Catalogs > Industrial Controls Catalog > Power Supplies > Control Transformers > Bulletin 1497 — Global Control Transformers
Bulletin 1497 — Global Control Transformers
| Introduction | Standards Compliance and Certifications | Catalog Number Explanation | Product Selection | Approximate Dimensions |
Bulletin 1497 Multi‑Tap Transformers
| 1497 | | A | | M1 | | 3 | | N |
| a | b | c | d |
| a | b | c | d | ||||||||
| VA Rating | Primary and Secondary Voltage | Fuse Block Options§ | Factory Installed Options | ||||||||
| Code | Description | Code | Primary | Secondary | Code | Block Options | Code | Description | |||
| A | 63 VA | M1 | 240V, 208V | 120V (60 Hz) | 0 | 0 Primary, 0 Secondary | N | No Fusing, No Cover | |||
| B | 80 VA | M2 | 240V, 208V | 24V (60 Hz) | 1 | 0 Primary, 1 Secondary | |||||
| C | 130 VA | M3 | 240V, 208V | 24V, 120V (60 Hz) | 2 | 2 Primary, 0 Secondary | |||||
| D | 200 VA | M4 | 415V, 400V, 380V | 115X230V (50 Hz) | 3 | 2 Primary, 1 Secondary | |||||
| E | 250 VA | M5 | 415V, 400V, 380V | 24V (50 Hz) | |||||||
| F | 350 VA | ||||||||||
| G | 500 VA | ||||||||||
| H | 750 VA | ||||||||||
| J | 800 VA | ||||||||||
| K | 1000 VA | ||||||||||
| L | 1600 VA | ||||||||||
| M | 2000 VA | ||||||||||
Bulletin 1497 Transformers
| 1497 | | A | | BADX | | 3 | | N |
| a | b | c | d |
| a | b | c | d | ||||||||
| VA Rating | Primary and Secondary Voltage | Fuse Block Options§ | Factory Installed Options | ||||||||
| Code | Description | Code | Primary | Secondary | Code | Block Options | Code | Description | |||
| A | 63 VA | HX | 208V (60 Hz) | — | 0 | 0 Primary, 0 Secondary | N | No Fusing, No Cover | |||
| B | 80 VA | AX | 240V (60 Hz), 220V (50 Hz) |
— | 1 | 0 Primary, 1 Secondary | |||||
| C | 130 VA | BAØ | 240X480V (60 Hz), 220X440V (50 Hz) |
— | 2 | 2 Primary, 0 Secondary | |||||
| D | 200 VA | CXT | 600V (60 Hz), 550V (50 Hz) |
— | 3 | 2 Primary, 1 Secondary | |||||
| E | 250 VA | DX | — | 120V (60 Hz) | |||||||
| F | 350 VA | JX | — | 24V (60 Hz) | |||||||
| G | 500 VA | SX | — | 120V (60 Hz), 110V (50Hz) |
|||||||
| H | 750 VA | JK | — | 24V (50 Hz), 26V (60 Hz) |
|||||||
| J | 800 VA | ||||||||||
| K | 1000 VA | ||||||||||
| L | 1600 VA | ||||||||||
| M | 2000 VA | ||||||||||
¬ When the primary voltage code BA is selected and a 120V AC secondary is desired, the secondary voltage code SX should be selected.
T VA rating codes G, H, or J with primary voltage over 500V have only cULus approval.
Not available for use with primary voltage code BA.
§ VA rating codes H…M are only available with no fuse block option (0).