Uninterruptible Power Supply

Catalogs > Industrial Controls Catalog > Power Supplies > Uninterruptible Power Supply > 1609-P Industrial

1609-P Industrial

Introduction Standards Compliance and Certifications Introduction Catalog Number Explanation
Product Selection Accessories Specifications Approximate Dimensions and Shipping Weights
Specifications

Electrical Ratings 1609-P3000N 1609-P3000A 1609-P5000E 1609-P8000E 1609-P10000E
Input V nom. (V AC) 120 230 208/230 208/230 208/230
Voltage Range, default (V AC) 90…150V 160…280V
Current (A) 20 nom., 28 max. 11 nom., 14 max. 19 nom., 24 max. 30 nom., 40 max. 39 nom., 48 max.
Capacity 3000VA (2100 W) 5000VA (3500 W) 8000VA (6400 W) 10 000VA (8000 W)
Frequency 45…65 Hz (self sensing)
PFC > 0.95
Protection N/A N/A N/A 70 A input circuit breaker
Output V nom. 120V 208V
Capacity 3000VA (2100 W) 5000VA (3500 W) 8000VA (6400 W) 10 000VA (8000 W)
Protection 3…15 A circuit breaker N/A N/A
On Battery Frequency Nominal +/- 3 Hz
Reg. +/- 2% static
+/- 5% dynamic
+/- 1% static, +/- 5% dynamic
THD <5% at full load
Crest Factor 3:01
Efficiency On Battery 86%
On Line 88%
Protection Surge IEC 1000-4-4
Overload 125% : 1 minute, 150% : 30 seconds
Output Short Input circuit breakers and/or premises branch protection
Thermal Protection Yes
Bypass N/A 70 A input circuit breaker
Regulatory Safety UL 1778, cULus, IEC 60950 EN 61000-3-2 UL 1778, cULus, IEC 60950
EMC FCC (Class A) EN50091-2 FCC (Class A), EN50091-2
Markings cULus, CSA CE cULus, CSA, CE
Battery Pack Run Time 14 minutes @ full load, 34 minutes @ half load 5…7 minutes @ full load, 13…18 minutes @ half load
Type Sealed Lead Acid, valve regulated, hot swappable, user replaceable
Voltage 192V
Charger Temperature compensated current limited, float charger
Recharge Time Less than 3 hours to 90% capacity Less than 3 hours to 85% capacity
Lifetime 2…4 years @ 25 °C ambient
Environment Temperature 0…40 °C (operating), -20…60 °C (short term storage)
Altitude 10 000 ft (operating)
Humidity 0…95% non-condensing (operating)
Heat Output (Full Load) 655 BTU/hour 1040 BTU/hour 1536 BTU/hour 2216 BTU/hour
Audible Noise <50 dB @ 1 meter (full load) <55 dB @ 1 meter (full load)
Rear Panel AC Outlets (6) NEMA 5…15
(2) NEMA 5…20
(8) IEC C13
(2) IEC C19
(12) IEC C13
(2) IEC C19
AC Inlets NEMA L5…30 IEC C14 IEC C20 3 position terminal blocks
Communication DB9 Serial and Contact Closures
EPO Via Contact Closure
Network Via Network Management Card (1609-NMC, provided as standard with units >3 KVA)
Indicators and Controls LED Status On-line, In Bypass Mode, On Battery, Overload and Replace Battery, Fault, Bar graph for Load, Bar graph for Battery Fuel Gauge, Bar graph for Measured Input Voltage when recessed switch is held
Control (Front panel) On/self-test/alarm silence/cold start/load off
Audible On Battery: 4 short beeps repeats about 20 seconds (mutable), Low Battery: persistent 0.5 second beep every 1 second (mutable), In Bypass: continuous beeping, Failure: continuous tone, Replace Battery: occasional on/off change - single beep
  

Click to enlarge - attention color
  • Wiring of the UPS should be performed by a qualified electrician. Use appropriate size wires.
  • In 230V AC applications, the UPS must be protected with a circuit breaker that complies with European standards for branch rated protection per the country of installation.
  • In 208V AC applications, the UPS must be protected by a dual-pole, 10 A branch rated, UL 489 circuit breaker.
  • The 120V AC 1609-P3000N has supplementary circuit breaker protection. The unit should be protected by a single-pole, 15 A branch rated, UL 489 circuit breaker.
    Allen-Bradley part number 1492-MCAA115 is suggested.
  • The branch circuit breaker must be off prior to wiring the unit.

  • Notes

    208V AC applications: The 1609-P5000E, 1609-P8000E, and 1609-P10000E, ship ready for 230V AC sources. When operating one of these in 208V AC applications, the UPS low transfer voltage settings are adjusted through the PowerChute® software or the Network Management Card.

    Refer to the PowerChute® User Guide or the Network Management Card instructions for details.