Power Supplies

Catalogs > Industrial Controls Catalog > Power Supplies > Switched Mode

Switched Mode

Introduction Certifications How to Select a Bulletin 1606 Power Supply Quick Guide Cat. No. Explanation
Product Selection 1606 Accessories Specifications Approximate Dimensions and Wire Size 1606-XL, 1606-XLBuffer, 1606-XLS DC UPS
Specifications

1606-XLS Performance Specifications

  Click to enlarge - 1606-XLS80E_graya Click to enlarge - 1606-XLS120E_graya Click to enlarge - 1606-XLS240E_graya Click to enlarge - 1606-XLS480E_graya Click to enlarge - 1606-XLS480E_graya
  1606-XLS80E 1606-XLS120E 1606-XLS240E and
1606-XLS240ECz 
1606-XLS480E 1606-XLS480E-3 and
1606-XLS480E-3Cz 
Output Volts/Watts 24…28V/80 W 24…28V/120 W 24…28V/240 W 24…28V/480 W 24…28V/480W
Input Voltage (47...63 Hz) 100…240V AC, 
110...300V DC
100…240V AC, 110...300V DC 100…240V AC, 110...300V DC 100…240V AC, 110...300V DC 380…480V AC, 600V DC
Operational Range 85…276V AC, 88…375V DC 85…264V AC, 88…360V DC 85…276V AC, 88…375V DC 85…276V AC, 88…375V DC 323…552V AC, 450…780V DC
Hold-up Time 27…174 ms 33…59 ms 27 ms 32…51 ms 19 ms
Rated Input Current 1.4 A (100V AC),
0.82 A (240V AC)
1.4 A (100V AC),
0.65 A (240V AC)
2.8 A (100V AC),
1.2 A (240V AC)
4.6 A (100V AC),
2.5 A (240V AC)
0.9 A (380V AC),
0.65 A (480V AC)
Efficiency typ. 90.0% typ. 92.7% typ. 91.8% typ. 92.4% typ. 94.8%
Output Voltage 24…28V 24…28V 24…28V 24…28V 24…28V
Rated Output Current 3.4 A (@ 24V)
3.0 A (@ 28V)
5 A (@ 24V)
4.5 A (@ 28V)
10 A (@ 24V)
9 A (@ 28V)
20 A (@ 24V)
17 A (@ 28V)
20 A (@ 24V)
17.5 A (@ 28V)
ReservePower (typ. 4 s) 5.4 A (@ 24V)
5.0 A (@ 28V)
7.5 A (@ 24V)
6.7 A (@ 28V)
15 A (@ 24V)
13.5 A (@ 28V)
30 A (@ 24V)
26 A (@ 28V)
30 A (@ 24V)
26 A (@ 28V)
Ripple/Noise <100 mVPP <50 mVPP <50 mVPP <100 mVPP <100 mVPP
Operating Temperature
Range (Tamb)
-25...+70 °C
>60 °C with derating
Non-Operating Temperature Range -40...+85 °C
MTBF§  >650 000 hours >831 000 hours >581 000 hours >469 000 hours >690 000 hours
Dimensions (W x H x D) 32 x 124 x 102 mm 40 x 124 x 117 mm 60 x 124 x 117 mm 84 x 124 x 127 mm 65 x 124 x 127 mm
Weight 420 g 620 g 900 g 1200 g 870 g
Certifications/Standards¬  1, 2, 3, 5, 6, 7
Special Features Active PFC; Class 1 Div. 2; Semi F47
  

  Click to enlarge - 1606-XLSDNET4a Click to enlarge - 1606-XLSDNET8a
  1606-XLSDNET4 1606-XLSDNET8
Output Volts/Watts 24V/91 W 24V/192 W
Input Voltage (47...63 Hz) 100…240V AC; 110...300V DC
Operational Range 85…264V AC 88…360V DC 85…276 V AC 88…375 V DC
Hold-up Time 43 ms (120V AC)
77 ms (240V AC)
38 ms (120V AC)
41 ms (240V AC)
Rated Input Current 1.1 A (100V AC)
0.5 A (240V AC)
2.3 A (100V AC)
1.0 A (240V AC)
Efficiency typ. 92.4% typ. 92.7%
Output Voltage 24V
Rated Output Current 3.8 A 8 A
Ripple/Noise < 50 mVpp
Operating Temperature
Range (Tamb)
-25...+70 °C
>60 °C with derating
Non-Operating Temperature Range -40...+85 °C
MTBF§  >581 000 hours >831 000 hours
Dimensions (W x H x D) 40 x 124 x 117 mm 60 x 124 x 117 mm
Weight 620 g 900 g
Certifications/Standards¬  1, 2, 3, 5, 6, 7
Special Features NEC Class 2 power supply; Active PFC; ODVA Approved; Class 1 Div. 2; Semi F47 Active PFC; ODVA Approved; Class 1 Div. 2; Semi F47
  

¬ 1) = CE, 2) = UL 508 (cULus LISTED), 3) = UL 1950 (cURus), 5) Safety standards = IEC/EN 60950, EN 50178, 6) EMC standards = EN 55011 (Class B), EN 55022 (Class B), EN 61000-6-2, 7) EMC standards = EN 61000-3-2 (A14), EN 50081-1
§ MTBF determined by Siemens norm SN 29500 at full load current and 40 °C
z Because these catalog numbers end with "C", it indicates these devices have conformal coating.


1606-XLE

           
  1606-XLE80E 1606-XLE120Ev  and
1606-XLE120ECz 
1606-XLE240Ev  1606-XLE240EP 1606-XLE240F
Output Volts/Watts 24V...28V/80 W 24V...28V/120 W 24V...28V/240 W 24V...28V/240 W 48V...52V/240 W
Input Voltage (47...63 Hz) 100...120V AC/200...240V AC
Operational Range 90...132V AC/180...264V AC
Hold-up Time >60 ms (120V)
>244 ms (240V)
>80 ms (120V)
>78 ms (240V)
>46 ms (120V)
>42 ms (240V)
Rated Input Current 20 A (100V AC)
45 A (240V AC)
2.6 A (100V AC)
1.3 A (240V AC)
5 A (100V AC)
2.5 A (240V AC)
Efficiency typ. 90% typ. 90% typ. 91% typ. 91% typ. 92%
Output Voltage 24...28V 48...52V
Rated Output Current 3.3 A @ 24V
2.9 A @ 28V
5 A @ 24V
4.3 A @ 28V
10 A @ 24V
8.6 A @ 28V
5 A @ 48V
4.6 A @ 52V
Ripple/Noise <50 mVPP
Operating Temperature
Range (Tamb)
-25...+70 °C, >60 °C with derating
Non-Operating Temperature Range -40...+85 °C
MTBF§  >700 000 hours
Dimensions (W x H x D) 32 x 124 x 102 mm 32 x 124 x 117 mm 60 x 124 x 117 mm
Weight 430 g 500 g 700 g 800 g 700 g
Certifications/Standards¬  1, 2, 3, 4, 5, 6, 7
Special Features NEC Class 2
  

¬ 1) = CE, 2) = UL 508 (cULus LISTED), 3) = UL 1950 (cURus), 4) = CSA C22.2, No. 107-1, 5) Safety standards = IEC/EN 60950, EN 50178, 6) EMC standards = EN 55011 (Class B), EN 55022 (Class B), EN 61000-6-2, 7) EMC standards = EN 61000-3-2 (A14), EN 50081-1
§ MTBF determined by Siemens norm SN 29500 at full load current and 40 °C
z Because this catalog number ends with C, it indicates the device has conformal coating.
v Available in regional voltages: add N to the end of the cat. no. for 90...132V, or add E to the end of the cat. no. for 180...264V.


1606-XLP Compact Specifications

        Click to enlarge - 1606-6-1a
  1606-XLP15A 1606-XLP15B 1606-XLP15E 1606-XLP25A
Output Volts/Watts 5...5.5V/15 W 12...15V/15 W 24...28V/15 W 5...5.5V/25 W
Input Voltage (47...63 Hz) 100...240V AC wide range; 85...370V DC
Operational Range 85...264V AC
Hold-up Time >168 ms (230V AC)
>45 ms (100V AC)
>191 ms (230V AC)
>46 ms (100V AC)
>196 ms (230V AC)
>47 ms (100V AC)
>170 ms (230V AC)
>19 ms (100V AC)
Rated Input Current <0.28 A (100V AC)
<0.17 A (196V AC)
<0.5 A (100V AC)
<0.35 A (196V AC)
Efficiency typ. >77% typ. >83% typ. >88% typ. >80%
Output Voltage 5...5.5V
5.1V preset
12...15V 24...28V 5...5.5V
5.1V preset
Rated Output Current 3 A 1.0...1.3 A 0.54...0.63 A 5 A (at 5.1V),
4.5 A (at 5.5V)
Ripple/Noise <50 mVpp <75 mVpp <50 mVpp <50 mVpp
Operating Temperature
Range (Tamb)
-10...+70 °C, >60 °C: 0.4 W/K derating -10...+70 °C
>60 °C: 0.5 W/K derating
Non-Operating Temperature Range -40...+85 °C
MTBF§  2 686 000 hours 3 811 000 hours 4 369 000 hours 600 000 hours
Dimensions (W x H x D) 22.5 x 75 x 91 mm 45 x 75 x 91 mm
Weight 130 g 240 g
Certifications/Standards¬  1, 2, 4, 5, 7
Special Features NEC Class 2 power supply; ABS/GL/RINA (Marine); Class 1 Div. 2
  

  Click to enlarge - 1606-6-3a Click to enlarge - 1606-6-5a Click to enlarge - 1606-6-7a Click to enlarge - 1606-6-9a
  1606-XLP30B 1606-XLP30E 1606-XLP36C 1606-XLP50B
Output Volts/Watts 10...12V/30 W 24...28V/30 W ±12V/±15V/36 W 12...15V/50 W
Input Voltage (47...63 Hz) 100...240V AC wide range; 85...375V DC 100...240V AC wide range; 85...375V DC 100...240V AC wide range; 85...375V DC
Operational Range 85...264V AC
Hold-up Time >170 ms (230V AC)
>18 ms (100V AC)
>190 ms (230V AC)
>19 ms (100V AC)
>180 ms (230V AC)
>18 ms (100V AC)
>170 ms (230V AC)
>17 ms (100V AC)
Rated Input Current <0.6 A (100V AC)
<0.25 A (240V AC)
<0.6 A (100V AC)
<0.35 A (196V AC)
<0.65 A (AC 100V AC)
<0.4 A (AC 196V AC)
<1.0 A (100V AC)
<0.6 A (196V AC)
Efficiency typ. 84% typ. 87.5% typ. 86% typ. 90%
Output Voltage 10...12V
12V preset (with jumper), 10...12V adjustable (without jumper)
24...28V
24.5V preset
±12V (without jumper),
±15V (with jumper)
±15V preset
12...15V
15V preset (with jumper) 12...15V adjustable (without jumper)
Rated Output Current 3 A (@ 10V),
2.5 A (@ 12V)
1.3 A (@ 24.5V),
1 A (@ 28V)
0...2.8 A (@ +12V),
0...1.4 A (@ -12V)
0...2.4 A (@ +15V),
0...1.4 A @ (-15V)
4.2 A (@ 12V),
3.4 A (@ 15V)
Ripple/Noise <10 mVpp <50 mVpp <50 mVpp <100mVpp
Operating Temperature
Range (Tamb)
-10...+70 °C
>60 °C: 0.6 W/K derating
-10...+70 °C
>60 °C: 0.5 W/K derating
-10...+70 °C
> 60 °C: 1 W/K derating
-10...+70 °C
>60 °C: 1 W/K derating
Non-Operating Temperature Range -10...+70 °C
>60 °C: 0.6 W/K derating
-10...+70 °C
>60 °C: 0.5 W/K derating
-10...+70 °C
> 60 °C: 1 W/K derating
-10...+70 °C
>60 °C: 1 W/K derating
MTBF§  appr. 650 000 hours 600 000 hours appr. 600 000 hours
Dimensions (W x H x D) 45 x 75 x 91 mm
Weight 250 g 230 g 240 g 260 g
Certifications/Standards¬  1, 2, 4, 5, 7
Special Features NEC Class 2 power supply; Class 1 Div. 2 NEC Class 2 power supply; Class 1 Div. 2; Semi F47 Output voltage adjustable:
DC ±12V without jumper
or DC ±15V with jumper;
NEC Class 2 power supply;
ABS/GL/RINA (Marine);
Class 1 Div. 2
Output voltage adjustable:
DC 12...15V without jumper or DC 15V with jumper;
NEC Class 2 power supply;
Class 1 Div. 2
  

¬ 1) = CE, 2) = UL 508 (cULus LISTED), 3) = UL 1950 (cURus), 4) = CSA C22.2, No. 60950, 5) Safety standards = IEC/EN 60950, EN 50178, 6) EMC standards = EN 55011 (Class B), EN 55022 (Class B), EN 61000-6-2, 7) EMC standards = EN 61000-3-2 (A14), EN 50081-1
§ MTBF determined by Siemens norm SN 29500 at full load current and 40 °C


  Click to enlarge - 1606-6-2a Click to enlarge - 1606-XLP50EZa Click to enlarge - 1606-6-4a Click to enlarge - 1606-6-6a Click to enlarge - 1606-XLP90Ba Click to enlarge - 1606-XLP90Ba
  1606-XLP50E 1606-XLP50EZ 1606-XLP50F 1606-XLP72E 1606-XLP90B 1606-XLP90E-2
Output Volts/Watts 24...28V/50 W 48...56V/50 W 24...28V/72 W 12...15V/90 W 24...28V/90 W
Input Voltage (47...63 Hz) 100...240V AC wide range; 85...375V DC 100...120/220...240V AC manual select; 220...375V DC 100...120/220...240V AC; 220...375V DC 2Æ, 380...480V AC
Operational Range 85...264V AC 85...132/184...264V AC 323..552V AC
Hold-up Time >171 ms (230V AC)
>17 ms (100V AC)
>170 ms (230V AC)
>17 ms (100V AC)
>40 ms (230V AC)
>25 ms (100V AC)
>40 ms (230V AC)
>20 ms (196V AC, 100V AC)
>52 ms (400V)
>93 ms (480V)
Rated Input Current <1.0 A (100V AC)
<0.6 A (196V AC)
<1.6 A (100V AC)
<0.8 A (220V AC)
<1.9 A <0.42 A (400V)
<0.36 A (480V)
Efficiency typ. 88.5% typ. 90% typ. 89% typ. 88.5% typ. 89%
Output Voltage 24...28V
24.5V preset
48...56V
48V preset
24...28V
24.5V preset (at 2.9 A)
12...15V
Preset at 12V
24...28V
Preset at 24.5V
Rated Output Current 2.1 A (@ 24.5V),
1.8 A (@ 28V)
1.05 A (@ 48V),
0.9 A (@ 56V)
3 A (@ 24V),
2.6 A (@ 28V)
7.5 A (@ 12V),
6 A (@ 15V)
3.75 A (@ 24V),
3.2 A (@ 28V)
Ripple/Noise <50 mVpp <200 mVpp <50 mVpp <50 mVpp <50 mVpp
Operating Temperature
Range (Tamb)
-10...+70 °C
>60 °C: 1 W/K derating
-10...+70 °C
>60 °C: 1.5 W/K derating
-10...+70 °C
>60 °C: 1 W/K derating
-10...+70 °C
>60 °C: 2 W/K derating
Non-Operating Temperature Range -40...+85 °C
MTBF§  appr. 600 000 hours appr. 600 000 hours appr. 500 000 hours appr. 500 000 hours
Dimensions (W x H x D) 45 x 75 x 91 mm 45 x 75 x 91 mm 73 x 75 x 103 mm 73 x 75 x 103 mm
Weight 240 g 260 g 360 g 360 g
Certifications/Standards¬  1, 2, 3, 4, 5, 6 1, 2, 3, 4, 5, 6 1, 2, 3, 4, 5, 6, 7 1, 2, 3, 4, 5, 6, 7
Special Features NEC Class 2 power supply;
ABS/GL/RINA (Marine);
Class 1 Div. 2;
Semi F47
Removeable Terminations;
NEC Class 2 power supply;
ABS/GL/RINA (Marine);
Class 1 Div. 2
NEC Class 2 power supply NEC Class 2 power supply;
ABS/GL/RINA (Marine);
Class 1 Div. 2
NEC Class 2 power supply;
ABS/GL/RINA (Marine);
Class 1 Div. 2
NEC Class 2 power supply
  

  Click to enlarge - 1606-6-8a Click to enlarge - 1606-6-8a Click to enlarge - 1606-6-8a Click to enlarge - 1606-6-8a
  1606-XLP95E 1606-XLP100E 1606-XLP100F 1606-XLP100E-2
Output Volts/Watts 24...28V/95 W 24...28V/100 W 48...56V/100 W 24...28V/100 W
Input Voltage (47...63 Hz) 100...120/220...240V AC auto select; 220...375V DC 2Æ, 380...480V AC
Operational Range 85...132/184...264V AC 323..552V AC
Hold-up Time >40 ms (230V AC)
>20 ms (100V AC)
>48 ms (400V)
>85 ms (480V)
Rated Input Current <2.0 A (100V AC)
<0.95 A (220V AC)
<2.1 A (100V AC)
<1.0 A (220V AC)
<0.46 A (400V)
<0.40 A (480V)
Efficiency typ. 90% typ. 91% typ. 89%
Output Voltage 24...28V
24.5V preset
48...56V
48V preset
24...28V
Preset at 24.5V
Rated Output Current 3.9 A (@ 24.5V),
3.2 A (@ 28V)
4.2 A (@ 24.5V),
3.6 A (@ 28V)
2.1 A (@ 48V),
1.8 A (@ 56V)
4.2 A (@ 24V),
3.6 A (@ 28V)
Power Boost
Ripple/Noise <50 mVpp <50 mVpp <50 mVpp <50 mVpp
Operating Temperature
Range (Tamb)
-10...+70 °C
>60 °C: 2 W/K derating
Non-Operating Temperature Range -40...+85 °C
MTBF§  appr. 500 000 hours
Dimensions (W x H x D) 73 x 75 x 103 mm
Weight 360 g
Certifications/Standards¬  1, 2, 3, 4, 5, 6, 7
Special Features NEC Class 2 power supply;
Class 1 Div. 2
Single/parallel operation (inclined characteristic) select on front panel;
ABS/GL/RINA (Marine);
Class 1 Div. 2;
Semi F47
Single/parallel operation (inclined characteristic) select on front panel;
ABS/GL/RINA (Marine)
  

¬ 1) = CE, 2) = UL 508 (cULus LISTED), 3) = UL 1950 (cURus), 4) = CSA C22.2, No. 60950, 5) Safety standards = IEC/EN 60950, EN 50178, 6) EMC standards = EN 55011 (Class B), EN 55022 (Class B), EN 61000-6-2, 7) EMC standards = EN 61000-3-2 (A14), EN 50081-1
§ MTBF determined by Siemens norm SN 29500 at full load current and 40 °C


1606-XL Single Phase Specifications

  Click to enlarge - 1606-7-1a Click to enlarge - 1606-XL180Ba Click to enlarge - 1606-7-4a Click to enlarge - 1606-7-6a Click to enlarge - 1606-7-7a Click to enlarge - 1606-7-9a
  1606-XL60D 1606-XL180B 1606-XL480EP 1606-XL480EPT 1606-XL480GP 1606-XL480F
Output Volts/Watts 24V/60 W 12...15V/180 W 24...28V/480 W 36...43V/480 W 48...56V/480 W
Input Voltage (47...63 Hz) 100...120/200...240V AC manual select;
160...375V DC
100...120/220...240V AC
240...375V DC
100...120/200...240V AC
Operational Range 85...132/176...264V AC 85...132/176...264V AC 85...132/184...264V AC
Hold-up Time >20 ms (196V AC) >81 ms (230V AC)
>84 ms (120V AC)
>45 ms (100V AC)
30 ms (120/230V AC) >27 ms (230V AC) 30 ms (230V AC)
Rated Input Current <1.3 A (115V)/<0.7A (230V) <5A (115V)/<2.3 A (230V) 10 A (115V)/5 A (230V)
Efficiency typ. 87.5% typ. >87% typ. 90.5% typ. 92% typ. 93%
Output Voltage 24V 12...15V
Preset at 12V
24...28V
Front panel potentiometer
36...43V
Front panel potentiometer
48...56V
Front panel potentiometer
Rated Output Current 2.5 A 15 A (@ 12V),
12 A (@ 15V)
20 A (@ 24V),
18 A (@ 28V)
13.3 A (@ 36V),
11.2 A (@ 43V)
10 A (@ 48V),
8.6 A (@ 56V)
Power Boost 18 A 25 A (22 A) 16.6 A (14 A) 12.5 A (10.7 A)
Ripple/Noise <25 mVpp <50 mVpp < 20 mVpp (single operation)
<40 mVpp (parallel operation)
<30 mVpp (single operation)
<80 mVpp (parallel operation)
<40 mVpp (single operation)
<80 mVpp (parallel operation)
Operating Temperature
Range (Tamb)
-10...+70 °C
>60 °C with derating
0...70 °C
>60 °C with derating
0...+70 °C
>60 °C with derating
Non-Operating Temperature Range -40...+85 °C 0...70 °C
>60 °C with derating
-40...+85 °C
MTBF§  740 000 hours <425 000 hours 519 000 hours
Dimensions (W x H x D) 49 x 124 x 102 mm 120 x 124 x 102 mm 220 x 124 x 102 mm
Weight 460 g 980 g 2500 g 1800 g
Certifications/Standards¬  1, 2, 3, 4, 5, 6, 7 1, 2, 3, 4, 5, 6 1, 2, 3, 4, 5, 6, 7 1, 2, 3, 4, 5, 6
Special Features NEC Class 2 power supply;
Semi F47
PFC choke; Overload behavior selectable; (hiccup/continuous current); ‡  PFC choke; ‡  Selectable single/parallel operation (inclined characteristic); PFC choke; ‡  ‡ 
  

¬ 1) = CE, 2) = UL 508 (cULus LISTED), 3) = UL 1950 (cURus), 4) = CSA C22.2, No. 60950, 5) Safety standards = IEC/EN 60950, EN 50178, 6) EMC standards = EN 55011 (Class B), EN 55022 (Class B), EN 61000-6-2, 7) EMC standards = EN 61000-3-2 (A14), EN 50081-1
‡ Low inrush current
§ MTBF determined by Siemens norm SN 29500 at full load current and 40 °C


1606-XL Three Phase Specifications

  Click to enlarge - 1606-8-1a Click to enlarge - 1606-8-2a Click to enlarge - 1606-9-1a Click to enlarge - 1606-9-2a Click to enlarge - 1606-9-3a Click to enlarge - 1606-9-4a
  1606-XL120E-3 1606-XL240E-3 and
1606-XL240E-3Cz 
1606-XL480F-3H 1606-XL720E-3 1606-XL960E-3 1606-XL960E-3S§ 
Output Volts/Watts 24...28V/120 W 24...28V/240 W 48...56V/480 W 24...28V/720 W 24...28V/960 W
Input Voltage (47...63 Hz) 3Æ, 400...500V AC wide range;
450...820V DC
3Æ, 400...500V AC wide range;
450...820V DC
3Æ, 400V AC;
450...700V DC
3Æ, 400...500V AC wide range;
450...820V DC
3Æ, 400...500V AC wide range
Operational Range 340...576V AC 340...479V AC 340...576V AC
Hold-up Time >16 ms (3Æ 400V AC)
>10 ms (2Æ 400V AC)
>24 ms (3Æ 400V AC)
>20 ms (2Æ 400V AC)
>11 ms >10 ms (3Æ 400V AC) >15 ms (3Æ 400V AC)
Rated Input Current 3 x 0.5 A 3 x 0.8/0.7 A @ 400/500V 3 x 1.5 A 3 x 2.0 A 3 x 3.0 A
Efficiency typ. 89% typ. 92% typ. 92% typ. 92.5% typ. 92.5%
Output Voltage 24...28V
24.5V preset
24...28V
24.5V preset
48...56V
48.1V preset
24...28V front panel potentiometer 24...28V
front panel potentiometer
Rated Output Current 5 A (@ 24V),
4.3 A (@ 28V)
10 A (@ 24V)
8.6 A (@ 28V)
10 A (@ 48V),
9 A (@ 56V)
30 A (@ 24V),
26 A (@ 28V)
40 A (@ 24V),
35 A (@ 28V)
Power Boost 6 A 12 A (up to 288 W) 12.5 A 33 A 45 A
Ripple/Noise <25 mVPP <30 mVPP <50 mVPP <20 mVPP (single operation)
<40 mVPP (parallel operation)
<50 mVPP
Operating Temperature
Range (Tamb)
-10...+70 °C
>60 °C with derating
0...+70 °C
>60 °C with derating
0...+70 °C
>60 °C with derating
Non-Operating Temperature Range -40...+85 °C -40...+85 °C
MTBF§  410 000 hours 543 000 hours (3Æ),
525 000 hours (2Æ)
310 000 hours 425 000 h @ 400V AC,
360 000 h @ 480V AC
305 000 hours 268 000 hours
Dimensions (W x H x D) 73 x 124 x 117 mm 89 x 124 x 117 mm 220 x 124 x 102 mm 240 x 124 x 112 mm 275 x 124 x 117 mm
Weight 730 g 980 g 1800 g 2000 g 3300 g
Certifications/Standards¬  1, 2, 3, 4, 5, 6, 7
Special Features PFC choke Overload behavior selectable (FUSE Mode/continuous current); 2-phase operation admissible, Single/parallel operation (inclined characteristic); PFC choke; ‡  Single/parallel operation (inclined characteristic) selectable (jumper); PFC choke; ‡  PFC choke; ‡  Single/parallel operation (inclined characteristic) selectable (jumper); passive load sharing; PFC choke; ‡  Parallel operation through active current sharing; Output signals (Power-Fail, Shut-Down, internal current measurement, overtemperature warning);
PFC choke; ‡ § 
  

¬ 1) = CE, 2) = UL 508 (cULus LISTED), 3) = UL 1950 (cURus), 4) = CSA C22.2, No. 60950, 5) Safety standards = IEC/EN 60950, EN 50178, 6) EMC standards = EN 55011 (Class B), EN 55022 (Class B), EN 61000-6-2, 7) EMC standards = EN 61000-3-2 (A14), EN 50081-1
‡ Low inrush current
§ MTBF determined by Siemens norm SN 29500 at full load current and 40 °C
z Because this catalog number ends with "C", it indicates the device has conformal coating.


"Shut Down" Input

Function: Turning the unit on or off using logic signal (remote monitoring).
Unit switches off when Input is connected to "Signal GND" terminal (DU £ 1V) or the input has a voltage of +20...28V with respect to the "Signal GND" terminal, (max. 20 mA).


"DC Ok" Output

Function: Indicating whether the unit is operating properly. Output can directly energize a relay or a control light.
Signaling: Output signal is at a "high" level (24V, current source) in normal operation (no overload, overheating, short circuit). When the output signal switches to "low" level (no power at output), Vout remains for 5 ms (nominal) at nominal load.
Connection (signal common): Connection is made with respect to the "Signal GND" terminal (signal output).
Important: Do not connect to the power output (terminals + and -).


Permissible load: resistance - min. 300 W, e.g. 24V relay, control lights (LEDs need no series resistance), Evaluation logic.
For 5V signal: In order to receive a 5V signal: switch a 5V Zener diode (0.5 W) and 1 kW resistance in parallel between this output and the "Signal GND" terminal.


"Thermal Alarm" Output

Function: Output gives warning shortly before and while overtemperature state occurs. Output can directly control a relay or a control light.
Signaling: Output signal is at a "high" level (24V, current source) in normal operation (no overtemperature). At overtemperature, the output switches to "low". Only when the temperature in the unit increases further will the unit reduce its output current (power output).
Connection and permissible load: same as for "DC ok" output.


"Current Monitor" Output

Function: Measuring the output current (power output). Output signal is proportional to the output current of the unit.
Connection: Made with respect to the "Signal GND" terminal (signal output).
Important: Do not connect to the power output (terminals + and -).
Signaling:
Voltage measuring: Voltage at signal output is 1V per 10 A output current (Ri(voltmeter) > 100 k ohm )
Current measurement: Current at signal output is 1 mA per 10 A output current (Ri(ammeter) < 100 W)


"Current Balance" In-/Output

Function: Using these terminals, parallel operating units ensure an equal load sharing (active balancing). Balancing also works reliably with decoupling diodes at the power output (redundancy).

Connection: Connect together "Current Balance" outputs of all units involved.
Important: Signal common here is the - terminal of the power output, not the "Signal GND". Do not connect the "Signal GND" terminals to each other!


"Signal GND" Terminal

Function: Grounding terminal for all signal terminals (not for "Current Balance").
Connection instructions: Do not connect this terminal with terminals + or - of the unit (not even over a load: risk of overload). Do not connect this terminal with terminals of other units (not even with the "Signal GND" terminal of another unit).
Permissible load: Maximum current load: 0.3 A. Terminal is fused internally with a self-healing fuse (polyswitch).


Click to enlarge - 1606-9-5


Click to enlarge - 1606-9-6


Special Modules

1606-XL Special Modules

  Click to enlarge - 1606-10-1a Click to enlarge - 1606-XLS240E_graya Click to enlarge - 1606-XLS240E-3_4c Click to enlarge - 1606-10-9a Click to enlarge - 1606-10-2a
  Buffer Module UPS DC/DC Converter N+1 Redundancy N+1 Redundancy
  1606-XLBUFFER 1606-XLS240-UPS 1606-XLDC40A 1606-XL60DR 1606-XL120DR
Output Volts/Watts 22.5V...27.8V/480 W 22.5V...30V/240 W DC 5.1V ±1% 24V/60 W 24V/120 W
Input Voltage (47...63 Hz) 24V DC (24...28.8V DC) 24V DC (22.5...30V DC) 18...36V DC 100...120V/200...240V AC manual select;
160...375V DC
100...120/200...240V AC manual select;
210...375V DC
Operational Range 23...35V DC 22.5...30V DC 18...36V DC 85...132/176...264V AC
Hold-up Time >0.2 s (20 A) battery dependent >10 ms (DC 24 Vin) >20 ms (AC 196V) >37 ms (AC 196V)
Rated Input Current charging current
<600 mA
<0.12 A (standby)
<1.3 A (charging)
<2.9 A/<1.5 A <1.3 A (115V)/<0.7 A (230V) <2.6 A (115V)/<1.4 A (230V)
Efficiency N/A N/A typ. 82% typ. 86.5% typ. 89%
Output Voltage Vin -1V: 23...27.8V
22.5V fixed
22.4V 5.1V DC ±1%
selectable 4.5...5.5V
24V 24V
Rated Output Current 0...20 A 10 A 8 A 2.5 A 5 A
Power Boost 15 A 6 A
Ripple/Noise <200 mVPP <50 mVPP <30 mVPP <30 mVPP
Operating Temperature
Range (Tamb)
-10...+70 °C
>60 °C with derating
-25...+60 °C 0...+70 °C
>60 °C with derating
-10...+70 °C
>60 °C with derating
-10...+70 °C
>60 °C with derating
Non-Operating Temperature Range -40...+85 °C -40...+85 °C
MTBF§  480 000 hours 510 000 hours 700 000 hours 480.000 hours
Dimensions (W x H x D) 64 x 124 x 102 mm 49 x 124 x 117 49 x 124 x 102 mm 49 x 124 x 102 mm 64 x 124 x 102 mm
Weight 740 g 530 g 470 g 470 g 620 g
Certifications/Standards¬  1, 2, 3, 5, 6 1, 2, 3, 5, 6 1, 5, 6 1, 2, 3, 5, 6 1, 2, 3, 5, 6, 7
Special Features Selectable buffered voltage; ‡  Inhibit replacement battery buffering MOSFET inverse battery protection; ‡  RDY relay contact;
N+1 redundancy;
plug connectors;
NEC Class 2 power supply
RDY relay contact;
N+1 redundancy;
plug connectors
  

¬ 1) = CE, 2) = UL 508 (cULus LISTED), 3) = UL 1950 (cURus), 5) Safety standards = IEC/EN 60950, EN 50178, 6 EMC standards = EN 55011 (Class B), EN 55022 (Class B), EN 61000-6-2, 7) = EMC standards = EN 61000-3-2 (A14), EN 50081-1
‡ Low inrush current
§ MTBF determined by Siemens norm SN 29500 at full load current and 40 °C


  Click to enlarge - 1606-10-4a Click to enlarge - 1606-10-6a Click to enlarge - 1606-10-8a Click to enlarge - 1606-XLPPREDa Click to enlarge - 1606-XLSRED_gs Click to enlarge - 1606-XLSRED_gs
  N+1 Redundancy N+1 Redundancy N+1 Redundancy N+1 Redundancy N+1 Redundancy
  1606-XL240DR 1606-XLRED20-30 1606-XLRED40 1606-XLPRED 1606-XLSRED 1606-XLERED
Output Volts/Watts 24V/240 W 30 A Dual redundancy module 40 A Single redundancy module 10 A Dual redundancy 20 A Dual redundancy
Input Voltage (47...63 Hz) AC 100...120/200...240V manual select;
DC 240...375V
DC 24V (max. 35V) DC 10...60V DC 10...60V
Operational Range 85...132/176...264 V AC 18...36 V DC 10...60V DC 10...60V DC
Hold-up Time >25 ms (AC 196V)
Rated Input Current <6 A (115V)/<2.8 A (230V) 20...30 A (max. 35 A) 0...40 A (max. 50 A) Single input: 10 A max.
Dual input: 16 A max. total
Single input: 20 A max.
Dual input: 20 A max. total
Efficiency typ. 89% typ. >97% typ. >97%
Output Voltage 24V Vin -0.5V typ. Vin -0.6V typ. Vin -0.9V typ. Vin -0.9V typ.
Rated Output Current 10 A 20...30 A (max. 35 A) 0...40 A (max. 50 A) 0...10 A 0...20 A
Power Boost 12 A
Ripple/Noise <30 mVPP
Operating Temperature
Range (Tamb)
0...+70 °C
>60 °C with derating
-10 °C...+70 °C -40 °C...+70 °C
>60 °C with derating
-25 °C...+70 °C
>60 °C with derating
Non-Operating Temperature Range -40...+85 °C
MTBF§  390.000 hours
Dimensions (W x H x D) 120 x 124 x 102 mm 48 x 124 x 102 mm 48 x 124 x 117 mm 45 x 75 x 91 mm 32 x 124 x 102 mm 32 x 124 x 117 mm
Weight 980 g 625 g 646 g 136 g 290 g 350 g
Certifications/Standards¬  1, 2, 3, 5, 6 1, 2, 3, 6 1, 2, 3, 6 1, 2, 3, 6
Special Features RDY relay contact;
N+1 redundancy;
plug connectors
Dual redundancy module for 2x35 A; N+1 redundancy Single redundancy module for 2.5-50 A; N+1 redundancy Redundancy for DC 10...60V applications;
ABS/GL/RINA (Marine);
Class 1 Div. 2
Redundancy for DC 10...60V applications;
Class 1 Div. 2
Redundancy for DC 10...60V applications;
Class 1 Div. 2;
DC OK
  

¬ 1) = CE, 2) = UL 508 (cULus LISTED), 3) = UL 1950 (cURus), 5) Safety standards = IEC/EN 60950, EN 50178, 6 EMC standards = EN 55011 (Class B), EN 55022 (Class B), EN 61000-6-2, 7) = EMC standards = EN 61000-3-2 (A14), EN 50081-1
§ MTBF determined by Siemens norm SN 29500 at full load current and 40 °C