Uninterruptible Power Supply

Catalogs > Industrial Controls Catalog > Power Supplies > Uninterruptible Power Supply > 1609-S Industrial

1609-S Industrial

Introduction Standards Compliance and Certifications Catalog Number Explanation Product Selection Accessories Specifications Approximate Dimensions and Shipping Weights
Specifications

  1609-S350NS 1609-S350ES
Input Wiring Touch-proof terminal block
Nominal Voltage 120V 208/230V
Voltage Range, Default 81…143V 160…287V
Voltage Range, Widest, On Line 75…153V 150…300V
Nominal Current 2.9 A 1.5 A
Capacity 350VA/280 W
Frequency 47…63 Hz
PFC None, load power factor is reflected in the input line current
On Line Output Wiring Touch-proof terminal block
Nominal Voltage 120V 208/230V
Voltage Range, Default 106…127V 208…253V
Voltage Range, Widest, On Line 97…136V 196…265V
Transfer Point Accuracy +/- (2% of transfer voltage + 1.3) +/- (2% of transfer voltage + 2.6)
Overload Protection Alarm at 107% of rated load input circuit breaker Alarm at 107% of rated load
Premises branch protection 10 A or less
Efficiency 96% @ 100% resistive load
Surge Protection Per EN50091-2
On Battery Output Frequency Nominal +/- 3 Hz (Locked), Nominal +/- 0.5 Hz (Free-running)
THD < 5% at full (linear) load
Voltage Regulation +/- 5%, + 5…-15% after low battery warning
Crest Factor 2.5:1
Efficiency 77% @ 100% resistive load
Overload Protection Overload indication and shutdown @ 107% of rate load or electronic current limit and shutdown under short circuit condition
Battery Pack Run Time 12 minutes (full load)
24 minutes (50% full load)
Type Sealed lead acid, valve-regulated hot-swappable, user-replaceable
Voltage 24V
Charger Temperature-compensated, current-limited, float charger
Recharge Time Less than 3 hours to 90% capacity
Lifetime 3…5 years @ 25 °C ambient
Lifetime cut in half for every 10 °C above 25 °C
Environment Temperature 0…40 °C (operating), -15…45 °C (short-term storage)
Altitude 10 000 ft (operating)
Humidity 0…95% non-condensing (operating)
Heat Output On line, full load: 137 BTU per hour
On line, full load, charging: 190 BTU per hour
On battery, full load: 1706 BTU per hour
Audible Noise <45 dB @ 1 m (full load)
Communication Serial Serial RS232 DB-9
Options Dry contact I/O communication cable
Indicators and Controls Status LEDs On line (green)
AVR low line (yellow)
AVR high line (yellow)
On battery (yellow)
Overload and fault (red)
Bad battery (red)
Load percentage of full rating bar graph (green)
Battery state of charge bar graph (green)
Measured input voltage indicated by load bar graph when recessed switch is held
Control Buttons On/self-test/alarm silence/cold start
Output off
Audible Alarms On Battery: 4 short beeps repeats about 20 seconds (mute capability)
Low Battery: persistent 0.5 second beep every 1 second (mute capability)
Disconnected Battery: continual chirping
Failure: continuous tone
Replace Battery: occasional
On/off change: single beep