XLS80E |
| 100…240V AC, 110…300V DC | Auto | 120 | 24…28 | 5 | 6 A SLOW BLOW FUSE OR 1492-SPU1C060/20 A | <4.9 A | Yes | — | ü | 1606-XLS120E |
| 100…240V AC, 110…300V DC | Auto | 240 | 24…28 | 10 | 6 A SLOW BLOW FUSE OR 1492-SPU1C060/20 A | <5.0 A | Yes | — | ü | 1606-XLS240E |
| 100…240V AC, 110…300V DC | Auto | 480 | 24…28 | 20 | 6 A SLOW BLOW FUSE OR 1489-A1C060/20 A | <9.0 A | Yes | — | ü | 1606-XLS480E |
| 100…240V AC, 110…300V DC | Auto | 91 | 24 | 3.8 | 6 A SLOW BLOW FUSE OR 1489-A1C060/20 A | <4.9 A | No | Yes | ü | 1606-XLSDNET4 |
| 100…240V AC, 110…300V DC | Auto | 192 | 24 | 8 | 6 A SLOW BLOW FUSE OR 1489-A1C060/20 A | <7.6 A | Yes | No | ü | 1606-XLSDNET8 |
Three-Phase
| Input Voltage | Input Voltage Selector | Output Power [W] | Output Voltage | Output Current [A] | Input Circuit Protection | Inrush Current | Parallel Operation | Meets EN 61000-3-2 PFC Harmonics | DC OK Relay | Cat. No. |
| 380…480V AC, 600V DC | Auto | 480 | 24…28 | 20 | 6 A (X3) SLOW BLOW FUSE OR 1492-SP3C060 | <4.0 A | Yes | — | ü | 1606-XLS480E-3 |
§ Unit has internal (not accessible/replaceable) input fuse. Additional protection is not required if used on branch circuits £ UL test levels.
Consult local codes and regulations for installation.
1606-XLE Essential — Single-Phase
| Input Voltage | Input Voltage Selector | Output Power [W] | Output Voltage | Output Current [A] | Input Circuit Protection | Inrush Current | Parallel Operationª | Meets EN 61000-3-2 PFC Harmonics | DC OK Relay | Cat. No. |
| 100…120/200…240V AC | Auto | 80 | 24…28 | 3.3 | 10 A SLOW BLOW FUSE OR 1489-A1C100/20 A§ | <3 A | No | Yes | — | 1606-XLE80E |
| 100…120/200…240V AC | 120 | 24…28 | 5 | 10 A SLOW BLOW FUSE OR 1489-A1C100/20 A§ | <3 A | No | — | — | 1606-XLE120E | |
| 90…132V AC | 24…28 | 5 | 10 A SLOW BLOW FUSE OR 1489-A1C100/20 A§ | <3 A | Yes | — | — | 1606-XLE120EN | ||
| 180…264V AC | 24…28 | 5 | 10 A SLOW BLOW FUSE OR 1489-A1C100/20 A§ | <3 A | No | — | — | 1606-XLE120EE | ||
| 100…120/200…240V AC | 240 | 24…28 | 10 | 10 A SLOW BLOW FUSE OR 1489-A1C100/20 A§ | <3 A | No | — | — | 1606-XLE240E | |
| 90…132V AC | 24…28 | 10 | 10 A SLOW BLOW FUSE OR 1489-A1C100/20 A§ | <3 A | Yes | — | — | 1606-XLE240EN | ||
| 180…264V AC | 24…28 | 10 | 10 A SLOW BLOW FUSE OR 1489-A1C100/20 A§ | <3 A | No | — | — | 1606-XLE240EE | ||
| 100…120/200…240V AC | 24…28 | 10 | 10 A SLOW BLOW FUSE OR 1489-A1C100/20 A§ | <3 A | No | — | — | 1606-XLE240EP | ||
| 100…120/200…240V AC | 48…52 | 5 | 10 A SLOW BLOW FUSE OR 1489-A1C100/20 A§ | <3 A | No | — | — | 1606-XLE240F | ||
1606-XLP Compact — Single- and Two-Phase
Single-Phase
| Input Voltage | Input Voltage Selector | Output Power [W] | Output Voltage | Output Current [A] | Input Circuit Protection | Inrush Current | Parallel Operation | Meets EN 61000-3-2 PFC Harmonics | DC OK Relay | Cat. No. |
| 100…240V AC, 85…375V DC | Auto | 15 | 5…5.5 | 3 | 10 A SLOW BLOW FUSE OR 1489-A1C100/15 A§ | <11 A | Yes | NA | — | 1606-XLP15A |
| 12…15 | 1.3 | — | 1606-XLP15B | |||||||
| 24…28 | 0.6 | — | 1606-XLP15E | |||||||
| 100…240V AC, 85…375V DC | Auto | 25 | 5…5.5 | 5 | 10 A SLOW BLOW FUSE OR 1489-A1C100/15 A§ | <18 A | Yes | NA | — | 1606-XLP25A |
| 100…240V AC, 85…375V DC | Auto | 30 | 10…12 | 3 | 10 A SLOW BLOW FUSE OR 1489-A1C100/15 A§ | <18 A | Yes | NA | — | 1606-XLP30B |
| 24…28 | 1.3 | 1606-XLP30E | ||||||||
| 100…240V AC, 85…375V DC | Auto | 36 | +/- 12/15V | 2.8 | 10 A SLOW BLOW FUSE OR 1489-A1C100/15 A§ | <18 A | No | NA | — | 1606-XLP36C |
| 100…240V AC, 85…375V DC | Auto | 50 | 12…15 | 4.2 | 10 A SLOW BLOW FUSE OR 1489-A1C100/15 A§ | <18 A | Yes | NA | — | 1606-XLP50B |
| 24…28 | 2.1 | ü | 1606-XLP50E | |||||||
| 24…28 | 2.1 | ü | 1606-XLP50EZ | |||||||
| 48…56 | 1 | — | 1606-XLP50F | |||||||
| 100…120/220…240V AC, 220…375V DC | Man. | 72 | 24…28 | 3 | 10 A SLOW BLOW FUSE OR 1489-A1C100/15 A§ | <30 A | Yes | NA | — | 1606-XLP72E |
| 100…120/220…240V AC, 220…375V DC | Auto | 90 | 12…15 | 7.5 | 10 A SLOW BLOW FUSE OR 1489-A1C100/15 A§ | <30 A | Yes | Yes | — | 1606-XLP90B |
| 100…200/200…240V AC, 220…375V DC | Auto | 95 | 24…28 | 3.9 | 10 A SLOW BLOW FUSE OR 1489-A1C100/15 A§ | <30 A | No | Yes | — | 1606-XLP95E |
| 100…200/200…240V AC, 220…375V DC | Auto | 100 | 24…28 | 4.2 | 10 A SLOW BLOW FUSE OR 1489-A1C100/15 A§ | <30 A | Yes | Yes | — | 1606-XLP100E |
| 100…200/200…240V AC, 220…375V DC | Auto | 48…56 | 2.1 | 10 A SLOW BLOW FUSE OR 1489-A1C100/15 A§ | <30 A | Yes | Yes | — | 1606-XLP100F | |
Two-Phase
| Input Voltage | Input Voltage Selector | Output Power [W] | Output Voltage | Output Current [A] | Input Circuit Protection | Inrush Current | Parallel Operation | Meets EN 61000-3-2 PFC Harmonics | DC OK Relay | Cat. No. |
| 380…480V AC | — | 90 | 24…28 | 3.75 | 10 A (X2) SLOW BLOW FUSE OR 1489-A2C100/20 A§ | <35 A | No | — | — | 1606-XLP90E-2 |
| 380…480V AC | — | 100 | 24…28 | 4.2 | 10 A (X2) SLOW BLOW FUSE OR 1489-A2C100/20 A§ | <35 A | Yes | — | — | 1606-XLP100E-2 |
§ Unit has internal (not accessible/replaceable) input fuse. Additional protection is not required if used on branch circuits £ UL test levels.
ª Parallel use for 1 + 1 redundancy only.
Single/parallel operation (inclined characteristic) selectable (jumper).
Consult local codes and regulations for installation.
1606-XL Standard — Single- and Three-Phase
Single-Phase
| Input Voltage | Input Voltage Selector | Output Power [W] | Output Voltage | Output Current [A] | Input Circuit Protection | Inrush Current | Parallel Operation | Meets EN 61000-3-2 PFC Harmonics | DC OK Relay | Cat. No. |
| 100…120/200…240V AC, 160…375V DC | Man. | 60 | 24 | 2.5 | 10 A SLOW BLOW FUSE OR 1489-A1C100/16 A§ | <18 A | Yes | — | — | 1606-XL60D |
| 100…200/200…240V AC, 240…375V DC | Man. | 180 | 12…15 | 15 | 10 A SLOW BLOW FUSE OR 1489-A1C100/10 A§ | <21 A | Yes | — | — | 1606-XL180B |
| 200…240V AC, 270…370V DC | — | 480 | 24…28 | 20 | 10 A SLOW BLOW FUSE OR 1489-A1C100/16 A | <23 A | Yes | — | — | 1606-XL480E |
| 100…120/200…240V AC | Auto | 24…28 | 20 | 10 A SLOW BLOW FUSE OR 1489-A1C100 | <18 A @ 25°C | Yes | — | — | 1606-XL480EP | |
| 100…120/200…240V AC | Auto | 24…28 | 20 | 10 A SLOW BLOW FUSE OR 1489-A1C100 | <18 A @ 25°C | Yes | — | — | 1606-XL480EPT | |
| 100…120/200…240V AC | Auto | 36…43 | 13.3 | 10 A SLOW BLOW FUSE OR 1489-A1C100 | <18 A @ 25°C | Yes | — | — | 1606-XL480GP | |
| 100…120/200…240V AC | Auto | 48…56 | 10 | 10 A SLOW BLOW FUSE OR 1489-A1C100 | <18 A @ 25°C | Yes | — | — | 1606-XL480F | |
Three-Phase
| Input Voltage | Output Power [W] | Output Voltage | Output Current [A] | Input Circuit Protection | Inrush Current | Parallel Operation | Meets EN 61000-3-2 PFC Harmonics | DC OK Relay | Cat. No. |
| 400…500V AC, 450…820V DC | 120 | 24…28 | 5 | 10 A (X3) SLOW BLOW FUSE OR 1492-SP3C100 | <25 A | Yes | — | — | 1606-XL120E-3 |
| 400…500V AC, 450…820V DC | 240 | 24…28 | 10 | 6 A (X3) SLOW BLOW FUSE OR 1492-SP3C060/15 A§ | <17 A | Yes | — | — | 1606-XL240E-3 |
| 400…500V AC, 450…820V DC | 480 | 24…28 | 20 | 6 A (X3) SLOW BLOW FUSE OR 1492-SP3C060/16 A§ | <7 A | Yes | — | — | 1606-XL480E-3W |
| 400V AC, 450…700V DC | 48…56 | 10 | 10 A (X3) SLOW BLOW FUSE OR 1492-SP3C100 | <15 A | 1606-XL480F-3H | ||||
| 400…500V AC, 450…820V DC | 720 | 24…28 | 30 | 10 A (X3) SLOW BLOW FUSE OR 1492-SP3C100 | <17 A | Yes | — | — | 1606-XL720E-3 |
| 400…500V AC | 960 | 24…28 | 40 | 10 A (X3) SLOW BLOW FUSE OR 1492-SP3C100 | <30 A | Yes | — | — | 1606-XL960E-3 |
| Active current sharing | z | 1606-XL960E-3S | |||||||
Single/parallel operation (inclined characteristic) selectable (jumper).
§ Unit has internal (not accessible/replaceable) input fuse. Additional protection is not required if used on branch circuits £ UL test levels.
z DC OK output is provided through a 24V DC signal.
Consult local codes and regulations for installation.
1606 Special Modules
| Input Voltage | Input Voltage Selector | Output Power [W] | Output Voltage | Output Current [A] | Input Circuit Protection | Inrush Current | Parallel Operation | Meets EN 61000-3-2 PFC Harmonics | DC OK Relay | Cat. No. |
| 18…36V DC | — | 40 | 5.1 | 8 | N/A | <5 A | Yes | NA | — | 1606-XLDC40A |
| 100…240V AC, 110…300V DC | Auto | 91 | 24 | 3.8 | 6 A SLOW BLOW FUSE OR 1489-A1C060/20 A§ | <4.9 A | No | Yes | ü | 1606-XLSDNET4 |
| 100…240V AC, 110…300V DC | Auto | 192 | 24 | 8 | 6 A SLOW BLOW FUSE OR 1489-A1C060/20 A§ | <7.6 A | Yes | No | ü | 1606-XLSDNET8 |
| 100…120/200…240V AC, 160…375V DC | Man. | 60 | 24 | 2.5 | 10 A SLOW BLOW FUSE OR 1489-A1C100/16 A§ | <18 A | Yes | NA | ü | 1606-XL60DR |
| 100…120/200…240V AC, 210…375V DC | Man. | 120 | 5 | 10 A SLOW BLOW FUSE OR 1489-A1C100/16 A§ | <11 A | Yes | Yes | ü | 1606-XL120DR | |
| 100…120/200…240V AC, 240…375V DC | Man. | 240 | 10 | 10 A SLOW BLOW FUSE OR 1489-A1C100/10 A§ | <21 A | Yes | No | ü | 1606-XL240DR | |
| 24V DC | — | 720 | Vin -.5V typ | 30 | N/A | N/AT | — | NA | — | 1606-XLRED20-30 |
| 24V DC | — | 960 | Vin -.6V typ | 40 | N/A | N/A§ | — | NA | — | 1606-XLRED40 |
| 10…60V DC | — | 384 | Vin 1 -.9V typ | 16Ø | N/A | N/A | — | NA | — | 1606-XLPRED |
| 10…60V DC | — | 480 | Vin 1 -.9V typ | 20Ø | N/A | N/A | — | — | — | 1606-XLSRED |
| 24…60V DC | — | 480 | Vin 1 -.9V typ | 20Ø | N/A | N/A | — | — | — | 1606-XLERED |
| — | Auto | 120 | 24…28 | 5 | 10 A SLOW BLOW FUSE OR 1489-A1C100/20 A§ | <3 A | Yes | — | — | 1606-XLE120EC |
| 100…240V AC, 110…300V DC | Auto | 240 | 24…28 | 10 | 6 A SLOW BLOW FUSE OR 1489-A1C060/20 A§ | <4 A | Yes | — | ü | 1606-XLS240EC |
| 400…500V AC, 450…820V DC | — | 240 | 24…28 | 10 | 6 A (X3) SLOW BLOW FUSE OR 1492-SP3C060/15 A§ | <3 A | Yes | — | — | 1606-XL240E-3C |
| — | Auto | 480 | 24…28 | 20 | 6 A (X3) SLOW BLOW FUSE OR 1492-SP3C060 | <15 A | Yes | — | ü | 1606-XLS480E-3C |
1606 Special Modules with UPS
| Input Voltage | Input Voltage Selector | Output Power [W] | Output Voltage | Output Current [A] | Input Circuit Protection | Inrush Current | Parallel Operation | Meets EN 61000-3-2 PFC Harmonics | DC OK Relay | Cat. No. | |
| 22.5…30V DC | — | 240 | 22.5…30 | 10 | N/A | — | — | — | — | z | 1606-XLS240-UPS |
| 24…28.8V DC | — | 480 | 23…27.8 | 20 | N/A | — | — | NA | — | 1606-XLBUFFER | |
T To be used alongside 20, 30, and 40 A power supplies.
Single/parallel operation (inclined characteristic) selectable (jumper).
§ To be used alongside 40 A power supplies (or smaller).
§ Unit has internal (not accessible/replaceable) input fuse. Additional protection is not required if used on branch circuits £ UL test levels.
Ø See product specifications for proper use.
z The 1606-XLS240-UPS is a charging module, used along side a power supply and a battery assembly, which must be ordered separately. (See Accessories below.)
Consult local codes and regulations for installation.