1609-P Industrial
| Product Overview |
|
Bulletin 1609-P Series — Industrial Uninterruptible Power Supply
- Rugged industrial design
- Tower/rack compatible
- Extended runtime
- Battery management system
- Hot-swappable batteries
- Comprehensive network management
- Remote monitoring/configuration
- Double conversion online
- Pure sine wave output
- Frequency and voltage regulation
- Automatic internal bypass
Standards Compliance and Certifications
Standards Compliance
UL 1778
CE
CSA C22.2, No. 107
FCC
Certifications
UL Listed (File No. E190749, Guide YEDU)
CSA Certified (File LR1234)
Overview
The Bulletin 1609-P has multiple options for remote management. Please see Introduction for details.
Catalog Number Explanation
| 1609 | | P | 3000 | N | ||
| a | b | c |
| a | |
| Power Supply Type | |
| Code | Description |
| P | Double Conversion Online Uninterruptible Power Supply |
| b | |
| Rated Output Power | |
| Code | Description |
| 3000 | 3000VA (2100 W) |
| 5000 | 5000VA (3500 W) |
| 8000 | 8000VA (6400 W) |
| 10000 | 10000VA (8000 W) |
| c | |
| Input/Output Voltage | |
| Code | Description |
| N | 120V AC |
| E | 208/230V AC |
| A | 230V AC |
Product Selection
| Build a Catalog Number |
| Output Power | Input Voltage | Cat. No. |
| 3000VA (2100 W) | 120V AC | 1609-P3000N |
| 3000VA (2100 W) | 230V AC | 1609-P3000A |
| 5000VA (3500 W) | 208/230V AC | 1609-P5000E |
| 8000VA (6400 W) | 208/230V AC | 1609-P8000E |
| 10000VA (8000 W) | 208/230V AC | 1609-P10000E |
Accessories
| Description | Cat. No. |
| Network management card (Standard on units 5 kVA and larger) | 1609-NMC |
| Remote start cable | 1609-RSC |
| Replacement battery | 1609-PBAT |
| External battery pack | 1609-PXBP |
| 5000VA CCT (120V step down transformer) | 1609-5000CCT |
| Rail kit | 1609-PRK1 |
| Hardwire kit (for 3 and 5 kVA units) | 1609-HDK1 |
| Service bypass switch (16 kVA) | 1609-PSB1 |
Specifications
| Electrical Ratings | 1609-P3000N | 1609-P3000A | 1609-P5000E | 1609-P8000E | 1609-P10000E | |
| Input | V nom. (V AC) | 120 | 230 | 208/230 | 208/230 | 208/230 |
| Voltage Range, default (V AC) | 90…150V | 160…280V | ||||
| Current (A) | 20 nom., 28 max. | 11 nom., 14 max. | 19 nom., 24 max. | 30 nom., 40 max. | 39 nom., 48 max. | |
| Capacity | 3000VA (2100 W) | 5000VA (3500 W) | 8000VA (6400 W) | 10 000VA (8000 W) | ||
| Frequency | 45…65 Hz (self sensing) | |||||
| PFC | > 0.95 | |||||
| Protection | N/A | N/A | N/A | 70 A input circuit breaker | ||
| Output | V nom. | 120V | 208V | |||
| Capacity | 3000VA (2100 W) | 5000VA (3500 W) | 8000VA (6400 W) | 10 000VA (8000 W) | ||
| Protection | 3…15 A circuit breaker | N/A | N/A | |||
| On Battery | Frequency | Nominal +/- 3 Hz | ||||
| Reg. | +/- 2% static +/- 5% dynamic |
+/- 1% static, +/- 5% dynamic | ||||
| THD | <5% at full load | |||||
| Crest Factor | 3:01 | |||||
| Efficiency | On Battery | 86% | ||||
| On Line | 88% | |||||
| Protection | Surge | IEC 1000-4-4 | ||||
| Overload | 125% : 1 minute, 150% : 30 seconds | |||||
| Output Short | Input circuit breakers and/or premises branch protection | |||||
| Thermal Protection | Yes | |||||
| Bypass | N/A | 70 A input circuit breaker | ||||
| Regulatory | Safety | UL 1778, cULus, IEC 60950 | EN 61000-3-2 | UL 1778, cULus, IEC 60950 | ||
| EMC | FCC (Class A) | EN50091-2 | FCC (Class A), EN50091-2 | |||
| Markings | cULus, CSA | CE | cULus, CSA, CE | |||
| Battery Pack | Run Time | 14 minutes @ full load, 34 minutes @ half load | 5…7 minutes @ full load, 13…18 minutes @ half load | |||
| Type | Sealed Lead Acid, valve regulated, hot swappable, user replaceable | |||||
| Voltage | 192V | |||||
| Charger | Temperature compensated current limited, float charger | |||||
| Recharge Time | Less than 3 hours to 90% capacity | Less than 3 hours to 85% capacity | ||||
| Lifetime | 2…4 years @ 25 °C ambient | |||||
| Environment | Temperature | 0…40 °C (operating), -20…60 °C (short term storage) | ||||
| Altitude | 10 000 ft (operating) | |||||
| Humidity | 0…95% non-condensing (operating) | |||||
| Heat Output (Full Load) | 655 BTU/hour | 1040 BTU/hour | 1536 BTU/hour | 2216 BTU/hour | ||
| Audible Noise | <50 dB @ 1 meter (full load) | <55 dB @ 1 meter (full load) | ||||
| Rear Panel | AC Outlets | (6) NEMA 5…15 (2) NEMA 5…20 |
(8) IEC C13 (2) IEC C19 |
(12) IEC C13 (2) IEC C19 |
||
| AC Inlets | NEMA L5…30 | IEC C14 | IEC C20 | 3 position terminal blocks | ||
| Communication | DB9 | Serial and Contact Closures | ||||
| EPO | Via Contact Closure | |||||
| Network | Via Network Management Card (1609-NMC, provided as standard with units >3 KVA) | |||||
| Indicators and Controls | LED Status | On-line, In Bypass Mode, On Battery, Overload and Replace Battery, Fault, Bar graph for Load, Bar graph for Battery Fuel Gauge, Bar graph for Measured Input Voltage when recessed switch is held | ||||
| Control | (Front panel) On/self-test/alarm silence/cold start/load off | |||||
| Audible | On Battery: 4 short beeps repeats about 20 seconds (mutable), Low Battery: persistent 0.5 second beep every 1 second (mutable), In Bypass: continuous beeping, Failure: continuous tone, Replace Battery: occasional on/off change - single beep | |||||
- Wiring of the UPS should be performed by a qualified electrician. Use appropriate size wires.
- In 230V AC applications, the UPS must be protected with a circuit breaker that complies with European standards for branch rated protection per the country of installation.
- In 208V AC applications, the UPS must be protected by a dual-pole, 10 A branch rated, UL 489 circuit breaker.
- The 120V AC 1609-P3000N has supplementary circuit breaker protection. The unit should be protected by a single-pole, 15 A branch rated, UL 489 circuit breaker.
Allen-Bradley part number 1492-MCAA115 is suggested.
- The branch circuit breaker must be off prior to wiring the unit.
Notes
208V AC applications: The 1609-P5000E, 1609-P8000E, and 1609-P10000E, ship ready for 230V AC sources. When operating one of these in 208V AC applications, the UPS low transfer voltage settings are adjusted through the PowerChute® software or the Network Management Card.
Refer to the PowerChute® User Guide or the Network Management Card instructions for details.
Approximate Dimensions and Shipping Weights
Approximate dimensions are shown in millimeters (in.) unless otherwise indicated. Dimensions are not to be used for manufacturing purposes.
|
|
Approximate Shipping Weights
| Output Power | Input Voltage | Cat. No. | Approx. Shipping Weight [kg (lb)] |
| 3000VA (2100 W) | 120V AC | 1609-P3000N | 63.5 (140) |
| 3000VA (2100 W) | 230V AC | 1609-P3000A | 63.5 (140) |
| 5000VA (3500 W) | 208/230V AC | 1609-P5000E | 63.5 (140) |
| 8000VA (6400 W) | 208/230V AC | 1609-P8000E | 128.8 (284) |
| 10000VA (8000 W) | 208/230V AC | 1609-P10000E | 128.8 (284) |
Approximate dimensions are shown in millimeters (in.) unless otherwise indicated. Dimensions are not to be used for manufacturing purposes.
|
|
|
Approximate Shipping Weights
| Description | Cat. No. | Approx. Shipping Weight [kg (lb)] |
| Replacement battery | 1609-PBAT | 37.2 (82) |
| External battery pack | 1609-PXBP | 101.2 (223) |
| 5000VA CCT (120V step down transformer) | 1609-5000CCT | 63.5 (140) |
| Rail kit | 1609-PRK1 | 3.6 (8) |