1609-S Industrial

Product Overview


Click to enlarge - 1609-S35ONS_L


Bulletin 1609-S Series — Industrial Uninterruptible Power Supply


Standards Compliance and Certifications

Standards Compliance

UL 1778
CE
CSA C22.2, No. 107
FCC


Certifications

UL Listed (File No. E190749, Guide YEDU)
CSA Certified (File LR1234)


Catalog Number Explanation

1609 S    350    N    S
      a    b    c    d

a
Power Supply Type
Code Description
S Line Interactive, Panel Mount Uninterruptible Power Supply

b
Rated Output Power
Code Description
350 350VA (280 W)

c
Output Voltage
Code Description
N 120V AC
E 208/230V AC

d
Battery Type
Code Description
S 40 °C Battery

Product Selection

Build a Catalog Number


Output Power Input Voltage Cat. No.
350VA (280 W) 120V AC 1609-S350NS
350VA (280 W) 208/230V AC 1609-S350ES
  

Accessories

Description Output Power Cat. No.
40 °C replacement battery 500VA (325 W) 1609-500SBAT
Remote start cable 1609-RSC
DIN Rail kit 1609-SDK1
Dry contact I/O communication cable 1609-SDC1
  

Specifications

  1609-S350NS 1609-S350ES
Input Wiring Touch-proof terminal block
Nominal Voltage 120V 208/230V
Voltage Range, Default 81…143V 160…287V
Voltage Range, Widest, On Line 75…153V 150…300V
Nominal Current 2.9 A 1.5 A
Capacity 350VA/280 W
Frequency 47…63 Hz
PFC None, load power factor is reflected in the input line current
On Line Output Wiring Touch-proof terminal block
Nominal Voltage 120V 208/230V
Voltage Range, Default 106…127V 208…253V
Voltage Range, Widest, On Line 97…136V 196…265V
Transfer Point Accuracy +/- (2% of transfer voltage + 1.3) +/- (2% of transfer voltage + 2.6)
Overload Protection Alarm at 107% of rated load input circuit breaker Alarm at 107% of rated load
Premises branch protection 10 A or less
Efficiency 96% @ 100% resistive load
Surge Protection Per EN50091-2
On Battery Output Frequency Nominal +/- 3 Hz (Locked), Nominal +/- 0.5 Hz (Free-running)
THD < 5% at full (linear) load
Voltage Regulation +/- 5%, + 5…-15% after low battery warning
Crest Factor 2.5:1
Efficiency 77% @ 100% resistive load
Overload Protection Overload indication and shutdown @ 107% of rate load or electronic current limit and shutdown under short circuit condition
Battery Pack Run Time 12 minutes (full load)
24 minutes (50% full load)
Type Sealed lead acid, valve-regulated hot-swappable, user-replaceable
Voltage 24V
Charger Temperature-compensated, current-limited, float charger
Recharge Time Less than 3 hours to 90% capacity
Lifetime 3…5 years @ 25 °C ambient
Lifetime cut in half for every 10 °C above 25 °C
Environment Temperature 0…40 °C (operating), -15…45 °C (short-term storage)
Altitude 10 000 ft (operating)
Humidity 0…95% non-condensing (operating)
Heat Output On line, full load: 137 BTU per hour
On line, full load, charging: 190 BTU per hour
On battery, full load: 1706 BTU per hour
Audible Noise <45 dB @ 1 m (full load)
Communication Serial Serial RS232 DB-9
Options Dry contact I/O communication cable
Indicators and Controls Status LEDs On line (green)
AVR low line (yellow)
AVR high line (yellow)
On battery (yellow)
Overload and fault (red)
Bad battery (red)
Load percentage of full rating bar graph (green)
Battery state of charge bar graph (green)
Measured input voltage indicated by load bar graph when recessed switch is held
Control Buttons On/self-test/alarm silence/cold start
Output off
Audible Alarms On Battery: 4 short beeps repeats about 20 seconds (mute capability)
Low Battery: persistent 0.5 second beep every 1 second (mute capability)
Disconnected Battery: continual chirping
Failure: continuous tone
Replace Battery: occasional
On/off change: single beep
  

Click to enlarge - attention color
  • Wiring of the UPS should be performed by a qualified electrician. Use appropriate size wires.
  • In 230V AC applications, the UPS must be protected with a circuit breaker that complies with European standards for branch rated protection per the country of installation.
  • In 208V AC applications, the UPS must be protected by a dual-pole, 10 A branch rated, UL 489 circuit breaker.
  • The 120V AC 1609-S350NS has supplementary circuit breaker protection. The unit should be protected by a single-pole, 15 A branch rated, UL 489 circuit breaker.
    Allen-Bradley part number 1492-MCAA115 is suggested.
  • The branch circuit breaker must be off prior to wiring the unit.

  • Approximate Dimensions and Shipping Weights

    Approximate dimensions are shown in millimeters (in.) unless otherwise indicated. Dimensions are not to be used for manufacturing purposes.

    Click to enlarge - Power Supply


    Approximate Shipping Weights

    Cat. No. Approx. Shipping Weight
    [kg (lb)]
    1609-S350NS 13.15 (29)
    1609-S350ES 13.15 (29)