1609-P Industrial

Product Overview


Click to enlarge - 1609-P_fam


Bulletin 1609-P Series — Industrial Uninterruptible Power Supply


Standards Compliance and Certifications

Standards Compliance

UL 1778
CE
CSA C22.2, No. 107
FCC


Certifications

UL Listed (File No. E190749, Guide YEDU)
CSA Certified (File LR1234)


Overview

The Bulletin 1609-P has multiple options for remote management. Please see Introduction for details.

Catalog Number Explanation

1609 P    3000    N
      a    b    c

a
Power Supply Type
Code Description
P Double Conversion Online Uninterruptible Power Supply

b
Rated Output Power
Code Description
3000 3000VA (2100 W)
5000 5000VA (3500 W)
8000 8000VA (6400 W)
10000 10000VA (8000 W)

c
Input/Output Voltage
Code Description
N 120V AC
E 208/230V AC
A 230V AC

Product Selection

Build a Catalog Number


Output Power Input Voltage Cat. No.
3000VA (2100 W) 120V AC 1609-P3000N
3000VA (2100 W) 230V AC 1609-P3000A
5000VA (3500 W) 208/230V AC 1609-P5000E
8000VA (6400 W) 208/230V AC 1609-P8000E
10000VA (8000 W) 208/230V AC 1609-P10000E
  

Accessories

Description Cat. No.
Network management card (Standard on units 5 kVA and larger) 1609-NMC
Remote start cable 1609-RSC
Replacement battery 1609-PBAT
External battery pack 1609-PXBP
5000VA CCT (120V step down transformer) 1609-5000CCT
Rail kit 1609-PRK1
Hardwire kit (for 3 and 5 kVA units) 1609-HDK1
Service bypass switch (16 kVA) 1609-PSB1
  

Specifications

Electrical Ratings 1609-P3000N 1609-P3000A 1609-P5000E 1609-P8000E 1609-P10000E
Input V nom. (V AC) 120 230 208/230 208/230 208/230
Voltage Range, default (V AC) 90…150V 160…280V
Current (A) 20 nom., 28 max. 11 nom., 14 max. 19 nom., 24 max. 30 nom., 40 max. 39 nom., 48 max.
Capacity 3000VA (2100 W) 5000VA (3500 W) 8000VA (6400 W) 10 000VA (8000 W)
Frequency 45…65 Hz (self sensing)
PFC > 0.95
Protection N/A N/A N/A 70 A input circuit breaker
Output V nom. 120V 208V
Capacity 3000VA (2100 W) 5000VA (3500 W) 8000VA (6400 W) 10 000VA (8000 W)
Protection 3…15 A circuit breaker N/A N/A
On Battery Frequency Nominal +/- 3 Hz
Reg. +/- 2% static
+/- 5% dynamic
+/- 1% static, +/- 5% dynamic
THD <5% at full load
Crest Factor 3:01
Efficiency On Battery 86%
On Line 88%
Protection Surge IEC 1000-4-4
Overload 125% : 1 minute, 150% : 30 seconds
Output Short Input circuit breakers and/or premises branch protection
Thermal Protection Yes
Bypass N/A 70 A input circuit breaker
Regulatory Safety UL 1778, cULus, IEC 60950 EN 61000-3-2 UL 1778, cULus, IEC 60950
EMC FCC (Class A) EN50091-2 FCC (Class A), EN50091-2
Markings cULus, CSA CE cULus, CSA, CE
Battery Pack Run Time 14 minutes @ full load, 34 minutes @ half load 5…7 minutes @ full load, 13…18 minutes @ half load
Type Sealed Lead Acid, valve regulated, hot swappable, user replaceable
Voltage 192V
Charger Temperature compensated current limited, float charger
Recharge Time Less than 3 hours to 90% capacity Less than 3 hours to 85% capacity
Lifetime 2…4 years @ 25 °C ambient
Environment Temperature 0…40 °C (operating), -20…60 °C (short term storage)
Altitude 10 000 ft (operating)
Humidity 0…95% non-condensing (operating)
Heat Output (Full Load) 655 BTU/hour 1040 BTU/hour 1536 BTU/hour 2216 BTU/hour
Audible Noise <50 dB @ 1 meter (full load) <55 dB @ 1 meter (full load)
Rear Panel AC Outlets (6) NEMA 5…15
(2) NEMA 5…20
(8) IEC C13
(2) IEC C19
(12) IEC C13
(2) IEC C19
AC Inlets NEMA L5…30 IEC C14 IEC C20 3 position terminal blocks
Communication DB9 Serial and Contact Closures
EPO Via Contact Closure
Network Via Network Management Card (1609-NMC, provided as standard with units >3 KVA)
Indicators and Controls LED Status On-line, In Bypass Mode, On Battery, Overload and Replace Battery, Fault, Bar graph for Load, Bar graph for Battery Fuel Gauge, Bar graph for Measured Input Voltage when recessed switch is held
Control (Front panel) On/self-test/alarm silence/cold start/load off
Audible On Battery: 4 short beeps repeats about 20 seconds (mutable), Low Battery: persistent 0.5 second beep every 1 second (mutable), In Bypass: continuous beeping, Failure: continuous tone, Replace Battery: occasional on/off change - single beep
  

Click to enlarge - attention color
  • Wiring of the UPS should be performed by a qualified electrician. Use appropriate size wires.
  • In 230V AC applications, the UPS must be protected with a circuit breaker that complies with European standards for branch rated protection per the country of installation.
  • In 208V AC applications, the UPS must be protected by a dual-pole, 10 A branch rated, UL 489 circuit breaker.
  • The 120V AC 1609-P3000N has supplementary circuit breaker protection. The unit should be protected by a single-pole, 15 A branch rated, UL 489 circuit breaker.
    Allen-Bradley part number 1492-MCAA115 is suggested.
  • The branch circuit breaker must be off prior to wiring the unit.

  • Notes

    208V AC applications: The 1609-P5000E, 1609-P8000E, and 1609-P10000E, ship ready for 230V AC sources. When operating one of these in 208V AC applications, the UPS low transfer voltage settings are adjusted through the PowerChute® software or the Network Management Card.

    Refer to the PowerChute® User Guide or the Network Management Card instructions for details.


    Approximate Dimensions and Shipping Weights

    Approximate dimensions are shown in millimeters (in.) unless otherwise indicated. Dimensions are not to be used for manufacturing purposes.

    Click to enlarge - 1609_p3000n_dim


    Click to enlarge - 1609_p8000e_dim


    Approximate Shipping Weights

    Output Power Input Voltage Cat. No. Approx. Shipping Weight
    [kg (lb)]
    3000VA (2100 W) 120V AC 1609-P3000N 63.5 (140)
    3000VA (2100 W) 230V AC 1609-P3000A 63.5 (140)
    5000VA (3500 W) 208/230V AC 1609-P5000E 63.5 (140)
    8000VA (6400 W) 208/230V AC 1609-P8000E 128.8 (284)
    10000VA (8000 W) 208/230V AC 1609-P10000E 128.8 (284)
      

    Approximate dimensions are shown in millimeters (in.) unless otherwise indicated. Dimensions are not to be used for manufacturing purposes.

    Click to enlarge - 1609_pbat_dim


    Click to enlarge - 1609_pxbp_dim


    Click to enlarge - 1609_5000cct_dim


    Approximate Shipping Weights

    Description Cat. No. Approx. Shipping Weight
    [kg (lb)]
    Replacement battery 1609-PBAT 37.2 (82)
    External battery pack 1609-PXBP 101.2 (223)
    5000VA CCT (120V step down transformer) 1609-5000CCT 63.5 (140)
    Rail kit 1609-PRK1 3.6 (8)