Catalogs > Industrial Controls Catalog > Power Supplies > Uninterruptible Power Supply > 1609-P Industrial
1609-P Industrial
| Introduction | Standards Compliance and Certifications | Introduction | Catalog Number Explanation |
| Product Selection | Accessories | Specifications | Approximate Dimensions and Shipping Weights |
| Electrical Ratings | 1609-P3000N | 1609-P3000A | 1609-P5000E | 1609-P8000E | 1609-P10000E | |
| Input | V nom. (V AC) | 120 | 230 | 208/230 | 208/230 | 208/230 |
| Voltage Range, default (V AC) | 90…150V | 160…280V | ||||
| Current (A) | 20 nom., 28 max. | 11 nom., 14 max. | 19 nom., 24 max. | 30 nom., 40 max. | 39 nom., 48 max. | |
| Capacity | 3000VA (2100 W) | 5000VA (3500 W) | 8000VA (6400 W) | 10 000VA (8000 W) | ||
| Frequency | 45…65 Hz (self sensing) | |||||
| PFC | > 0.95 | |||||
| Protection | N/A | N/A | N/A | 70 A input circuit breaker | ||
| Output | V nom. | 120V | 208V | |||
| Capacity | 3000VA (2100 W) | 5000VA (3500 W) | 8000VA (6400 W) | 10 000VA (8000 W) | ||
| Protection | 3…15 A circuit breaker | N/A | N/A | |||
| On Battery | Frequency | Nominal +/- 3 Hz | ||||
| Reg. | +/- 2% static +/- 5% dynamic |
+/- 1% static, +/- 5% dynamic | ||||
| THD | <5% at full load | |||||
| Crest Factor | 3:01 | |||||
| Efficiency | On Battery | 86% | ||||
| On Line | 88% | |||||
| Protection | Surge | IEC 1000-4-4 | ||||
| Overload | 125% : 1 minute, 150% : 30 seconds | |||||
| Output Short | Input circuit breakers and/or premises branch protection | |||||
| Thermal Protection | Yes | |||||
| Bypass | N/A | 70 A input circuit breaker | ||||
| Regulatory | Safety | UL 1778, cULus, IEC 60950 | EN 61000-3-2 | UL 1778, cULus, IEC 60950 | ||
| EMC | FCC (Class A) | EN50091-2 | FCC (Class A), EN50091-2 | |||
| Markings | cULus, CSA | CE | cULus, CSA, CE | |||
| Battery Pack | Run Time | 14 minutes @ full load, 34 minutes @ half load | 5…7 minutes @ full load, 13…18 minutes @ half load | |||
| Type | Sealed Lead Acid, valve regulated, hot swappable, user replaceable | |||||
| Voltage | 192V | |||||
| Charger | Temperature compensated current limited, float charger | |||||
| Recharge Time | Less than 3 hours to 90% capacity | Less than 3 hours to 85% capacity | ||||
| Lifetime | 2…4 years @ 25 °C ambient | |||||
| Environment | Temperature | 0…40 °C (operating), -20…60 °C (short term storage) | ||||
| Altitude | 10 000 ft (operating) | |||||
| Humidity | 0…95% non-condensing (operating) | |||||
| Heat Output (Full Load) | 655 BTU/hour | 1040 BTU/hour | 1536 BTU/hour | 2216 BTU/hour | ||
| Audible Noise | <50 dB @ 1 meter (full load) | <55 dB @ 1 meter (full load) | ||||
| Rear Panel | AC Outlets | (6) NEMA 5…15 (2) NEMA 5…20 |
(8) IEC C13 (2) IEC C19 |
(12) IEC C13 (2) IEC C19 |
||
| AC Inlets | NEMA L5…30 | IEC C14 | IEC C20 | 3 position terminal blocks | ||
| Communication | DB9 | Serial and Contact Closures | ||||
| EPO | Via Contact Closure | |||||
| Network | Via Network Management Card (1609-NMC, provided as standard with units >3 KVA) | |||||
| Indicators and Controls | LED Status | On-line, In Bypass Mode, On Battery, Overload and Replace Battery, Fault, Bar graph for Load, Bar graph for Battery Fuel Gauge, Bar graph for Measured Input Voltage when recessed switch is held | ||||
| Control | (Front panel) On/self-test/alarm silence/cold start/load off | |||||
| Audible | On Battery: 4 short beeps repeats about 20 seconds (mutable), Low Battery: persistent 0.5 second beep every 1 second (mutable), In Bypass: continuous beeping, Failure: continuous tone, Replace Battery: occasional on/off change - single beep | |||||
Notes
208V AC applications: The 1609-P5000E, 1609-P8000E, and 1609-P10000E, ship ready for 230V AC sources. When operating one of these in 208V AC applications, the UPS low transfer voltage settings are adjusted through the PowerChute® software or the Network Management Card.
Refer to the PowerChute® User Guide or the Network Management Card instructions for details.